2021-11-10 16:15:411ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21100004
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COVER SHEET: PLEASE REFERENCE THE ASHRAE 62.1- 2016
 AS THIS IS THE EDITION REFERENCED IN THE 2020 FBC
 MECHANICAL CODE.
  
 2) PLEASE PROVIDE A DETAIL OF THE ROOF CONDENSING UNIT
 STAND AND THE APPLIANCE TIE DOWN METHOD. FBC 107.2.1
  
 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH
 USE OF SPACE FOR THESE TENANT SPACES. FBC M 403.3.1.1
 AND TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  