2021-11-20 17:35:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO LOAD CALCULATION SHOWN PLEASE SHOW HOW
 DISTRIBUTION WAS SIZED. 215.5
  
 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE AUTHORITY
 HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS
 SHALL BE
 PROVIDED PRIOR TO THE INSTALLATION OF THE FEEDERS. SUCH
 A DIAGRAM SHALL SHOW THE AREA IN SQUARE FEET OF THE
 BUILDING OR
 OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL
 CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS, THE
 DEMAND FACTORS USED,
 THE CALCULATED LOAD AFTER APPLYING DEMAND FACTORS, AND
 THE SIZE AND TYPE OF CONDUCTORS TO BE USED.
  
  
 2) POWER PLAN DOES NOT SHOW OUTLETS IN INDIVIDUAL
 OFFICES. THEY ARE SHOWN IN THE DETAILS PLEASE INDICATE
 OR COME UP WITH A SCHEDULE OF OFFICES AND WHAT TYPE OF
 POWER REQUIREMENTS ARE TO BE SUPPLIED.
  
 3) SEVERAL CONFERENCE ROOMS ARE SHOWN WHICH WILL HAVE
 TO MEET THE REQUIREMENTS OF 210.71(A)(B)
  
 210.71 MEETING ROOMS.
 (A) GENERAL. EACH MEETING ROOM OF NOT MORE THAN 93 M2
 (1000 FT2) IN OTHER THAN DWELLING UNITS SHALL HAVE
 OUTLETS FOR
 NONLOCKING-TYPE, 125-VOLT, 15- OR 20-AMPERE
 RECEPTACLES. THE OUTLETS SHALL BE INSTALLED IN
 ACCORDANCE WITH 210.71(B). WHERE
 A ROOM OR SPACE IS PROVIDED WITH MOVABLE PARTITION(S),
 EACH ROOM SIZE SHALL BE DETERMINED WITH THE PARTITION
 IN THE POSITION
 THAT RESULTS IN THE SMALLEST SIZE MEETING ROOM.
 INFORMATIONAL NOTE NO. 1: FOR THE PURPOSES OF THIS
 SECTION,
 MEETING ROOMS ARE TYPICALLY DESIGNED OR INTENDED FOR
 THE GATHERING OF SEATED OCCUPANTS FOR SUCH PURPOSES AS
 CONFERENCES,
 DELIBERATIONS, OR SIMILAR PURPOSES, WHERE PORTABLE
 ELECTRONIC EQUIPMENT SUCH AS COMPUTERS, PROJECTORS, OR
 SIMILAR EQUIPMENT
 IS LIKELY TO BE USED. INFORMATIONAL NOTE NO. 2:
 EXAMPLES OF ROOMS THAT ARE NOT MEETING ROOMS INCLUDE
 AUDITORIUMS, SCHOOLROOMS,
 AND COFFEE SHOPS.
 (B) RECEPTACLE OUTLETS REQUIRED. THE TOTAL NUMBER OF
 RECEPTACLE OUTLETS, INCLUDING FLOOR OUTLETS AND
 RECEPTACLE OUTLETS IN
 FIXED FURNITURE, SHALL NOT BE LESS THAN AS DETERMINED
 IN (1) AND (2). THESE RECEPTACLE OUTLETS SHALL BE
 PERMITTED TO BE LOCATED AS
 DETERMINED BY THE DESIGNER OR BUILDING OWNER. (1)
 RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE OUTLETS
 SHALL
 BE INSTALLED IN ACCORDANCE WITH 210.52(A)(1) THROUGH
 (A)(4). (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM
 THAT IS AT LEAST
 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF AT
 LEAST 20 M2 (215 FT2) SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET LOCATED IN THE
 FLOOR AT A DISTANCE NOT LESS THAN 1.8 M (6 FT) FROM ANY
 FIXED WALL FOR EACH 20 M2 (215 FT2) OR MAJOR PORTION OF
 FLOOR SPACE.
  
 4) SAME AS NOTE TWO FOR THE DATA AND PHONE WIRING.
 SEPARATE PERMIT REQUIRED
  
 5) FAULT CURRENT CALCULATIONS REQUIRED FOR THE
 DISTRIBUTION SYSTEM ON 17 AND 18. 110.9, 110.10
  
 110.9 INTERRUPTING RATING. EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT FAULT LEVELS SHALL HAVE AN
 INTERRUPTING RATING AT NOMINAL
 CIRCUIT VOLTAGE AT LEAST EQUAL TO THE CURRENT THAT IS
 AVAILABLE AT THE LINE TERMINALS OF THE EQUIPMENT.
  
  
 6) RISER NOTE SHALL BE REQUIIRED ON PLAN TO SHOW WHERE
 POWER IS RECEIVED FROM FOR ALL PANELS ON THE 17TH AND
 18TH FLOORS PER 408.4(B)
  
 408.4(B) SOURCE OF SUPPLY. ALL SWITCHBOARDS,
 SWITCHGEAR, AND PANELBOARDS SUPPLIED BY A FEEDER(S) IN
 OTHER THAN ONE- OR TWO-FAMILY
 DWELLINGS SHALL BE PERMANENTLY MARKED TO INDICATE EACH
 DEVICE OR EQUIPMENT WHERE THE POWER ORIGINATES. THE
 LABEL SHALL BE
 PERMANENTLY AFFIXED, OF SUFFICIENT DURABILITY TO
 WITHSTAND THE ENVIRONMENT INVOLVED, AND NOT HANDWRITTEN