| Plan Review Notes For Permit 21100004 |
| Permit Number |
21100004 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-19 14:14:39 | OFFICE BUILD OUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE DETAILS FOR THE RAISED FLOOR (NON | | | CUMBUSTIBLE) PER FBC 603.1 | | | | | | 2) FLOOR PLAN FOR THE 17TH FLOOR DOES NOT SHOW THE FIRE | | | RATED WALLS PER SCHEDULE MARKINGS. - PLEASE CLARIFY THE | | | FIRE RATED WALLS. | | | | | | 3) PLEASE SHOW THE HOURLY FIRE RATING AND THE FIRE | | | RATING PROTECTION TYPE FOR THE STEEL STAIR AND LANDING | | | CONSTRUCTION PER FBC 601 | | | | | | 4) FLOOR PLAN FOR THE 17TH FLOOR DOES NOT SHOW A RATED | | | ELEVATOR LOBBY - ARE THE ELEVATOR HOIST WAYS | | | PRESSURIZED? - PLEASE SHOW THE ELEVATOR HOIST WAY | | | PROTECTION PER FBC 3006.3 | | | | | | 5) PLEASE SHOW THE DOORS LOCATED IN THE FIRE RATED | | | WALLS TO BE FIRE RATED PER FBC 716 | | | | | | 6) PLEASE SHOW THE FIRE RATED DOORS TO BE SELF CLOSING | | | AND LATCHING PER FBC 716.5.9 | | | | | | 7) ACCESSIBLE RESTROOMS - PLEASE SHOW THE LOCATION | | | DIMENSIONS FOR THE TOILET GRAB BARS, FIXTURE CLEAR | | | FLOOR SPACE, TOILET PAPER DISPENSER, MIRRORS ETC PER | | | FBC ACCESSIBILITY CHAPTER 6. | | | | | | 8) PLEASE SHOW THE FLOOR RAMP SLOPES AND ANY REQUIRED | | | RAMP HAND RAILS PER FBC ACCESSIBILITY 405 |
|