Plan Review Notes
Plan Review Notes For Permit 21100004
Permit Number 21100004
Review Stop B
Sequence Number 1
Notes
Date Text
2021-11-19 14:14:39OFFICE BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE DETAILS FOR THE RAISED FLOOR (NON
 CUMBUSTIBLE) PER FBC 603.1
  
 2) FLOOR PLAN FOR THE 17TH FLOOR DOES NOT SHOW THE FIRE
 RATED WALLS PER SCHEDULE MARKINGS. - PLEASE CLARIFY THE
 FIRE RATED WALLS.
  
 3) PLEASE SHOW THE HOURLY FIRE RATING AND THE FIRE
 RATING PROTECTION TYPE FOR THE STEEL STAIR AND LANDING
 CONSTRUCTION PER FBC 601
  
 4) FLOOR PLAN FOR THE 17TH FLOOR DOES NOT SHOW A RATED
 ELEVATOR LOBBY - ARE THE ELEVATOR HOIST WAYS
 PRESSURIZED? - PLEASE SHOW THE ELEVATOR HOIST WAY
 PROTECTION PER FBC 3006.3
  
 5) PLEASE SHOW THE DOORS LOCATED IN THE FIRE RATED
 WALLS TO BE FIRE RATED PER FBC 716
  
 6) PLEASE SHOW THE FIRE RATED DOORS TO BE SELF CLOSING
 AND LATCHING PER FBC 716.5.9
  
 7) ACCESSIBLE RESTROOMS - PLEASE SHOW THE LOCATION
 DIMENSIONS FOR THE TOILET GRAB BARS, FIXTURE CLEAR
 FLOOR SPACE, TOILET PAPER DISPENSER, MIRRORS ETC PER
 FBC ACCESSIBILITY CHAPTER 6.
  
 8) PLEASE SHOW THE FLOOR RAMP SLOPES AND ANY REQUIRED
 RAMP HAND RAILS PER FBC ACCESSIBILITY 405