| 2022-03-23 07:50:32 | NEW 8 STORY R2 |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) THE REVISED LS DRAWINGS HAVE RED LINES ON THE WALLS |
| | - WHAT DOES THE RED LINES MEAN? - WALL HOURLY FIRE |
| | RATINGS ARE NOT CLEARLY SHOWN - FLOOR PLANS SHOW SOME |
| | BUT NOT ALL OF THE FIRE WALL RATINGS - LS PLANS DO NOT |
| | SHOW THE MECHANICAL (STORAGE) AND ELECTRICAL (STORAGE |
| | ROOM) WALL RATINGS BETWEEN UNITS. |
| | |
| | 2) CORRIDOR REQUIRES A FIRE RATING TO BE CONTINUOUS - |
| | SOME OF THE STORAGE ROOMS (ELECTRIC/MECHANICAL) DO NOT |
| | SHOW THE CORRIDOR WALLS AND DOORS TO BE RATED - FBC |
| | 1020.6 |
| | |
| | 3) 20 MINUTE FIRE RATED DOORS IN THE CORRIDORS DO NOT |
| | SHOW AS SELF CLOSING ON THE DOOR SCHEDULE - PLEASE SHOW |
| | FIRE RATED DOORS TO BE SELF CLOSING AND SELF LATCHING - |
| | FBC 716.5.9 |
| | |
| | 4) DRAWING AT-05 - TOILET REAR GRAB BAR CANNOT BE |
| | REDUCED TO 24 INCHES FOR THE COMMON AREA - ANSI FIG. 30 |
| | A117.1 1986 |
| | |
| | 5) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT |
| | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF |
| | THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |