2022-03-02 10:13:1802/25/22 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. DONE.
  
 2. DONE.
  
 3. ON SHEET AT-05A;
  
 A. DONE.
  
 B. DONE.
  
 C. DONE.
  
 D. DONE.
  
 E. NOT DONE TO NEW LOCATION AS DESCRIBED DOES NOT MATCH
 YOU REQUEST OR YOUR RESPONSE. WOULD YOU PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 ON THAT SAME DRAWING FOR THE ACCESSIBLE WATER FOUNTAIN,
 IT SHOWS KNEE AND TOE CLEARANCES OF 2'-4" BUT NEEDS TO
 BE AT 2'-3". THE SPOUT HEIGHTS WOULD ALSO BE REQUIRED
 PER THE 2020 FBC ACC SEC. 306, 307, & 602.2, COMPLIANCE
 WITH 2020 FBC ACC SEC. 307.2 PROTRUSION LIMITS. WOULD
 YOU PLEASE SHOW THE WATER CLOSET FLUSH CONTROL LOCATION
 PER THE 2020 FBC SEC. 604.6 FLUSH CONTROLS? HANDICAP
 WATER CLOSET FLUSH CONTROL SHALL BE HAND OPERATED OR
 AUTOMATIC AND SHALL BE 36" INCHES MAXIMUM ABOVE THE
 FINISH FLOOR PER THE 2020 FBC ACC SEC. 604.9.5.
  
 4. DONE.
  
 5. ON SHEET A3-01;
  
 A. DONE.
  
 B. DONE.
  
 C. DONE.
  
 D. DONE.
  
 E. DONE.
  
 6. ON SHEET A3-08;
  
 A. DONE.
  
 B. DONE.
  
 7. DONE.
  
 8. ON SHEET A8-01A;
  
 A. UNDER THE FAIR HOUSING DESIGN MANUAL, PLEASE LABEL
 THE TYPE OF UNIT FOR (A) OR (B) CONFIGURATION PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 NEW COMMENT, THE RESPOND IS NOTED BUT PLEASE LABEL AS
 SPECIFICATION B ON PLANS.
  
 B. DONE
  
 C. DONE.
  
 D. DONE,
  
 9. ON SHEET A8-01A.1;
  
 A. DONE
  
 B. DONE
  
 C. DONE.
  
 D. ON GENERAL NOTES # 6 REFERS TO BATHROOM CABINETRY
 DETAILS, AND THE SHEET NUMBER IS UNAVAILABLE. ALSO, THE
 CABINET NEEDS TO BE 34" PER SPECIFICATION (B) PER THE
 FAIR HOUSING DESIGN MANUAL. WOULD YOU PLEASE CORRECT
 DETAIL 5 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
 FOR THIS PAGE AND THE COMMENTS 10-14, PLEASE CORRECT ON
 THESE PAGES. WOULD YOU PLEASE CHANGE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 10. ON SHEETS A8-01B AND A8-01B.1, PLEASE REFER TO THE
 COMMENTS ABOVE.
  
 11. ON SHEETS A8-01C AND A8-01C.1, PLEASE REFER TO THE
 COMMENTS ABOVE.
  
 12. ON SHEETS A8-01D AND A8-01D.1, PLEASE REFER TO THE
 COMMENTS ABOVE.
  
 13. ON SHEETS A8-01E AND A8-01E.1, PLEASE REFER TO THE
 COMMENTS ABOVE.
  
 14. ON SHEETS A8-01F AND A8-01F.1, PLEASE REFER TO THE
 COMMENTS ABOVE.
  
 15. ON SHEET A8-02A;
  
 A. UNDER THE FAIR HOUSING DESIGN MANUAL, PLEASE LABEL
 THE TYPE OF UNIT FOR (A) OR (B) CONFIGURATION PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 IN REFERENCE TO THE COMMENTS, PLEASE LABEL THE PAGE FOR
 SPECIFICATION B PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. IT SHOWS TWO BATHROOMS THAT LOOK LIKE SPECIFICATION
 B, AND ONLY ONE NEEDS TO COMPLY WITH TYPE B. IF THIS IS
 WHAT WILL TAKE PRECEDENCE, PLEASE CHANGE. WOULD YOU
 PLEASE SHOW ONE AND LABEL IT PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 NEW COMMENT, PLEASE NOTE ON THIS PAGE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. ON GENERAL NOTES, # 6 REFERS TO BATHROOM CABINETRY
 DETAILS, AND THE SHEET NUMBER IS UNAVAILABLE. WOULD YOU
 PLEASE RESPOND TO THE REFERENCE # TO PAGE A8-18? WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. DONE
  
 E. DONE.
  
 F. DONE.
  
 16. ON SHEET A8-02A.1;
  
 A. DONE.
  
 B. DONE.
  
 C. IT SHOWS ELEVATION FOR CABINET, AND IT SEEMS THAT
 THESE ARE B TYPE UNITS. WOULD YOU PLEASE SHOW THE 34"
 TO THE TOP OF THE CABINET FOR THE CORRESPONDING DETAIL?
 A REFERENCE TO ANOTHER PAGE WILL NOT CORRECT THE
 COMMENT. WOULD YOU PLEASE CORRECT THIS PAGE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. ON GENERAL NOTES, # 6 REFERS TO BATHROOM CABINETRY
 DETAILS, AND THE SHEET NUMBER IS UNAVAILABLE. PLEASE
 PROVIDE THE RESPONSE THE REFERENCE # TO PAGE A8-18.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 17. ON SHEETS A8-02B AND A8-02B.1, PLEASE REFER TO THE
 COMMENTS ABOVE.
  
 18. ON SHEETS A8-02C AND A8-01C.1, PLEASE REFER TO THE
 COMMENTS ABOVE.
  
 19. ON SHEETS A8-03A AND A8-03#A.1, PLEASE REFER TO THE
 COMMENTS ABOVE.
  
 20. DONE.
 21. ON SHEET A8-40;
  
 A. DONE.
  
 22. ON SHEETS E1-08 AND E1-08 A, IT SHOWS AN OVERLAY
 OVER THE RESTROOM AND THE SINKS. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
 THE RESPONSE REFERS TO E3-02, AND IT IS STILL
 INCORRECT. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 23. ON SHEET P0-00;
  
 A. DONE.
  
 B. DONE.
  
 C. DONE.
  
 24. ON SHEET P0-01;
  
 A. DONE.
  
 B. DONE.
  
 C. DONE.
  
 D. DONE.
  
 E. DONE.
  
 F. DONE.
  
 H. DONE.
  
 25. ON SHEET P0-02;
  
 A. WOULD YOU PLEASE SHOW AND LABEL ALL PIPE VENTED
 THROUGH THE ROOF FOR THIS PAGE PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 B. THERE ARE EXPANSION FITTING; PLEASE PROVIDE THE
 STANDARD FOR THE TYPE OF MATERIAL USED PER THE 2020 FBC
 TABLE 702.4 PIPE FITTINGS. WOULD YOU PLEASE PROVIDE THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS? A TEST TEE
 MAY BE REQUIRED ABOVE EACH FITTING IF AGREED FOR
 TESTING PURPOSES. WOULD YOU PLEASE SHOW ON ISOMETRIC?
  
 THE CHIEF PLUMBING INSPECTOR REVIEWED THIS ITEM, AND
 THIS IS HIS COMMENT.
  
 FOR WOOD FRAME CONSTRUCTION, YES. FOR CONCRETE/STEEL
 CONSTRUCTION, THEY WOULD NEED TO STATE THE NEED FOR IT.
 PER THESE MANUFACTURER?S INSTRUCTIONS, THIS PRODUCT IS
 ONLY REQUIRED FOR WOOD FRAME. THERE ARE SOME CASES
 WHERE IT IS NEEDED FOR CONCRETE/STEEL CONSTRUCTION, BUT
 THEY WOULD NEED TO STATE THE NEED AND USE OF THE
 PRODUCT SPECIFICALLY FOR EACH APPLICATION. TYPICALLY
 THEY CAN SHOW THAT THE MANUFACTURER OF THE PVC OR CPVC
 REQUIRES EXPANSION CONTROL. CPVC CAN ONLY RUN SO FAR IN
 A STRAIGHT LINE UNTIL IT GETS AN EXPANSION LOOP, BUT
 THAT IS FOR CPVC. (PER MANUFACTURER?S INSTRUCTIONS)
  
 308.8 EXPANSION JOINT FITTINGS. EXPANSION JOINT
 FITTINGS SHALL BE USED ONLY WHERE NECESSARY TO PROVIDE
 FOR EXPANSION AND CONTRACTION OF THE PIPES. EXPANSION
 JOINT FITTINGS SHALL BE OF THE TYPICAL MATERIAL
 SUITABLE FOR USE WITH THE TYPE OF PIPING IN WHICH SUCH
 FITTINGS ARE INSTALLED.
  
 C. DONE.
  
 D. WOULD YOU PLEASE PROVIDE A CONDENSATE RISER AND SIZE
 IN ACCORDANCE WITH THE 2020 FBC SEC [M]314.2.2 DRAIN
 PIPE MATERIALS AND SIZES. PLEASE NOTE THAT IF
 CONDENSATE IS NOT VENTED THROUGH THE ROOF, IT CANNOT
 TERMINATE IN-WALL DUE TO CONDENSATE LINES THAT HAVE A
 P-TRAP AND ARE UNDER 2020 FBC M307.2.4 AND P1002.1.
 EACH TRAP SHALL BE VENTED TO PERMIT THE ADMISSION OR
 EMISSION OF AIR SO THAT THE SEAL OF ANY FIXTURE TRAP
 SHALL NOT BE SUBJECTED TO A PRESSURE DIFFERENTIAL OF
 MORE THAN 1 INCH OF WATER COLUMN PER THE 2020 FBC
 SECTION 901.2 TRAP SEAL PROTECTION. THEY CANNOT
 TERMINATE IN A WALL AS IT HAS NO NEGATIVE OR POSITIVE
 PRESSURE TO ALLOW IT TO HAVE A DIFFERENTIAL OF ONE-INCH
 WATER COLUMN. YOU MAY VENT IN THE A/C PLENUM, BUT IT
 HAS TO BE CPVC AS THE FLAME INDEX DOES NOT ALLOW PVC.
 WOULD YOU PLEASE PROVIDE DETAIL?
  
 IN REFERENCE TO THE RESPONSE, THE P TRAP MAY BE
 REQUIRED FOR THE PROTECTION AGAINST RODENTS INTO THE
 UNIT.
  
 F. DONE.
  
 G. DONE.
  
 26. ON SHEET P1-00H;
  
 A. DONE.
  
 B. DONE.
  
 C. DONE.
  
 27. ON SHEET P1-01A AND P1-01B,
  
 A. DONE WITH NEW COMMENT?WOULD YOU PLEASE SHOW THE
 FIRST FLOOR SANITARY AND ITS CORRESPONDING SANITARY
 RISER TO MATCH P0-02 PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 A NEW COMMENT WOULD YOU PLEASE PROVIDE THE PAGE FOR THE
 CIVIL DRAWING CONTINUATION PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 B. DONE.
  
 C. DONE.
  
 D. DONE.
  
 E. THERE IS A 6" MANUAL FSP W/ FDV THAT MENTIONS F/1,
 AND I COULD NOT FIND A DETAIL. DOES THIS INCUR A FLOOR
 DRAIN, AND IF SO IT NEEDS TO BE CAST IRON AS IT IS IN
 THE FIRE-RATED STAIRWELL?
  
 NEW COMMENT, PLEASE NOTE ON PLANS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 28. ON SHEETS P1-02 A AND P1-02B, THE WATER RISERS NEED
 TO SHOW THE SHUT-OFF VALVES AND THEIR ACCESS PANEL
 OUTSIDE THE UNIT. WOULD YOU PLEASE PROVIDE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 THE QUESTION IS THE VALVE IS OUT OF THE UNIT OR IN THE
 UNIT. IF IN THE UNIT WILL BE ACCESSIBLE BY MAINTENANCE,
 SHOW THE LOCATION AND ACCESS TO THEM. WOULD YOU PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 29. DONE.
  
 30. ON SHEET P1-09A AND P1-09B;
  
 A. DONE,
  
 B. DONE.
  
 C. DONE.
  
 D. DONE.
  
 E. DONE.
  
 31. ON SHEET P3-01;
  
 A. DONE.
  
 B. HOT WATER LINES LOOPED FOR THE RECIRCULATING SYSTEM
 ARE NOT IN A CONTINUOUS LOOP; THEY ARE TEES IN MANY
 LOCATIONS. THERE IS A REQUIREMENT IN THE FLORIDA ENERGY
 CODE SEC. C404.6.1. THERE IS A TABLE THAT LIMITS THE
 DISTANCE BETWEEN THE SOURCE AND THE OUTLET; PLEASE
 REFER TO TABLE 404.5.1 FOR THE MAXIMUM ALLOWABLE PIPE
 LENGTH METHOD AND SIZE ACCORDANTLY.
  
 C. DONE.
  
 D. DONE.
  
 E. DONE.
  
 F. DONE WITH COMMENT?IT SEEMS THAT A JANITOR'S SINK IS
 REQUIRED, AND ONE IS NOT PRESENT FOR THE ASSEMBLY TYPE.
 WOULD YOU PLEASE PROVIDE ONE PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 THE MOP SINK IS NOT DRAWN IN ON THE PLAN. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 G. DONE.
  
 32. ON SHEET P3-02;
  
 A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE AS
 REQUESTED IN THE ARCHITECTURAL COMMENTS.
  
 B. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE OF 30" X
 48" IN THE LAVS OF THE AMENITY WOMEN'S AND MEN'S PER
 THE 2020 FBC SEC. ACC 305.3.
  
 C. DETAIL TWO; WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE OF 30" X 48" IN THE LAVS OF THE AMENITY WOMEN'S
 AND MEN'S PER THE 2020 FBC SEC. ACC 305.3.
  
 NEW COMMENTS; WOULD YOU PLEASE SHOW THE FOLLOWING
 COMMENTS OR PUT A NOTE ON THIS PAGE TO REFERENCE A3-20
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 33. DONE.
  
 34. DONE.
  
 PLEASE FEEL FREE TO SET UP A MEETING OR CONTACT ME ON
 ANY OF THE COMMENTS BY PHONE OR ZOOM MEETING IF YOU
 LIKE TO PREVENT FURTHER REVIEWS.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  