2022-02-24 07:55:312ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21100002
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT 15 OF PREVIOUS REVIEW CYCLE ASKED FOR THE
 BIKE ROOM NATURAL VENTILATION CALCULATIONS. THE
 RESPONSE SUBMITTED IS VENTILATION CALCULATIONS INCLUDED
 ON SHEET A3-01. THE NATURAL VENTILATION CALCULATIONS ON
 THIS SHEET IS FOR THE DOG SPA AREA WHICH HAS MECHANICAL
 VENTILATION. PLEASE SHOW THE NATURAL VENTILATION
 CALCULATIONS FOR THE BIKE STORAGE ROOM OR SUPPLY
 OUTDOOR AIR TO THIS AREA. FBC M 402 OR 403
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  