| Plan Review Notes For Permit 21100002 |
| Permit Number |
21100002 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-03-04 16:01:49 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E5-01 | | | | | | RSB-A, RSB-B, MSB-A BREAKER SIZES MISSING ON RISER. | | | PLEASE INDICATE BREAKER SIZES ON RISER DIAGRAM 215.5 | | | | | | FAULT CURRENT CALCULATION MISSING FROM PLANS. FAULT | | | CURRENT RATING IS SHOWN, PLEASE SHOW CALCULATIONS ON | | | HOW THEY WERE CALCULATED, 110.9, 110.10 |
|