2022-03-04 16:01:49ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E5-01
  
 RSB-A, RSB-B, MSB-A BREAKER SIZES MISSING ON RISER.
 PLEASE INDICATE BREAKER SIZES ON RISER DIAGRAM 215.5
  
 FAULT CURRENT CALCULATION MISSING FROM PLANS. FAULT
 CURRENT RATING IS SHOWN, PLEASE SHOW CALCULATIONS ON
 HOW THEY WERE CALCULATED, 110.9, 110.10