Plan Review Notes
Plan Review Notes For Permit 21100002
Permit Number 21100002
Review Stop B
Sequence Number 2
Notes
Date Text
2022-02-23 09:05:59NEW 8 STORY R2
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE REVISED LS DRAWINGS HAVE RED LINES ON THE WALLS
 - WHAT DOES THE RED LINES MEAN? - WALL HOURLY FIRE
 RATINGS ARE NOT CLEARLY SHOWN - FLOOR PLANS SHOW SOME
 BUT NOT ALL OF THE FIRE WALL RATINGS - LS PLANS DO NOT
 SHOW THE MECHANICAL (STORAGE) AND ELECTRICAL (STORAGE
 ROOM) WALL RATINGS BETWEEN UNITS.
  
 2) CORRIDOR REQUIRES A FIRE RATING TO BE CONTINUOUS -
 SOME OF THE STORAGE ROOMS (ELECTRIC/MECHANICAL) DO NOT
 SHOW THE CORRIDOR WALLS AND DOORS TO BE RATED - FBC
 1020.6
  
 3) 20 MINUTE FIRE RATED DOORS IN THE CORRIDORS DO NOT
 SHOW AS SELF CLOSING ON THE DOOR SCHEDULE - PLEASE SHOW
 FIRE RATED DOORS TO BE SELF CLOSING AND SELF LATCHING -
 FBC 716.5.9
  
 4) DRAWING AT-05 - TOILET REAR GRAB BAR CANNOT BE
 REDUCED TO 24 INCHES FOR THE COMMON AREA - ANSI FIG. 30
 A117.1 1986
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  