| Plan Review Notes For Permit 21100002 |
| Permit Number |
21100002 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-02-23 09:05:59 | NEW 8 STORY R2 | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE REVISED LS DRAWINGS HAVE RED LINES ON THE WALLS | | | - WHAT DOES THE RED LINES MEAN? - WALL HOURLY FIRE | | | RATINGS ARE NOT CLEARLY SHOWN - FLOOR PLANS SHOW SOME | | | BUT NOT ALL OF THE FIRE WALL RATINGS - LS PLANS DO NOT | | | SHOW THE MECHANICAL (STORAGE) AND ELECTRICAL (STORAGE | | | ROOM) WALL RATINGS BETWEEN UNITS. | | | | | | 2) CORRIDOR REQUIRES A FIRE RATING TO BE CONTINUOUS - | | | SOME OF THE STORAGE ROOMS (ELECTRIC/MECHANICAL) DO NOT | | | SHOW THE CORRIDOR WALLS AND DOORS TO BE RATED - FBC | | | 1020.6 | | | | | | 3) 20 MINUTE FIRE RATED DOORS IN THE CORRIDORS DO NOT | | | SHOW AS SELF CLOSING ON THE DOOR SCHEDULE - PLEASE SHOW | | | FIRE RATED DOORS TO BE SELF CLOSING AND SELF LATCHING - | | | FBC 716.5.9 | | | | | | 4) DRAWING AT-05 - TOILET REAR GRAB BAR CANNOT BE | | | REDUCED TO 24 INCHES FOR THE COMMON AREA - ANSI FIG. 30 | | | A117.1 1986 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|