| 2021-12-09 08:33:49 | 12/08/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET AT-01, THE INDEX P100H IS MISSING. WOULD |
| | YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 2. ON SHEET, AT-02 INDICATES THE FAIR HOUSING DESIGN |
| | MANUAL, BUT ON PAGE AT-05A, IT REFERS TO THE FHA DESIGN |
| | GUIDELINES UNDER TYP UNIT BLOCKING REQUIREMENT IN THE |
| | LEFT TOP OF THE PAGE. WOULD YOU PLEASE CLARIFY SHOW THE |
| | CORRECT ONE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 3. ON SHEET AT-05A; |
| | |
| | A. FOR THE TYP ADAPTABLE UNIT MOUNTING HEIGHT, UNDER |
| | THIS OUTLINE, IT MENTIONS THE A11.1 ANSI-2003, AND IT |
| | HAS NO PAGE REFERENCE, BUT SHOULD IT NOT BE UNDER THE |
| | FAIR HOUSING ACT DESIGN MANUAL. WOULD YOU PLEASE |
| | CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? THE TOILET |
| | TISSUE 30" IS NOT AN APPROVED ACCESSIBLE MEASUREMENT |
| | PER THE 2020 FBC ACC SEC. 604.7. |
| | |
| | B. ON THIS SAME PAGE, IT HAS FAIR HOUSING AND A PUBLIC |
| | RESTROOM. WOULD YOU PLEASE PROVIDE TWO SEPARATE PAGES, |
| | ONE FOR THE FHA AND THE OTHER FOR FLORIDA ACCESSIBILITY |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | C. ON UNIT BLOCKING IN THE UPPER LEFT-HAND CORNER, THE |
| | TYPICAL UNIT TOILET FRONT VIEW HAS A SWING-UP BAR, AND |
| | THE BACKING IS AT 8" AND A12" BACKING IS REQUIRED PER |
| | THE FHA DESIGN MANUAL PAGE 6-6. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | D. ON THE TYP PUBLIC MOUNTING HEIGHT, GRAB BARS ON THE |
| | VERTICAL BUT GRAB BARS SHALL BE INSTALLED IN A |
| | HORIZONTAL POSITION PER THE 2020 FBC ACC SEC. 609.4. |
| | |
| | E. ON THAT SAME DRAWING FOR THE ACCESSIBLE WATER |
| | FOUNTAIN, IT SHOWS KNEE AND TOE CLEARANCES OF 2'-4" BUT |
| | NEEDS TO BE AT 2'-3". THE SPOUT HEIGHTS WOULD ALSO BE |
| | REQUIRED PER THE 2020 FBC ACC SEC. 306, 307, & 602.2, |
| | COMPLIANCE WITH 2020 FBC ACC SEC. 307.2 PROTRUSION |
| | LIMITS. WOULD YOU PLEASE SHOW THE WATER CLOSET FLUSH |
| | CONTROL LOCATION PER THE 2020 FBC SEC. 604.6 FLUSH |
| | CONTROLS? HANDICAP WATER CLOSET FLUSH CONTROL SHALL BE |
| | HAND OPERATED OR AUTOMATIC AND SHALL BE 36" INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR PER THE 2020 FBC ACC |
| | SEC. 604.9.5. |
| | |
| | 4. ON SHEET A1-08 AND A1-08 A-B, WOULD YOU PLEASE SHOW |
| | CLEAR FLOOR SPACE OF 30" X 48" IN THE ROOFTOP EXTERIOR |
| | AMENITY SINK AND THE WOMEN'S AND MEN'S RESTROOMS PER |
| | THE 2020 FBC SEC. ACC 305.3. |
| | |
| | 5. ON SHEET A3-01; |
| | |
| | A. THE MEN'S AND WOMEN'S LOOK LIKE THEY MAY BE MISSED |
| | LABELED AS I SEE A URINAL IN THE WOMEN'S. WOULD YOU |
| | PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | WOULD YOU PLEASE CORRECT ALL OTHER PAGES IN THIS SET OF |
| | PLANS? |
| | |
| | B. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE IN THE |
| | OPEN AREA FOR THE LAVS IN THE WOMEN'S AND BATHS LAVE OF |
| | 30" BY 48" WHERE THE 5' CIRCLE? YOU MAY SHOW THE CIRCLE |
| | AS WELL PER THE 2020 FBC SEC. ACC 305.3. |
| | |
| | C. WOULD YOU PLEASE SHOW THE 30" X 48" CLEAR FLOOR |
| | SPACE IN THE CLUB ROOM SINK AND THE WORKROOM PER THE |
| | 2020 FBC SEC. ACC 305.3. |
| | |
| | D. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE |
| | WOMEN'S TOILET OF 60" INCHES MINIMUM MEASURED |
| | PERPENDICULAR FROM THE SIDEWALL AND 56" ROOMS PER THE |
| | 2020 FBC ACC. SEC. 604.3.1. |
| | |
| | E. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE |
| | DRINKING FOUNTAINS PER THE 2020 FBC SEC. ACC 305.3. |
| | |
| | 6. ON SHEET A3-08; |
| | |
| | A. DETAIL ONE, TWO, AND THREE; WOULD YOU PLEASE SHOW |
| | THE CLEAR FLOOR SPACE OF 30" X 48" IN THE LAVS OF THE |
| | AMENITY WOMEN'S AND MEN'S PER THE 2020 FBC SEC. ACC |
| | 305.3. |
| | |
| | B. DETAIL TWO; WOULD YOU PLEASE SHOW THE CLEAR FLOOR |
| | SPACE OF 30" X 48" IN THE LAVS OF THE AMENITY WOMEN'S |
| | AND MEN'S PER THE 2020 FBC SEC. ACC 305.3. THERE IS A |
| | TILE HATCH SHOW THAT MAKES THE DASH LINES NOT SEEN. |
| | WOULD YOU PLEASE LIGHTEN THE TILE HATCHES FOR CLARITY? |
| | |
| | 7. ON SHEET A3-60, THERE IS A TRASH SHOOT, AND IN MOST |
| | INSTALLATIONS, THERE IS A CLEANING/ SANITIZING SYSTEM |
| | IN THE EIGHTH LEVEL, IF SO WOULD YOU PLEASE SHOW IT AND |
| | GIVE A DETAIL OR PAGE REFERENCE PER THE ON SHEET |
| | A8-01A; |
| | |
| | 8. ON SHEET A8-01A; |
| | |
| | A. UNDER THE FAIR HOUSING DESIGN MANUAL, PLEASE LABEL |
| | THE TYPE OF UNIT FOR (A) OR (B) CONFIGURATION PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. ON GENERAL NOTES, # 6 REFERS TO BATHROOM CABINETRY |
| | DETAILS, AND THE SHEET NUMBER IS UNAVAILABLE. DOES THE |
| | CABINET NEED TO BE 34" PER SPECIFICATION (B) PER THE |
| | FAIR HOUSING DESIGN MANUAL? WOULD YOU PLEASE CLARIFY |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | C. THE WATER CLOSET HAS A CLEAR FLOOR SPACE PER FHA |
| | 7.43 OF 48" X 56" PER DETAIL NUMBER TWO. WOULD YOU |
| | PLEASE SHOW THE DISTANCE FROM THE WALL TO THE WALL AND |
| | THE LAV PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | D. THERE IS A DOOR NEXT TO THE WATER CLOSET THAT HAS A |
| | DOOR TO THE CLOSET AND THE SHOWER. WOULD YOU PLEASE |
| | SHOW THE REINFORCEMENT-REQUIRED SUPPORT FOR THE GRAB |
| | BARS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 9. ON SHEET A8-01A.1; |
| | |
| | A. IT SHOWS ELEVATION FOR CABINET, AND IT SEEMS THAT |
| | THESE ARE B TYPE UNITS. WOULD YOU PLEASE SHOW THE 34" |
| | TO THE TOP OF THE CABINET FOR THE CORRESPONDING DETAIL? |
| | |
| | B. DETAIL FOUR AND SIX SHOW GRAB BARS, WHICH ARE NOT |
| | REQUIRED AT THIS TIME. WOULD YOU PLEASE REMOVE OR NOTE |
| | THAT NOT TO BE INSTALLED PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. DETAIL FIVE SHOWS 1'- 4 7/8" AND 15" IS REQUIRED PET |
| | FHA DESIGN PAGE 6.7. WOULD YOU PLEASE CORRECT PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | D. ON GENERAL NOTES # 6 REFERS TO BATHROOM CABINETRY |
| | DETAILS, AND THE SHEET NUMBER IS UNAVAILABLE. DOES THE |
| | CABINET NEED TO BE 34" PER SPECIFICATION (B) PER THE |
| | FAIR HOUSING DESIGN MANUAL. WOULD YOU PLEASE CLARIFY |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 10. ON SHEETS A8-01B AND A8-01B.1, PLEASE REFER TO THE |
| | COMMENTS ABOVE. |
| | |
| | 11. ON SHEETS A8-01C AND A8-01C.1, PLEASE REFER TO THE |
| | COMMENTS ABOVE. |
| | |
| | 12. ON SHEETS A8-01D AND A8-01D.1, PLEASE REFER TO THE |
| | COMMENTS ABOVE. |
| | |
| | 13. ON SHEETS A8-01E AND A8-01E.1, PLEASE REFER TO THE |
| | COMMENTS ABOVE. |
| | |
| | 14. ON SHEETS A8-01F AND A8-01F.1, PLEASE REFER TO THE |
| | COMMENTS ABOVE. |
| | |
| | 15. ON SHEET A8-02A; |
| | |
| | A. UNDER THE FAIR HOUSING DESIGN MANUAL, PLEASE LABEL |
| | THE TYPE OF UNIT FOR (A) OR (B) CONFIGURATION PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. IT SHOWS TWO BATHROOMS THAT LOOK LIKE SPECIFICATION |
| | B, AND ONLY ONE NEEDS TO COMPLY WITH TYPE B. IF THIS IS |
| | WHAT WILL TAKE PRECEDENCE, PLEASE CHANGE. WOULD YOU |
| | PLEASE SHOW ONE AND LABEL IT PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | C. ON GENERAL NOTES, # 6 REFERS TO BATHROOM CABINETRY |
| | DETAILS, AND THE SHEET NUMBER IS UNAVAILABLE. DOES THE |
| | CABINET NEED TO BE 34" PER SPECIFICATION (B) PER THE |
| | FAIR HOUSING DESIGN MANUAL. WOULD YOU PLEASE CLARIFY |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | D. DETAIL FOUR, FIVE, SIX, AND EIGHT SHOW GRAB BAR, AND |
| | THEY ARE NOT REQUIRED AT THIS TIME. WOULD YOU PLEASE |
| | REMOVE OR MAKE A NOTE THAT NOT TO BE INSTALLED PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | E. THE WATER CLOSET HAS A CLEAR FLOOR SPACE PER FHA |
| | 7.43 OF 48" X 56" PER DETAIL NUMBER TWO. WOULD YOU |
| | PLEASE SHOW THE DISTANCE FROM THE WALL TO THE WALL AND |
| | THE LAV PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | F. THERE IS A DOOR NEXT TO THE WATER CLOSET THAT HAS A |
| | DOOR TO THE CLOSET AND THE SHOWER. WOULD YOU PLEASE |
| | SHOW THE REINFORCEMENT-REQUIRED SUPPORT FOR THE GRAB |
| | BARS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 16. ON SHEET A8-02A.1; |
| | |
| | A. ON DETAIL SEVEN SHOWS 1'- 4 3/4" AND 15" IS REQUIRED |
| | PET FHA DESIGN PAGE 6.7. WOULD YOU PLEASE CORRECT PER |
| | THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. ON DETAIL EIGHT IT SHOWS THE GRAB BAR ON THE TUB AND |
| | NOT THE FHA DESIGN MANUAL ON PAGE 6.9. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | C. IT SHOWS ELEVATION FOR CABINET, AND IT SEEMS THAT |
| | THESE ARE B TYPE UNITS. WOULD YOU PLEASE SHOW THE 34" |
| | TO THE TOP OF THE CABINET FOR THE CORRESPONDING DETAIL? |
| | |
| | D. ON GENERAL NOTES # 6 REFERS TO BATHROOM CABINETRY |
| | DETAILS, AND THE SHEET NUMBER IS UNAVAILABLE. DOES THE |
| | CABINET NEED TO BE 34" PER SPECIFICATION (B) PER THE |
| | FAIR HOUSING DESIGN MANUAL. WOULD YOU PLEASE CLARIFY |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 17. ON SHEETS A8-02B AND A8-02B.1, PLEASE REFER TO THE |
| | COMMENTS ABOVE. |
| | |
| | 18. ON SHEETS A8-02C AND A8-01C.1, PLEASE REFER TO THE |
| | COMMENTS ABOVE. |
| | |
| | 19. ON SHEETS A8-03A AND A8-03#A.1, PLEASE REFER TO THE |
| | COMMENTS ABOVE. |
| | |
| | 20. ON SHEET A8-18, YOU SHOW ACCESSIBLE VANITY. WOULD |
| | YOU INCLUDE AN FHA DETAIL AND LABEL IT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 21. ON SHEET A8-40; |
| | |
| | A. WOULD YOU PLEASE LABEL DETAILS CORRESPONDING TO FHA |
| | ONE-EIGHT AND CORRECT THE TYPE. WOULD YOU PLEASE |
| | CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 22. ON SHEETS E1-08 AND E1-08A, IT SHOWS AN OVERLAY |
| | OVER THE RESTROOM AND THE SINKS. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 23. ON SHEET P0-00; |
| | |
| | A. UNDER PLUMBING GENERAL NOTES, IT REFERS TO THE 2017 |
| | CODE, AND 2020 IS THE CURRENT. WOULD YOU PLEASE CORRECT |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. WOULD YOU PLEASE PROVIDE THE MINIMUM NUMBER OF |
| | FIXTURES FOR THE OCCUPANT LOAD BASED ON THE ACTUAL USE |
| | OF THE BUILDING OR SPACE FOR AMENITIES PER TABLE 403.1 |
| | MINIMUM NUMBER OF FIXTURES AS ON THE LS IF POSSIBLE. |
| | |
| | C. FIXTURES UNDER THE COFFEE MAKER/ICE MAKER REQUIRE AN |
| | INLINE VACUUM BREAKER THAT COMPLIES WITH THE ASSE 1024 |
| | NON-CARBONATED PER THE 2020 FBC SEC. 608.17.1.2. |
| | |
| | 24. ON SHEET P0-01; |
| | |
| | A. ON THE WATER HEATER DETAIL SHOWS THE A/C UNIT |
| | DUMPING INTO THE SANITARY AND CONDENSATE IS NOT |
| | PERMITTED TO DISCHARGE INTO THE CITY'S SANITARY SYSTEM |
| | PER CITY ORDINANCE CHAPTER 90, ARTICLE III, SEC.90-126 |
| | (B)(5). WOULD YOU PLEASE PROVIDE AN ALTERNATE DRAIN PER |
| | THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. WOULD YOU PLEASE SHOW AN EXPANSION DEVICE ALL |
| | DEPENDING ON IF THE SUB-METER IS A RESTRICTED FLOW ONE |
| | WAY OR A DUAL FLOW. IF A DUAL, WOULD YOU PROVIDE THE |
| | SPECIFICATION FOR IT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. FOR THE FLOOR DRAIN DETAIL, A DEEP SEAL TRAP IS NOT |
| | APPROVED; PLEASE PROVIDE TRAP SEAL PER THE 2020 FBC |
| | SEC. 1002.4.1 TRAP SEAL PROTECTION. |
| | |
| | D. ON THE ELEVATOR PUMP, PLEASE SHOW THE DISCHARGE TO A |
| | FLOOR IN AN INDIRECT CONNECTION PER THE 2020 FBC SEC P |
| | 712.3.5 PUMP CONNECTION TO THE DRAINAGE SYSTEM. |
| | |
| | E. ON THE WASHER BOX DETAIL, PLEASE ADD FIRE-RATED WERE |
| | NEEDED PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | F. ON THE ROOFTOP HOSE BIBB, WOULD YOU PLEASE SHOW A |
| | GATE VALVE SHUT OFF PER THE 2020 FBC SEC. 606.2 |
| | LOCATION OF SHUT-OFF VALVES. |
| | |
| | H. ON THE BOTTOM RIGHT-HAND CORNER, IT CALLS OUT FOR |
| | GAS ON THE ROOF. I COULD NOT FIND IT ON THIS SET OF |
| | PLANS. IF THERE IS ANY TYPE OF GAS SYSTEM, YOU MAY |
| | CHOOSE TO HAVE IT ON THE SET OF PLANS OR MAKE A NOTE |
| | THAT A SEPARATE PERMIT WILL BE APPLIED FOR GAS BY A |
| | LICENSED CONTRACTOR. AN ISOMERIC IS REQUIRED WITH SPECS |
| | FOR ALL EQUIPMENT AND REGULATOR FOR THIS REVIEW. IF NO |
| | GAS AT THIS TIME, PLEASE REMOVE ANY GAS DETAILS. WOULD |
| | YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 25. ON SHEET P0-02; |
| | |
| | A. WOULD YOU PLEASE SHOW AND LABEL ALL PIPE VENTED |
| | THROUGH THE ROOF PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. THERE ARE EXPANSION FITTING; PLEASE PROVIDE THE |
| | STANDARD FOR THE TYPE OF MATERIAL USED PER THE 2020 FBC |
| | TABLE 702.4 PIPE FITTINGS. WOULD YOU PLEASE PROVIDE THE |
| | MANUFACTURE'S INSTALLATION INSTRUCTIONS? A TEST TEE MAY |
| | BE REQUIRED ABOVE EACH FITTING IF AGREED FOR TESTING |
| | PURPOSES. WOULD YOU PLEASE SHOW ON ISOMETRIC? |
| | |
| | C. VERTICAL RISER SHOWS A RISER CLAMP ON EVERY OTHER |
| | FLOOR. WOULD YOU PLEASE SHOW OR MENTION THAT THEY SHALL |
| | BE EVERY 10 ? PER THE 2020 FBC TABLE 308.5 HANGER |
| | SPACING? |
| | |
| | D. WOULD YOU PLEASE PROVIDE A CONDENSATE RISER AND SIZE |
| | IN ACCORDANCE WITH THE 2020 FBC SEC [M]314.2.2 DRAIN |
| | PIPE MATERIALS AND SIZES. PLEASE NOTE THAT IF |
| | CONDENSATE IS NOT VENTED THROUGH THE ROOF, IT CANNOT |
| | TERMINATE IN-WALL DUE TO CONDENSATE LINES THAT HAVE A |
| | P-TRAP AND ARE UNDER 2020 FBC M307.2.4 AND P1002.1. |
| | EACH TRAP SHALL BE VENTED TO PERMIT THE ADMISSION OR |
| | EMISSION OF AIR SO THAT THE SEAL OF ANY FIXTURE TRAP |
| | SHALL NOT BE SUBJECTED TO A PRESSURE DIFFERENTIAL OF |
| | MORE THAN 1 INCH OF WATER COLUMN PER THE 2020 FBC |
| | SECTION 901.2 TRAP SEAL PROTECTION. THEY CANNOT |
| | TERMINATE IN A WALL AS IT HAS NO NEGATIVE OR POSITIVE |
| | PRESSURE TO ALLOW IT TO HAVE A DIFFERENTIAL OF ONE-INCH |
| | WATER COLUMN. YOU MAY VENT IN THE A/C PLENUM, BUT IT |
| | HAS TO BE CPVC AS THE FLAME INDEX DOES NOT ALLOW PVC. |
| | WOULD YOU PLEASE PROVIDE DETAIL? |
| | |
| | F. WOULD YOU PLEASE SHOW THE DFU ON THE BOTTOM OF EACH |
| | RISER PER THE 2020 FBC TABLE 710.1(2) HORIZONTAL |
| | FIXTURE BRANCHES AND STACKS. |
| | |
| | G. PLEASE PROVIDE A SANITARY RISER ISOMETRIC DIAGRAM |
| | FOR THE MAIN SEWER LINE WITH SIZES THAT GOES THROUGH |
| | THE BUILDING AND MATCH STACK RISERS CONNECTION POINTS |
| | ON P0-02 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.5.1.3 (13) COMMERCIAL PLUMBING. |
| | |
| | 26. ON SHEET P1-00H; |
| | |
| | A. THERE IS A SECTIONAL VIEW FOR 7- H-5, AND NO SUCH |
| | PAGE WAS FOUND. WOULD YOU PLEASE PROVIDE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. THE THREE IN SANITARY SAYS SEE CIVIL DRAWING OR |
| | CONTINUATION A COULD NOT MATCH. WOULD YOU PLEASE |
| | PROVIDE THE PAGE NUMBER AFTER THE CONTINUATION COMMENT |
| | PER THE WOULD YOU PLEASE PROVIDE PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | C. THERE SEEMS TO BE TWO BBQS IN THE POOL AREA. DO THEY |
| | REQUIRE GAS OR PORTABLE PROPANE TANKS? IF GAS, PLEASE |
| | REFER TO P0-01 (H) COMMENT PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 27. ON SHEET P1-01A AND P1-01B, |
| | |
| | A. WOULD YOU PLEASE SHOW THE FIRST FLOOR SANITARY AND |
| | ITS CORRESPONDING SANITARY RISER TO MATCH P0-02 PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. THERE IS A SINK IN THE CLUB ROOM (P1-01A) THAT HAS |
| | NO PAGE CONTINUATION OF THE SANITARY WOULD YOU PLEASE |
| | ADD IT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. THE SINK IN THE WORKROOM AND RESTROOM AREA (P1-01B), |
| | WOULD YOU PLEASE SHOW THE CONTINUATION PAGE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | D. ON THE TWO 8" SANITARY, IT REFERS TO THE CIVIL WOULD |
| | YOU PLEASE PROVIDE THE PAGE IN REFERENCE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | E. THERE IS A 6" MANUAL FSP W/ FDV THAT MENTIONS F/1, |
| | AND I COULD NOT FIND A DETAIL. DOES THIS INCUR A FLOOR |
| | DRAIN, AND IF SO IT NEEDS TO BE CAST IRON AS IT IS IN |
| | THE FIRE-RATED STAIRWELL? |
| | |
| | 28. ON SHEETS P1-02 A AND P1-02B, THE WATER RISERS NEED |
| | TO SHOW THE SHUT-OFF VALVES AND THEIR ACCESS PANEL |
| | OUTSIDE THE UNIT. WOULD YOU PLEASE PROVIDE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 29. ON SHEET P1-02A, THE TRASH SHOOT MAY REQUIRE A HOSE |
| | BIBB AND WATER FOR SANITIZING SYSTEM ON THE EIGHTH |
| | FLOOR; IF SO, PLEASE SHOW PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 30. ON SHEET P1-09A AND P1-09B; |
| | |
| | A. IT HAS A NOTE THAT REFERS TO THE SCUPPERS AND |
| | DOWNSPOUTS. WOULD YOU PROVIDE THE PAGE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. WOULD YOU PLEASE PROVIDE AN ISOMETRIC WITH THE SIZE |
| | OF PIPES, ROOF DRAINS, AND SCUPPER DETAIL, AND |
| | LOCATIONS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.5.1.3 (13) COMMERCIAL PLUMBING. |
| | |
| | C. STORM WATER FORMULA IS REQUIRED, ALONG WITH A TABLE |
| | THAT SHOWS SQUARE FOOTAGE AND GALLONS PER MINUTE. SO |
| | PLEASE SIZE PER THE 2020 FBC SEC. P1106. |
| | |
| | D. WOULD YOU PLEASE IDENTIFY ALL THE STORM RISERS WITH |
| | RISER TAGS PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | E. WOULD YOU PLEASE PROVIDE THE LOCATION OF THE ROOF |
| | DRAIN WITH PRIMARY AND SECONDARY (EMERGENCY OVERFLOW) |
| | ROOF DRAINS OR SCUPPERS WHICH SHALL BE PROVIDED WHERE |
| | THE ROOF PERIMETER CONSTRUCTION EXTENDS ABOVE THE ROOF |
| | IN SUCH A MANNER THAT WATER WILL B ENTRAPPED IF THE |
| | PRIMARY DRAINS ALLOW BUILDUP FOR ANY REASON PER THE |
| | 2020 FBC SEC. P 1108.1 SECONDARY (EMERGENCY OVERFLOW) |
| | DRAINS OR SCUPPERS. |
| | |
| | 31. ON SHEET P3-01; |
| | |
| | A. WOULD YOU PLEASE PROVIDE A SANITARY ISOMETRIC |
| | DRAWING PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.5.1.3 (13) COMMERCIAL PLUMBING. |
| | |
| | B. HOT WATER LINES LOOPED FOR THE RECIRCULATING SYSTEM |
| | ARE NOT IN A CONTINUOUS LOOP. THERE IS A REQUIREMENT IN |
| | THE FLORIDA ENERGY CODE SEC. C404.6.1. THERE IS A TABLE |
| | THAT LIMITS THE DISTANCE BETWEEN THE SOURCE AND THE |
| | OUTLET; PLEASE REFER TO TABLE 404.5.1 FOR THE MAXIMUM |
| | ALLOWABLE PIPE LENGTH METHOD AND SIZE ACCORDANTLY. |
| | |
| | C. WOULD YOU PLEASE INCORPORATE THE SANITARY LINES AND |
| | SIZE OF THE DISCHARGE FROM THE ELEVATORS TO THE DRAIN |
| | THAT CORRESPONDS TO THE ISOMETRIC AND FLAT DRAWINGS PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | D. IN THE MANAGER'S OFFICE, IT SHOWS A SINK; IF IT IS |
| | NOT USED, WOULD YOU PLEASE CORRECT IT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | E. WOULD YOU PLEASE PROVIDE DETAIL FOR THE WATER HEATER |
| | IN THE JANITOR'S ROOM AND SHOW FOR SANITARY AND WATER |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | F. IT SEEMS THAT A JANITOR'S SINK IS REQUIRED, AND ONE |
| | IS NOT PRESENT FOR THE ASSEMBLY TYPE. WOULD YOU PLEASE |
| | PROVIDE ONE PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL SHALL |
| | BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE 2020 |
| | FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P 310.3. |
| | WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET? |
| | |
| | 32. ON SHEET P3-02; |
| | |
| | A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE AS |
| | REQUESTED IN THE ARCHITECTURAL COMMENTS. |
| | |
| | B. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE OF 30" X |
| | 48" IN THE LAVS OF THE AMENITY WOMEN'S AND MEN'S PER |
| | THE 2020 FBC SEC. ACC 305.3. |
| | |
| | C. DETAIL TWO; WOULD YOU PLEASE SHOW THE CLEAR FLOOR |
| | SPACE OF 30" X 48" IN THE LAVS OF THE AMENITY WOMEN'S |
| | AND MEN'S PER THE 2020 FBC SEC. ACC 305.3. |
| | |
| | 33. ON SHEETS P8-01, P802 AND P803, IT SHOWS THE |
| | WASHING MACHINE BOX BEHIND THE UNITS AND SHALL BE |
| | ACCESSIBLE WITHOUT MOVING THE UNIT AND WITHIN REACH PER |
| | THE 2020 FBC SEC. P 606.3 ACCESS TO VALVES. |
| | |
| | 34. WHEN YOU REFER TO A SANITARY STACK OR WATER, WOULD |
| | YOU PLEASE DO IT AS S-1 IN THE TOP (RISER) AND THE PAGE |
| | NUMBER ON THE BOTTOM FOR CLARITY PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS? |
| | |
| | PLEASE FEEL FREE TO SET UP A MEETING OR CONTACT ME ON |
| | ANY OF THE COMMENTS BY PHONE OR ZOOM MEETING IF YOU |
| | LIKE TO PREVENT FURTHER REVIEWS. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| | REQUEST. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |