2021-12-09 08:33:4912/08/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET AT-01, THE INDEX P100H IS MISSING. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 2. ON SHEET, AT-02 INDICATES THE FAIR HOUSING DESIGN
 MANUAL, BUT ON PAGE AT-05A, IT REFERS TO THE FHA DESIGN
 GUIDELINES UNDER TYP UNIT BLOCKING REQUIREMENT IN THE
 LEFT TOP OF THE PAGE. WOULD YOU PLEASE CLARIFY SHOW THE
 CORRECT ONE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 3. ON SHEET AT-05A;
  
 A. FOR THE TYP ADAPTABLE UNIT MOUNTING HEIGHT, UNDER
 THIS OUTLINE, IT MENTIONS THE A11.1 ANSI-2003, AND IT
 HAS NO PAGE REFERENCE, BUT SHOULD IT NOT BE UNDER THE
 FAIR HOUSING ACT DESIGN MANUAL. WOULD YOU PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS? THE TOILET
 TISSUE 30" IS NOT AN APPROVED ACCESSIBLE MEASUREMENT
 PER THE 2020 FBC ACC SEC. 604.7.
  
 B. ON THIS SAME PAGE, IT HAS FAIR HOUSING AND A PUBLIC
 RESTROOM. WOULD YOU PLEASE PROVIDE TWO SEPARATE PAGES,
 ONE FOR THE FHA AND THE OTHER FOR FLORIDA ACCESSIBILITY
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. ON UNIT BLOCKING IN THE UPPER LEFT-HAND CORNER, THE
 TYPICAL UNIT TOILET FRONT VIEW HAS A SWING-UP BAR, AND
 THE BACKING IS AT 8" AND A12" BACKING IS REQUIRED PER
 THE FHA DESIGN MANUAL PAGE 6-6. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. ON THE TYP PUBLIC MOUNTING HEIGHT, GRAB BARS ON THE
 VERTICAL BUT GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION PER THE 2020 FBC ACC SEC. 609.4.
  
 E. ON THAT SAME DRAWING FOR THE ACCESSIBLE WATER
 FOUNTAIN, IT SHOWS KNEE AND TOE CLEARANCES OF 2'-4" BUT
 NEEDS TO BE AT 2'-3". THE SPOUT HEIGHTS WOULD ALSO BE
 REQUIRED PER THE 2020 FBC ACC SEC. 306, 307, & 602.2,
 COMPLIANCE WITH 2020 FBC ACC SEC. 307.2 PROTRUSION
 LIMITS. WOULD YOU PLEASE SHOW THE WATER CLOSET FLUSH
 CONTROL LOCATION PER THE 2020 FBC SEC. 604.6 FLUSH
 CONTROLS? HANDICAP WATER CLOSET FLUSH CONTROL SHALL BE
 HAND OPERATED OR AUTOMATIC AND SHALL BE 36" INCHES
 MAXIMUM ABOVE THE FINISH FLOOR PER THE 2020 FBC ACC
 SEC. 604.9.5.
  
 4. ON SHEET A1-08 AND A1-08 A-B, WOULD YOU PLEASE SHOW
 CLEAR FLOOR SPACE OF 30" X 48" IN THE ROOFTOP EXTERIOR
 AMENITY SINK AND THE WOMEN'S AND MEN'S RESTROOMS PER
 THE 2020 FBC SEC. ACC 305.3.
  
 5. ON SHEET A3-01;
  
 A. THE MEN'S AND WOMEN'S LOOK LIKE THEY MAY BE MISSED
 LABELED AS I SEE A URINAL IN THE WOMEN'S. WOULD YOU
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
 WOULD YOU PLEASE CORRECT ALL OTHER PAGES IN THIS SET OF
 PLANS?
  
 B. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE IN THE
 OPEN AREA FOR THE LAVS IN THE WOMEN'S AND BATHS LAVE OF
 30" BY 48" WHERE THE 5' CIRCLE? YOU MAY SHOW THE CIRCLE
 AS WELL PER THE 2020 FBC SEC. ACC 305.3.
  
 C. WOULD YOU PLEASE SHOW THE 30" X 48" CLEAR FLOOR
 SPACE IN THE CLUB ROOM SINK AND THE WORKROOM PER THE
 2020 FBC SEC. ACC 305.3.
  
 D. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 WOMEN'S TOILET OF 60" INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDEWALL AND 56" ROOMS PER THE
 2020 FBC ACC. SEC. 604.3.1.
  
 E. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 DRINKING FOUNTAINS PER THE 2020 FBC SEC. ACC 305.3.
  
 6. ON SHEET A3-08;
  
 A. DETAIL ONE, TWO, AND THREE; WOULD YOU PLEASE SHOW
 THE CLEAR FLOOR SPACE OF 30" X 48" IN THE LAVS OF THE
 AMENITY WOMEN'S AND MEN'S PER THE 2020 FBC SEC. ACC
 305.3.
  
 B. DETAIL TWO; WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE OF 30" X 48" IN THE LAVS OF THE AMENITY WOMEN'S
 AND MEN'S PER THE 2020 FBC SEC. ACC 305.3. THERE IS A
 TILE HATCH SHOW THAT MAKES THE DASH LINES NOT SEEN.
 WOULD YOU PLEASE LIGHTEN THE TILE HATCHES FOR CLARITY?
  
 7. ON SHEET A3-60, THERE IS A TRASH SHOOT, AND IN MOST
 INSTALLATIONS, THERE IS A CLEANING/ SANITIZING SYSTEM
 IN THE EIGHTH LEVEL, IF SO WOULD YOU PLEASE SHOW IT AND
 GIVE A DETAIL OR PAGE REFERENCE PER THE ON SHEET
 A8-01A;
  
 8. ON SHEET A8-01A;
  
 A. UNDER THE FAIR HOUSING DESIGN MANUAL, PLEASE LABEL
 THE TYPE OF UNIT FOR (A) OR (B) CONFIGURATION PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. ON GENERAL NOTES, # 6 REFERS TO BATHROOM CABINETRY
 DETAILS, AND THE SHEET NUMBER IS UNAVAILABLE. DOES THE
 CABINET NEED TO BE 34" PER SPECIFICATION (B) PER THE
 FAIR HOUSING DESIGN MANUAL? WOULD YOU PLEASE CLARIFY
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. THE WATER CLOSET HAS A CLEAR FLOOR SPACE PER FHA
 7.43 OF 48" X 56" PER DETAIL NUMBER TWO. WOULD YOU
 PLEASE SHOW THE DISTANCE FROM THE WALL TO THE WALL AND
 THE LAV PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. THERE IS A DOOR NEXT TO THE WATER CLOSET THAT HAS A
 DOOR TO THE CLOSET AND THE SHOWER. WOULD YOU PLEASE
 SHOW THE REINFORCEMENT-REQUIRED SUPPORT FOR THE GRAB
 BARS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 9. ON SHEET A8-01A.1;
  
 A. IT SHOWS ELEVATION FOR CABINET, AND IT SEEMS THAT
 THESE ARE B TYPE UNITS. WOULD YOU PLEASE SHOW THE 34"
 TO THE TOP OF THE CABINET FOR THE CORRESPONDING DETAIL?
  
 B. DETAIL FOUR AND SIX SHOW GRAB BARS, WHICH ARE NOT
 REQUIRED AT THIS TIME. WOULD YOU PLEASE REMOVE OR NOTE
 THAT NOT TO BE INSTALLED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. DETAIL FIVE SHOWS 1'- 4 7/8" AND 15" IS REQUIRED PET
 FHA DESIGN PAGE 6.7. WOULD YOU PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 D. ON GENERAL NOTES # 6 REFERS TO BATHROOM CABINETRY
 DETAILS, AND THE SHEET NUMBER IS UNAVAILABLE. DOES THE
 CABINET NEED TO BE 34" PER SPECIFICATION (B) PER THE
 FAIR HOUSING DESIGN MANUAL. WOULD YOU PLEASE CLARIFY
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 10. ON SHEETS A8-01B AND A8-01B.1, PLEASE REFER TO THE
 COMMENTS ABOVE.
  
 11. ON SHEETS A8-01C AND A8-01C.1, PLEASE REFER TO THE
 COMMENTS ABOVE.
  
 12. ON SHEETS A8-01D AND A8-01D.1, PLEASE REFER TO THE
 COMMENTS ABOVE.
  
 13. ON SHEETS A8-01E AND A8-01E.1, PLEASE REFER TO THE
 COMMENTS ABOVE.
  
 14. ON SHEETS A8-01F AND A8-01F.1, PLEASE REFER TO THE
 COMMENTS ABOVE.
  
 15. ON SHEET A8-02A;
  
 A. UNDER THE FAIR HOUSING DESIGN MANUAL, PLEASE LABEL
 THE TYPE OF UNIT FOR (A) OR (B) CONFIGURATION PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. IT SHOWS TWO BATHROOMS THAT LOOK LIKE SPECIFICATION
 B, AND ONLY ONE NEEDS TO COMPLY WITH TYPE B. IF THIS IS
 WHAT WILL TAKE PRECEDENCE, PLEASE CHANGE. WOULD YOU
 PLEASE SHOW ONE AND LABEL IT PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 C. ON GENERAL NOTES, # 6 REFERS TO BATHROOM CABINETRY
 DETAILS, AND THE SHEET NUMBER IS UNAVAILABLE. DOES THE
 CABINET NEED TO BE 34" PER SPECIFICATION (B) PER THE
 FAIR HOUSING DESIGN MANUAL. WOULD YOU PLEASE CLARIFY
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. DETAIL FOUR, FIVE, SIX, AND EIGHT SHOW GRAB BAR, AND
 THEY ARE NOT REQUIRED AT THIS TIME. WOULD YOU PLEASE
 REMOVE OR MAKE A NOTE THAT NOT TO BE INSTALLED PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 E. THE WATER CLOSET HAS A CLEAR FLOOR SPACE PER FHA
 7.43 OF 48" X 56" PER DETAIL NUMBER TWO. WOULD YOU
 PLEASE SHOW THE DISTANCE FROM THE WALL TO THE WALL AND
 THE LAV PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 F. THERE IS A DOOR NEXT TO THE WATER CLOSET THAT HAS A
 DOOR TO THE CLOSET AND THE SHOWER. WOULD YOU PLEASE
 SHOW THE REINFORCEMENT-REQUIRED SUPPORT FOR THE GRAB
 BARS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 16. ON SHEET A8-02A.1;
  
 A. ON DETAIL SEVEN SHOWS 1'- 4 3/4" AND 15" IS REQUIRED
 PET FHA DESIGN PAGE 6.7. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 B. ON DETAIL EIGHT IT SHOWS THE GRAB BAR ON THE TUB AND
 NOT THE FHA DESIGN MANUAL ON PAGE 6.9. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. IT SHOWS ELEVATION FOR CABINET, AND IT SEEMS THAT
 THESE ARE B TYPE UNITS. WOULD YOU PLEASE SHOW THE 34"
 TO THE TOP OF THE CABINET FOR THE CORRESPONDING DETAIL?
  
 D. ON GENERAL NOTES # 6 REFERS TO BATHROOM CABINETRY
 DETAILS, AND THE SHEET NUMBER IS UNAVAILABLE. DOES THE
 CABINET NEED TO BE 34" PER SPECIFICATION (B) PER THE
 FAIR HOUSING DESIGN MANUAL. WOULD YOU PLEASE CLARIFY
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 17. ON SHEETS A8-02B AND A8-02B.1, PLEASE REFER TO THE
 COMMENTS ABOVE.
  
 18. ON SHEETS A8-02C AND A8-01C.1, PLEASE REFER TO THE
 COMMENTS ABOVE.
  
 19. ON SHEETS A8-03A AND A8-03#A.1, PLEASE REFER TO THE
 COMMENTS ABOVE.
  
 20. ON SHEET A8-18, YOU SHOW ACCESSIBLE VANITY. WOULD
 YOU INCLUDE AN FHA DETAIL AND LABEL IT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 21. ON SHEET A8-40;
  
 A. WOULD YOU PLEASE LABEL DETAILS CORRESPONDING TO FHA
 ONE-EIGHT AND CORRECT THE TYPE. WOULD YOU PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 22. ON SHEETS E1-08 AND E1-08A, IT SHOWS AN OVERLAY
 OVER THE RESTROOM AND THE SINKS. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 23. ON SHEET P0-00;
  
 A. UNDER PLUMBING GENERAL NOTES, IT REFERS TO THE 2017
 CODE, AND 2020 IS THE CURRENT. WOULD YOU PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. WOULD YOU PLEASE PROVIDE THE MINIMUM NUMBER OF
 FIXTURES FOR THE OCCUPANT LOAD BASED ON THE ACTUAL USE
 OF THE BUILDING OR SPACE FOR AMENITIES PER TABLE 403.1
 MINIMUM NUMBER OF FIXTURES AS ON THE LS IF POSSIBLE.
  
 C. FIXTURES UNDER THE COFFEE MAKER/ICE MAKER REQUIRE AN
 INLINE VACUUM BREAKER THAT COMPLIES WITH THE ASSE 1024
 NON-CARBONATED PER THE 2020 FBC SEC. 608.17.1.2.
  
 24. ON SHEET P0-01;
  
 A. ON THE WATER HEATER DETAIL SHOWS THE A/C UNIT
 DUMPING INTO THE SANITARY AND CONDENSATE IS NOT
 PERMITTED TO DISCHARGE INTO THE CITY'S SANITARY SYSTEM
 PER CITY ORDINANCE CHAPTER 90, ARTICLE III, SEC.90-126
 (B)(5). WOULD YOU PLEASE PROVIDE AN ALTERNATE DRAIN PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 B. WOULD YOU PLEASE SHOW AN EXPANSION DEVICE ALL
 DEPENDING ON IF THE SUB-METER IS A RESTRICTED FLOW ONE
 WAY OR A DUAL FLOW. IF A DUAL, WOULD YOU PROVIDE THE
 SPECIFICATION FOR IT PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. FOR THE FLOOR DRAIN DETAIL, A DEEP SEAL TRAP IS NOT
 APPROVED; PLEASE PROVIDE TRAP SEAL PER THE 2020 FBC
 SEC. 1002.4.1 TRAP SEAL PROTECTION.
  
 D. ON THE ELEVATOR PUMP, PLEASE SHOW THE DISCHARGE TO A
 FLOOR IN AN INDIRECT CONNECTION PER THE 2020 FBC SEC P
 712.3.5 PUMP CONNECTION TO THE DRAINAGE SYSTEM.
  
 E. ON THE WASHER BOX DETAIL, PLEASE ADD FIRE-RATED WERE
 NEEDED PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 F. ON THE ROOFTOP HOSE BIBB, WOULD YOU PLEASE SHOW A
 GATE VALVE SHUT OFF PER THE 2020 FBC SEC. 606.2
 LOCATION OF SHUT-OFF VALVES.
  
 H. ON THE BOTTOM RIGHT-HAND CORNER, IT CALLS OUT FOR
 GAS ON THE ROOF. I COULD NOT FIND IT ON THIS SET OF
 PLANS. IF THERE IS ANY TYPE OF GAS SYSTEM, YOU MAY
 CHOOSE TO HAVE IT ON THE SET OF PLANS OR MAKE A NOTE
 THAT A SEPARATE PERMIT WILL BE APPLIED FOR GAS BY A
 LICENSED CONTRACTOR. AN ISOMERIC IS REQUIRED WITH SPECS
 FOR ALL EQUIPMENT AND REGULATOR FOR THIS REVIEW. IF NO
 GAS AT THIS TIME, PLEASE REMOVE ANY GAS DETAILS. WOULD
 YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 25. ON SHEET P0-02;
  
 A. WOULD YOU PLEASE SHOW AND LABEL ALL PIPE VENTED
 THROUGH THE ROOF PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THERE ARE EXPANSION FITTING; PLEASE PROVIDE THE
 STANDARD FOR THE TYPE OF MATERIAL USED PER THE 2020 FBC
 TABLE 702.4 PIPE FITTINGS. WOULD YOU PLEASE PROVIDE THE
 MANUFACTURE'S INSTALLATION INSTRUCTIONS? A TEST TEE MAY
 BE REQUIRED ABOVE EACH FITTING IF AGREED FOR TESTING
 PURPOSES. WOULD YOU PLEASE SHOW ON ISOMETRIC?
  
 C. VERTICAL RISER SHOWS A RISER CLAMP ON EVERY OTHER
 FLOOR. WOULD YOU PLEASE SHOW OR MENTION THAT THEY SHALL
 BE EVERY 10 ? PER THE 2020 FBC TABLE 308.5 HANGER
 SPACING?
  
 D. WOULD YOU PLEASE PROVIDE A CONDENSATE RISER AND SIZE
 IN ACCORDANCE WITH THE 2020 FBC SEC [M]314.2.2 DRAIN
 PIPE MATERIALS AND SIZES. PLEASE NOTE THAT IF
 CONDENSATE IS NOT VENTED THROUGH THE ROOF, IT CANNOT
 TERMINATE IN-WALL DUE TO CONDENSATE LINES THAT HAVE A
 P-TRAP AND ARE UNDER 2020 FBC M307.2.4 AND P1002.1.
 EACH TRAP SHALL BE VENTED TO PERMIT THE ADMISSION OR
 EMISSION OF AIR SO THAT THE SEAL OF ANY FIXTURE TRAP
 SHALL NOT BE SUBJECTED TO A PRESSURE DIFFERENTIAL OF
 MORE THAN 1 INCH OF WATER COLUMN PER THE 2020 FBC
 SECTION 901.2 TRAP SEAL PROTECTION. THEY CANNOT
 TERMINATE IN A WALL AS IT HAS NO NEGATIVE OR POSITIVE
 PRESSURE TO ALLOW IT TO HAVE A DIFFERENTIAL OF ONE-INCH
 WATER COLUMN. YOU MAY VENT IN THE A/C PLENUM, BUT IT
 HAS TO BE CPVC AS THE FLAME INDEX DOES NOT ALLOW PVC.
 WOULD YOU PLEASE PROVIDE DETAIL?
  
 F. WOULD YOU PLEASE SHOW THE DFU ON THE BOTTOM OF EACH
 RISER PER THE 2020 FBC TABLE 710.1(2) HORIZONTAL
 FIXTURE BRANCHES AND STACKS.
  
 G. PLEASE PROVIDE A SANITARY RISER ISOMETRIC DIAGRAM
 FOR THE MAIN SEWER LINE WITH SIZES THAT GOES THROUGH
 THE BUILDING AND MATCH STACK RISERS CONNECTION POINTS
 ON P0-02 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 26. ON SHEET P1-00H;
  
 A. THERE IS A SECTIONAL VIEW FOR 7- H-5, AND NO SUCH
 PAGE WAS FOUND. WOULD YOU PLEASE PROVIDE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. THE THREE IN SANITARY SAYS SEE CIVIL DRAWING OR
 CONTINUATION A COULD NOT MATCH. WOULD YOU PLEASE
 PROVIDE THE PAGE NUMBER AFTER THE CONTINUATION COMMENT
 PER THE WOULD YOU PLEASE PROVIDE PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 C. THERE SEEMS TO BE TWO BBQS IN THE POOL AREA. DO THEY
 REQUIRE GAS OR PORTABLE PROPANE TANKS? IF GAS, PLEASE
 REFER TO P0-01 (H) COMMENT PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 27. ON SHEET P1-01A AND P1-01B,
  
 A. WOULD YOU PLEASE SHOW THE FIRST FLOOR SANITARY AND
 ITS CORRESPONDING SANITARY RISER TO MATCH P0-02 PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. THERE IS A SINK IN THE CLUB ROOM (P1-01A) THAT HAS
 NO PAGE CONTINUATION OF THE SANITARY WOULD YOU PLEASE
 ADD IT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. THE SINK IN THE WORKROOM AND RESTROOM AREA (P1-01B),
 WOULD YOU PLEASE SHOW THE CONTINUATION PAGE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. ON THE TWO 8" SANITARY, IT REFERS TO THE CIVIL WOULD
 YOU PLEASE PROVIDE THE PAGE IN REFERENCE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 E. THERE IS A 6" MANUAL FSP W/ FDV THAT MENTIONS F/1,
 AND I COULD NOT FIND A DETAIL. DOES THIS INCUR A FLOOR
 DRAIN, AND IF SO IT NEEDS TO BE CAST IRON AS IT IS IN
 THE FIRE-RATED STAIRWELL?
  
 28. ON SHEETS P1-02 A AND P1-02B, THE WATER RISERS NEED
 TO SHOW THE SHUT-OFF VALVES AND THEIR ACCESS PANEL
 OUTSIDE THE UNIT. WOULD YOU PLEASE PROVIDE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 29. ON SHEET P1-02A, THE TRASH SHOOT MAY REQUIRE A HOSE
 BIBB AND WATER FOR SANITIZING SYSTEM ON THE EIGHTH
 FLOOR; IF SO, PLEASE SHOW PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 30. ON SHEET P1-09A AND P1-09B;
  
 A. IT HAS A NOTE THAT REFERS TO THE SCUPPERS AND
 DOWNSPOUTS. WOULD YOU PROVIDE THE PAGE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE PROVIDE AN ISOMETRIC WITH THE SIZE
 OF PIPES, ROOF DRAINS, AND SCUPPER DETAIL, AND
 LOCATIONS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 C. STORM WATER FORMULA IS REQUIRED, ALONG WITH A TABLE
 THAT SHOWS SQUARE FOOTAGE AND GALLONS PER MINUTE. SO
 PLEASE SIZE PER THE 2020 FBC SEC. P1106.
  
 D. WOULD YOU PLEASE IDENTIFY ALL THE STORM RISERS WITH
 RISER TAGS PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 E. WOULD YOU PLEASE PROVIDE THE LOCATION OF THE ROOF
 DRAIN WITH PRIMARY AND SECONDARY (EMERGENCY OVERFLOW)
 ROOF DRAINS OR SCUPPERS WHICH SHALL BE PROVIDED WHERE
 THE ROOF PERIMETER CONSTRUCTION EXTENDS ABOVE THE ROOF
 IN SUCH A MANNER THAT WATER WILL B ENTRAPPED IF THE
 PRIMARY DRAINS ALLOW BUILDUP FOR ANY REASON PER THE
 2020 FBC SEC. P 1108.1 SECONDARY (EMERGENCY OVERFLOW)
 DRAINS OR SCUPPERS.
  
 31. ON SHEET P3-01;
  
 A. WOULD YOU PLEASE PROVIDE A SANITARY ISOMETRIC
 DRAWING PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 B. HOT WATER LINES LOOPED FOR THE RECIRCULATING SYSTEM
 ARE NOT IN A CONTINUOUS LOOP. THERE IS A REQUIREMENT IN
 THE FLORIDA ENERGY CODE SEC. C404.6.1. THERE IS A TABLE
 THAT LIMITS THE DISTANCE BETWEEN THE SOURCE AND THE
 OUTLET; PLEASE REFER TO TABLE 404.5.1 FOR THE MAXIMUM
 ALLOWABLE PIPE LENGTH METHOD AND SIZE ACCORDANTLY.
  
 C. WOULD YOU PLEASE INCORPORATE THE SANITARY LINES AND
 SIZE OF THE DISCHARGE FROM THE ELEVATORS TO THE DRAIN
 THAT CORRESPONDS TO THE ISOMETRIC AND FLAT DRAWINGS PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 D. IN THE MANAGER'S OFFICE, IT SHOWS A SINK; IF IT IS
 NOT USED, WOULD YOU PLEASE CORRECT IT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 E. WOULD YOU PLEASE PROVIDE DETAIL FOR THE WATER HEATER
 IN THE JANITOR'S ROOM AND SHOW FOR SANITARY AND WATER
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 F. IT SEEMS THAT A JANITOR'S SINK IS REQUIRED, AND ONE
 IS NOT PRESENT FOR THE ASSEMBLY TYPE. WOULD YOU PLEASE
 PROVIDE ONE PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL SHALL
 BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE 2020
 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P 310.3.
 WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET?
  
 32. ON SHEET P3-02;
  
 A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE AS
 REQUESTED IN THE ARCHITECTURAL COMMENTS.
  
 B. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE OF 30" X
 48" IN THE LAVS OF THE AMENITY WOMEN'S AND MEN'S PER
 THE 2020 FBC SEC. ACC 305.3.
  
 C. DETAIL TWO; WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE OF 30" X 48" IN THE LAVS OF THE AMENITY WOMEN'S
 AND MEN'S PER THE 2020 FBC SEC. ACC 305.3.
  
 33. ON SHEETS P8-01, P802 AND P803, IT SHOWS THE
 WASHING MACHINE BOX BEHIND THE UNITS AND SHALL BE
 ACCESSIBLE WITHOUT MOVING THE UNIT AND WITHIN REACH PER
 THE 2020 FBC SEC. P 606.3 ACCESS TO VALVES.
  
 34. WHEN YOU REFER TO A SANITARY STACK OR WATER, WOULD
 YOU PLEASE DO IT AS S-1 IN THE TOP (RISER) AND THE PAGE
 NUMBER ON THE BOTTOM FOR CLARITY PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 PLEASE FEEL FREE TO SET UP A MEETING OR CONTACT ME ON
 ANY OF THE COMMENTS BY PHONE OR ZOOM MEETING IF YOU
 LIKE TO PREVENT FURTHER REVIEWS.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  