Plan Review Notes
Plan Review Notes For Permit 21100002
Permit Number 21100002
Review Stop M
Sequence Number 1
Notes
Date Text
2021-11-08 10:22:081ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21100002
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR EACH SYSTEM IN THIS NEW BUILDING. FBC
 EC C403.2.1.
  
 2) PLEASE SHOW WHICH CONDITION APPLIES FOR THE I-1
 OCCUPANCY. FBC 308.3
  
 3) PLEASE MAKE SURE THE SUBMITTED DRAWINGS AND
 SPECIFICATIONS ARE UNDER THE 2020 FBC 7TH EDITION AND
 NOT THE 2018 IMC OR ANY OTHER VERSION.
  
 4) PLEASE REFERENCE THE CURRENT EDITION OF ASHRAE
 62.1-2016
  
 5) SHEET M0.06: THE DAYROOM OUTDOOR AIR CALCULATIONS
 ARE LOW BASED ON THE OCCUPANT DENSITY PER TABLE 6.2.2.1
  
 6) SHEET M0.06: THE AEROBICS ROOM OUTDOOR AIR
 CALCULATIONS ARE LOW BASED ON THE OCCUPANT DENSITY PER
 TABLE 6.2.2.1.
  
 7) SHEET M0.06: THE LOBBIES OUTDOOR AIR CALCULATIONS
 ARE LOW BASED ON THE OCCUPANT DENSITY PER TABLE 6.2.2.1
  
 8) SHEET M0.06: THE BIKE STORAGE OUTDOOR AIR
 CALCULATIONS ARE LOW BASED ON THE OCCUPANT DENSITY PER
 TABLE 6.2.2.1
  
 9) SHEET M1-01: PLEASE ADD A NOTE ON THE DRAWING
 STATING THAT THE GENERATOR WILL NEED A SEPARATE
 MECHANICAL PERMIT APPLICATION AND PLAN REVIEW AS IT
 WILL NOT BE REVIEWED UNDER THIS PERMIT APPLICATION.
  
 10) SHEET M1-01: PLEASE SHOW THE CONDENSATE DRAIN
 TERMINATION IS NOT BEING DRAINED INTO THE BUILDING
 SEWER. ARTICLE III SEC. 90-126 NUMBER 5
  
 11) SHEET M1-01: PLEASE SHOW FIRE DAMPERS IN EVERY
 LOCATION WHERE THE DUCT PENETRATES A RATED WALL. FBC M
 607
  
 12) PLEASE MAKE SURE THAT THE 6 INCH OUTDOOR AIR DUCT
 FOR THE CORRIDOR MECHANICAL SYSTEMS ARE PULLING AIR
 FROM THE OUTDOORS ON EACH FLOOR. THE ARROWS INDICATE
 THIS IS AN EXHAUST PIPE. FBC 107.2.1
  
 13) PLEASE REMOVE SHEET M1-09 ALT- ROOF PLAN AS THE
 PLANS SUBMITTED SHOULD NOT HAVE ALTERNATES. FBC 107.2.1
  
 14) SHEET M3-01: THE 8 INCH DUCT SHOWN IN THE DOG
 GROOMING AREA APPEARS TO BE SUPPLYING OUTDOOR AIR TO
 THE DOG GROOMING ROOM. PLEASE SHOW THE VOLUME DAMPER.
 FBC 107.2.1
  
 15) SHEET M3-01: PLEASE SHOW HOW THE BIKE ROOM IS
 NATURALLY VENTILATED AND PROVIDE THE CALCULATIONS FOR
 NATURAL VENTILATION. FBC M 402
  
 16) SHEET M3-01: PLEASE REMOVE THE TXR TRANSFER GRILLES
 IN THE WALL BETWEEN THE MALE AND FEMALE BATHROOMS AND
 THE FITNESS ROOM AS PULLING RETURN AIR FROM THE BATH
 ROOMS IS NOT ALLOWED. FBC M 601.5-7
  
 17) SHEET M0-06: PLEASE TAKE ANOTHER LOOK AT THE
 OUTDOOR AIR CALCULATIONS AS SOME APPEAR TO BE LOW.
 EXAMPLE: THE CLUB DAYROOM OCCUPANT COUNT SHOWS ONLY 15
 PEOPLE BUT THERE ARE MORE SEATS IN THIS AREA THAN 15.
 THERE IS ALSO STANDING ROOM IN THIS AREA. THIS AREA
 SHOULD BE BASED ON THE OCCUPANT DENSITY PER TABLE
 6.2.2.1 AS SHOULD THE OTHER AREAS.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  