2021-11-08 11:57:42NEW 8 STORY R2
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) WALL HOURLY FIRE RATINGS ARE NOT CLEARLY SHOWN -
 FLOOR PLANS SHOW SOME BUT NOT ALL OF THE FIRE WALL
 RATINGS - LS PLANS DO NOT SHOW THE MECHANICAL (STORAGE)
 AND ELECTRICAL (STORAGE ROOM) WALL RATINGS BETWEEN
 UNITS.
  
 2) CORRIDOR REQUIRES A FIRE RATING TO BE CONTINOUS -
 SOME OF THE STORAGE ROOMS (ELECTRIC/MECHANICAL) DO NOT
 SHOW THE CORRIDOR WALLS AND DOORS TO BE RATED - FBC
 1020.6
  
 3) PLYWOOD ROOF SHEATHING SHOULD BE SHOWN AS FIRE
 RETARDANT - FBC 603.1
  
 4) DRAWING S100 SHOWS DESIGN PER THE 2017 FBC - PLEASE
 REVISE TO THE CODE IN EFFECT 2020 FBC
  
 5) PLEASE SHOW THE EMERGENCY EGRESS FOR THE BEDROOMS -
 FBC 1030.1 GENERAL.
 IN ADDITION TO THE MEANS OF EGRESS REQUIRED BY THIS
 CHAPTER, PROVISIONS SHALL BE MADE FOR EMERGENCY ESCAPE
 AND RESCUE OPENINGS IN GROUP R-2 OCCUPANCIES IN
 ACCORDANCE WITH TABLES 1006.3.3(1) AND 1006.3.3(2) AND
 GROUP R-3 OCCUPANCIES. BASEMENTS AND SLEEPING ROOMS
 BELOW THE FOURTH STORY ABOVE GRADE PLANE SHALL HAVE AT
 LEAST ONE EXTERIOR EMERGENCY ESCAPE AND RESCUE OPENING
 IN ACCORDANCE WITH THIS SECTION.
  
 6) PLEASE SHOW FIRE RATED DOORS TO BE SELF CLOSING AND
 SELF LATCHING - FBC 716.5.9
  
 7) WALLS MARKED 10 ON DRAWING A3-52 (DETAIL 1 AND 2)
 SHOULD BE SHOWN AS FIRE RATED.
  
 8) PLEASE SHOW COMMON AREA RESTROOM WALL FINISHES - FBC
 1210.2
  
 9) PLEASE PROVIDE STRUCTURAL DETAILS FOR THE SLOPE ROOF
 AREAS AT PORTE COCHERE AND BUILDING ROOF - SLOPE,
 FRAMING, TRUSS TIE DOWNS, SHEATHING SIZE AND
 ATTACHMENTS ETC. FBC WPB 107.2.1
  
 10) SOME PLANS HAVE NOTES REFERRING TO THE IBC (SUCH AS
 THE LS DRAWINGS - FIRE WALL NOTES) - PLEASE HAVE NOTES
 REFER TO THE FBC
  
 11) PLEASE PROVIDE STATEMENTS ON THE DRAWINGS FOR THE
 REQUIRED FIRE CLASSIFICATION FOR THE WALL, CEILING AND
 FLOOR FINISHES PER - FBC CHAPTER 8
  
 12) PLEASE PROVIDE ACCESSIBLE COMMON AREA AND RESTROOM
 DETAILS - LOCATION DIMENSIONS FOR GRAB BARS, TOILET
 PAPER HOLDER, FIXTURE CLEAR FLOOR SPACE, DOOR
 MANUVERING CLEARANCE, SEATING AT TABLES, ACCESSIBLE
 PATH AROUND GAMING AND FITNESS AREA ETC. - FBC A FHA
 REQUIREMENT #2
  
 13) PLEASE PROVIDE BACKING DETAILS FOR GRAB BARS
 ETC.(TYPE OF MATERIAL AND ATTACHMENTS TO FRAMING) - FBC
 A FHA REQUIREMENT #6
  
 14) PLEASE SHOW THE 8TH FLOOR COMMON AREA AMENITY
 TERRACE AND RESTROOMS TO COMPLY WITH ACCESSIBILITY
 (SHOW DIMENSIONS AND GRAB BARS) - FBC A FHA REQUIREMENT
 #2
  
 15) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS,
 ROOFING SYSTEMS ETC. - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD FBC WPB 107.2.1
  
 16) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 17) PLEASE PROVIDE DETAILS FOR THE ALUMINUM TRELLIS TO
 COMPLY WITH THE REQUIRED WIND LOADS FBC 1609
  
 18) PLEASE PROVIDE DETAILS FOR THE FIBER CEMENT SIDING
 TO COMPLY WITH THE WIND LOADS FBC 1609
  
 19) A SEPARATE PERMIT IS REQUIRED FOR POOL, POOL
 PAVILION, DETACHED CANOPIES, PARKING LOT PAVING AND
 STRIPING, FENCES - PLEASE ACKNOWLEDGE THIS.
  
 20) SIDING DETAILS, ALUMINUM TRELLIS, ROOFING SYSTEMS,
 AND WINDOW AND DOOR PRODUCT APPROVALS JUST TO NAME A
 FEW - MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS TO BE
 DEFERRED ON THE CONSTRUCTION DOCUMENTS - 107.3.4.1
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
 21) PLEASE SHOW ELEVATOR DIMENSIONS - FBC 3002.4
 ELEVATOR CAR TO ACCOMMODATE AMBULANCE STRETCHER.
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 (7620 MM), MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE
 PASSENGER ELEVATOR THAT IS OPERATIONAL FOR BUILDING
 OCCUPANTS AND FIRE DEPARTMENT EMERGENCY ACCESS TO ALL
 FLOORS. THE ELEVATOR CAR SHALL BE OF SUCH A SIZE AND
 ARRANGEMENT TO ACCOMMODATE AN AMBULANCE STRETCHER 24
 INCHES BY 76 INCHES (610 MM BY 1950 MM) WITH NOT LESS
 THAN 5-INCH (127 MM) RADIUS CORNERS, IN THE HORIZONTAL,
 OPEN POSITION AND SHALL BE IDENTIFIED BY THE
 INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL SERVICES
 (STAR OF LIFE). THE SYMBOL SHALL BE NOT LESS THAN 3
 INCHES (76 MM) IN HEIGHT AND SHALL BE PLACED INSIDE ON
 BOTH SIDES OF THE HOISTWAY DOOR FRAME.
  
 22) PLEASE SHOW STEEL COLUMNS ON THE FLOOR PLANS TO BE
 FIRE RATED PER FBC 601
  
 23) PLEASE SHOW STEEL COLUMN ATTACHMENTS TO CONCRETE
 SLABS ABOVE AND BELOW FBC 107.2.1
  