| 2021-11-08 11:57:42 | NEW 8 STORY R2 |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | 1) WALL HOURLY FIRE RATINGS ARE NOT CLEARLY SHOWN - |
| | FLOOR PLANS SHOW SOME BUT NOT ALL OF THE FIRE WALL |
| | RATINGS - LS PLANS DO NOT SHOW THE MECHANICAL (STORAGE) |
| | AND ELECTRICAL (STORAGE ROOM) WALL RATINGS BETWEEN |
| | UNITS. |
| | |
| | 2) CORRIDOR REQUIRES A FIRE RATING TO BE CONTINOUS - |
| | SOME OF THE STORAGE ROOMS (ELECTRIC/MECHANICAL) DO NOT |
| | SHOW THE CORRIDOR WALLS AND DOORS TO BE RATED - FBC |
| | 1020.6 |
| | |
| | 3) PLYWOOD ROOF SHEATHING SHOULD BE SHOWN AS FIRE |
| | RETARDANT - FBC 603.1 |
| | |
| | 4) DRAWING S100 SHOWS DESIGN PER THE 2017 FBC - PLEASE |
| | REVISE TO THE CODE IN EFFECT 2020 FBC |
| | |
| | 5) PLEASE SHOW THE EMERGENCY EGRESS FOR THE BEDROOMS - |
| | FBC 1030.1 GENERAL. |
| | IN ADDITION TO THE MEANS OF EGRESS REQUIRED BY THIS |
| | CHAPTER, PROVISIONS SHALL BE MADE FOR EMERGENCY ESCAPE |
| | AND RESCUE OPENINGS IN GROUP R-2 OCCUPANCIES IN |
| | ACCORDANCE WITH TABLES 1006.3.3(1) AND 1006.3.3(2) AND |
| | GROUP R-3 OCCUPANCIES. BASEMENTS AND SLEEPING ROOMS |
| | BELOW THE FOURTH STORY ABOVE GRADE PLANE SHALL HAVE AT |
| | LEAST ONE EXTERIOR EMERGENCY ESCAPE AND RESCUE OPENING |
| | IN ACCORDANCE WITH THIS SECTION. |
| | |
| | 6) PLEASE SHOW FIRE RATED DOORS TO BE SELF CLOSING AND |
| | SELF LATCHING - FBC 716.5.9 |
| | |
| | 7) WALLS MARKED 10 ON DRAWING A3-52 (DETAIL 1 AND 2) |
| | SHOULD BE SHOWN AS FIRE RATED. |
| | |
| | 8) PLEASE SHOW COMMON AREA RESTROOM WALL FINISHES - FBC |
| | 1210.2 |
| | |
| | 9) PLEASE PROVIDE STRUCTURAL DETAILS FOR THE SLOPE ROOF |
| | AREAS AT PORTE COCHERE AND BUILDING ROOF - SLOPE, |
| | FRAMING, TRUSS TIE DOWNS, SHEATHING SIZE AND |
| | ATTACHMENTS ETC. FBC WPB 107.2.1 |
| | |
| | 10) SOME PLANS HAVE NOTES REFERRING TO THE IBC (SUCH AS |
| | THE LS DRAWINGS - FIRE WALL NOTES) - PLEASE HAVE NOTES |
| | REFER TO THE FBC |
| | |
| | 11) PLEASE PROVIDE STATEMENTS ON THE DRAWINGS FOR THE |
| | REQUIRED FIRE CLASSIFICATION FOR THE WALL, CEILING AND |
| | FLOOR FINISHES PER - FBC CHAPTER 8 |
| | |
| | 12) PLEASE PROVIDE ACCESSIBLE COMMON AREA AND RESTROOM |
| | DETAILS - LOCATION DIMENSIONS FOR GRAB BARS, TOILET |
| | PAPER HOLDER, FIXTURE CLEAR FLOOR SPACE, DOOR |
| | MANUVERING CLEARANCE, SEATING AT TABLES, ACCESSIBLE |
| | PATH AROUND GAMING AND FITNESS AREA ETC. - FBC A FHA |
| | REQUIREMENT #2 |
| | |
| | 13) PLEASE PROVIDE BACKING DETAILS FOR GRAB BARS |
| | ETC.(TYPE OF MATERIAL AND ATTACHMENTS TO FRAMING) - FBC |
| | A FHA REQUIREMENT #6 |
| | |
| | 14) PLEASE SHOW THE 8TH FLOOR COMMON AREA AMENITY |
| | TERRACE AND RESTROOMS TO COMPLY WITH ACCESSIBILITY |
| | (SHOW DIMENSIONS AND GRAB BARS) - FBC A FHA REQUIREMENT |
| | #2 |
| | |
| | 15) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS, |
| | ROOFING SYSTEMS ETC. - ALL PRODUCT APPROVALS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER |
| | OF RECORD FBC WPB 107.2.1 |
| | |
| | 16) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. |
| | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING |
| | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY |
| | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP |
| | CEILING DESCRIPTION) |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP |
| | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING |
| | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED |
| | DROP CEILING DESCRIPTION) |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS |
| | ATTACHED TO THE FLOORING) |
| | |
| | 17) PLEASE PROVIDE DETAILS FOR THE ALUMINUM TRELLIS TO |
| | COMPLY WITH THE REQUIRED WIND LOADS FBC 1609 |
| | |
| | 18) PLEASE PROVIDE DETAILS FOR THE FIBER CEMENT SIDING |
| | TO COMPLY WITH THE WIND LOADS FBC 1609 |
| | |
| | 19) A SEPARATE PERMIT IS REQUIRED FOR POOL, POOL |
| | PAVILION, DETACHED CANOPIES, PARKING LOT PAVING AND |
| | STRIPING, FENCES - PLEASE ACKNOWLEDGE THIS. |
| | |
| | 20) SIDING DETAILS, ALUMINUM TRELLIS, ROOFING SYSTEMS, |
| | AND WINDOW AND DOOR PRODUCT APPROVALS JUST TO NAME A |
| | FEW - MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS TO BE |
| | DEFERRED ON THE CONSTRUCTION DOCUMENTS - 107.3.4.1 |
| | DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, |
| | DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF |
| | THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED |
| | SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL |
| | REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL |
| | WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 21) PLEASE SHOW ELEVATOR DIMENSIONS - FBC 3002.4 |
| | ELEVATOR CAR TO ACCOMMODATE AMBULANCE STRETCHER. |
| | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN |
| | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL |
| | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET |
| | (7620 MM), MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE |
| | PASSENGER ELEVATOR THAT IS OPERATIONAL FOR BUILDING |
| | OCCUPANTS AND FIRE DEPARTMENT EMERGENCY ACCESS TO ALL |
| | FLOORS. THE ELEVATOR CAR SHALL BE OF SUCH A SIZE AND |
| | ARRANGEMENT TO ACCOMMODATE AN AMBULANCE STRETCHER 24 |
| | INCHES BY 76 INCHES (610 MM BY 1950 MM) WITH NOT LESS |
| | THAN 5-INCH (127 MM) RADIUS CORNERS, IN THE HORIZONTAL, |
| | OPEN POSITION AND SHALL BE IDENTIFIED BY THE |
| | INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL SERVICES |
| | (STAR OF LIFE). THE SYMBOL SHALL BE NOT LESS THAN 3 |
| | INCHES (76 MM) IN HEIGHT AND SHALL BE PLACED INSIDE ON |
| | BOTH SIDES OF THE HOISTWAY DOOR FRAME. |
| | |
| | 22) PLEASE SHOW STEEL COLUMNS ON THE FLOOR PLANS TO BE |
| | FIRE RATED PER FBC 601 |
| | |
| | 23) PLEASE SHOW STEEL COLUMN ATTACHMENTS TO CONCRETE |
| | SLABS ABOVE AND BELOW FBC 107.2.1 |
| | |