Notes
Date Text
2021-11-10 17:41:10BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RE: 345 SHUTTERS
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SUBMIT A SEPERATE PERMIT FOR EACH STRUCTURE (6
 TOTAL). INCLUDE CORRECT ADDRESS AND PCN NUMBER. ASSIGN
 THE APPROPRIATE VALUE TO EACH PERMIT BASED ON THE
 NUMBER AND TYPE OF SHUTTERS TO BE INSTALLED.
 PERMITS - 105.1 REQUIRED.
  
 2. PROVIDE ELEVATION VIEWS OF EACH STRUCTURE. IDENTIFY
 THE PLANS BY ADDRESS. SHOW LOCATION OF SHUTTERS ON EACH
 FLOOR LEVEL AND EACH ELEVATION (N/S/E/W).
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
 NOTE: THE FLOOR PLANS AND PHOTOS ATTACHED TO YOUR
 E-MAIL WILL WORK FOR THE COLOMIAL MASTER SHUTTERS.
 (NEED ATTACCHMENT DETAIL OR FASTENER SCHEDULE FOR EACH
 OF THE 3 SIZES OF COLONIAL SHUTTERS)
  
 3. PROVIDE A CURRENT FLORIDA PRODUCT APPROVAL OR A SHOP
 DRAWING OF EACH TYPE OF SHUTTER. SHOP DRAWING SHALL BE
 PEREPARED BY A QUALIFIED DESIGN PROFESSIONAL, SIGNED
 AND SEALED.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 4. FLOOR PLANS OF EACH STRUCTURE SHALL BE IDENTIFYED BY
 ADDRESS. FLOOR PLANS SUBMITTED FOR REVIEW APPEAR TO BE
 FOR 1 LEVEL OF A 4 STORY STRUCTURE. PLEASE CLARIFY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 5. DESIGN PRESSURE CALCULATIONS SHALL BE PREPARED BY A
 QUALIFIED DESIGN PROFESSIONAL. CALCULATIONS SHALL BE
 BASED ON THE FBC CHPT. 16 OR ASCE 7-16.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 6. IDENTIFY DESIGN PRESSURE CALCULATIONS BY BUILDING
 ADDRESS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 7. DESIGN PRESSURE CALCULATIONS SUBMITTED FOR REVIEW
 REFERENCE DEVICE WIDTH. FLOOR PLANS SUBMITTED FOR
 REVIEW REFERENCES OPENING WIDTH. PLEASE CLARIFY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 8. DESIGN PRESSURE CALCULATIONS, FLOOR PLANS AND
 ELEVATION VIEWS SHALL BE COORDINATED.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 9. DESIGN PRESSURE CALCULATINS SUBMITTED FOR REVIEW
 REFERENCE INTERIOR ZONES ONLY. PROVIDE PRESSURES FOR
 SHUTTERS LOCATED IN EXTERIOR ZONES (ZONE 5).
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  