Plan Review Notes
Plan Review Notes For Permit 21091343
Permit Number 21091343
Review Stop M
Sequence Number 4
Notes
Date Text
2022-09-08 09:04:364TH REVIEW FMC
 PERMIT: 21091343
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NARRATIVES SUBMITTED STATES M-203- PROVIDE FIRE
 DAMPER FOR AHU-1L-2 OUTSIDE AIR DUCT PENETRATION, THIS
 IS NOT ON THIS SHEET, THIS IS LOCATED ON M205. ALSO,
 THE NARRATIVE STATES THAT THE SPF-1A HAS BEEN RELOCATED
 TO THE 6TH LEVEL, PLEASE SUBMIT THIS DRAWING SHOWING
 THE CHANGE. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  