| 2022-08-05 13:56:10 | 1. SATISFIED- PLEASE INCLUDE A TABLE WITH ALL THE |
| | PROJECT DATA (UPDATED SHEET A.001 IN SITE PLAN SET) - |
| | PLEASE PROVIDE A COMPLETE SITE PLAN INDICATING THE |
| | MINIMUM SETBACKS, SIDEWALK WIDTH, PLANNING AREAS, TREE |
| | LOCATIONS, BIKE RACKS AND BENCHES. |
| | 2. SATISFIED. PLEASE EXPLAIN THE DIFFERENCE IN GBA |
| | BETWEEN THE APPROVED 424,004 SF IN THE SITE PLAN |
| | DOCUMENTS AND THE 368,240 SF LISTED IN THE BUILDING |
| | PERMIT SET. |
| | 3. SATISFIED -PLEASE ADJUST THE SETBACK TABLE IN SHEET |
| | A0-002 AS IT LISTS A SIDE SETBACK OF 157?. |
| | 4. SATISFIER - FULLY ENCLOSED STORAGE ON THE GROUND |
| | FLOOR COUNTS AS PART OF THE GBA. |
| | 5. SATISFIED- PLEASE EXPLAIN THE PUBLIC OPEN SPACE |
| | DIAGRAM IN SHEET A0-005. IT DOES NOT MATCH APPROVED |
| | SITE PLAN. |
| | 6. SATISFIED - PLEASE PROVIDE A FA?ADE DIAGRAM TO |
| | CONFIRM COMPLIANCE WITH TRANSPARENCY REQUIREMENT AS |
| | MEASURED ACCORDING TO SEC 94-109 OF THE ZLDRS. |
| | 7. SATISFIED - A TURN AROUND SPACE SHALL BE PROVIDED |
| | FOR THE GROUND FLOOR DEAD END PARKING. |
| | 8. SATISFIED - SOME OF THE PARKING SPACES HAVE COLUMNS |
| | THAT OBSTRUCT THE OPENING OF THE CAR DOOR. PLEASE |
| | ADJUST STALL DIMENSION ACCORDING TO SEC 94-110 (C). - |
| | PARKING STALLS WITH A COLUMN OR WALL LOCATED NEXT TO |
| | DOOR OPENING AREA SHALL BE WIDENED BY 1 FOOT. |
| | 9. SATISFIED- ALL MECHANICAL EQUIPMENT ON ROOF SHALL BE |
| | CONSOLIDATED/GROUP AS MUCH AS POSSIBLE AND SCREENED |
| | WITH A SCREEN AS TALL AS THE EQUIPMENT MAKING IT AN |
| | INTEGRAL PART OF THE OVERALL BUILDING DESIGN. |
| | 10. NOT SATISFIED ? IF TREATMENT FROM SITE PLAN CANNOT |
| | BE ACHIEVED, FURTHER DISCUSSIONS ARE NEEDED TO ENHANCE |
| | THE FA?ADE. AN OPTION IS TO MAINTAIN THE PATTERN BUT |
| | WILL NO OPENINGS. - SOUTH ELEVATION DOES NOT SEEM TO |
| | MATCH APPROVED SITE PLAN ELEVATION WITHIN THE PARKING |
| | GARAGE AREA. PLEASE ADJUST. |
| | 11. SATISFIED - PLEASE EXPLAIN THE REASON WHY THE TOP |
| | LEVEL OF THE PARKING GARAGE IS NOW A 12? FINISHED FLOOR |
| | TO FINISHED FLOOR. AMENITY DECK HEIGHT WAS REDUCED FROM |
| | 14? TO 12? AND THAT SEEMS TO AFFECT THE PROPORTIONS AND |
| | SEPARATION OF BASE AND TOWER. |
| | 12. SATISFIED. PLEASE STUDY MAINTAINING A WINDOW |
| | SIMILAR TO APPROVED SITE PLAN. - GROUND FLOOR WINDOW OF |
| | SOUTH END RESIDENTIAL UNIT HAS BEEN CHANGED FROM |
| | APPROVED. PLEASE ADJUST. |
| | 13. SATISFIED - SITE PLAN APPROVAL INCLUDED AN EYE |
| | BROS-CANOPY TURNING THE CORNER FROM NORTH FA?ADE TO |
| | EAST AT THE RETAIL LEVEL. PLEASE JUSTIFY WHY IT WAS |
| | REMOVED. |
| | 14. SATISFIED- LOADING ENTRANCE ALONG CLEARWATER DRIVE |
| | SHALL INCLUDE AN OPAQUE DECORATIVE GATE. |
| | 15. LANDSCAPE DRAWINGS SHALL BE REMOVED FROM THIS |
| | PERMIT AND SUBMITTED UNDER A SEPARATE LANDSCAPE PERMIT. |
| | 16. SATISFIED - PLEASE INDICATE THE LOCATION OF THE |
| | MICROMOBILITY STATION. |
| | 17. SATISFIED ? PLEASE ADD A NOTE IN CIVIL DRAWINGS |
| | STATING THAT THE SIDEWALK ELEVATION SHALL BE MAINTAINED |
| | ACROSS THE DRIVEWAY .- SIDEWALK ELEVATION SHALL BE |
| | MAINTAINED ACROSS DRIVEWAY. PLEASE PROVIDE SECTIONS OR |
| | DETAILS TO CONFIRM COMPLIANCE. |
| | 18. SATISFIED - PLEASE PROVIDE CROSS SECTION OF THE |
| | SIDEWALK LEVEL TO CONFIRM GRADES ARE MET. |
| | 19. PARTIALLY SATISFIED - CLEARLY INDICATE THE |
| | BOUNDARIES OF THE REQUIRED PUBLIC OPEN SPACE AREA.- |
| | PLEASE PROVIDE OPEN SPACE DIAGRAM TO MATCH APPROVED |
| | SITE PLAN. |
| | 20. PARTIALLY SATISFIED. PLEASE INCLUDE LOCATIONS AND |
| | SPECS OF FIXTURES AND POLES ALONG CLEARWATER DRIVE TO |
| | CONFIRM COMPLIANCE WITH THE MINIMUM 0.6 FOOTCANDLE |
| | REQUIRED. SPEC FOR FIXTURE AND POLE SHALL COMPLY WITH |
| | CITY STANDARD. -PLEASE PROVIDE PHOTOMETRICS FOR THE |
| | GROUND FLOOR PUBLIC REALM AND CONFIRM COMPLIANCE WITH |
| | THE REQUIRED CITY STANDARD LIGHT FIXTURE. |
| | ADDITIONAL COMMENTS: |
| | 21. NOT SATISFIED-SOUTH ELEVATION DOES NOT MATCH |
| | APPROVED DESIGN FOR THE GARAGE SCREENING. PLEASE ADJUST |
| | OR JUSTIFY CHANGES. |
| | 22. SATISFIED- SOUTH WINDOW FOR THE CORNER UNIT WAS |
| | REMOVED CHANGING APPROVED SITE PLAN. PLEASE ADJUST OR |
| | JUSTIFY CHANGE. |
| | 23. SATISFIED - BIKE RACKS ON NORTH SIDE OF LOBBY NEED |
| | TO BE REPOSITION. AS PROPOSED, SOME OF THE SPACES ARE |
| | NOT ACCESSIBLE. |
| | 24. SATISFIED- PLEASE CLEARLY INDICATE WHICH PORTIONS |
| | OF THE GARAGE FA?ADE ARE OPEN. |
| | 25. PARTIALLY SATISFIED - PLEASE CORRECT ADA STALL |
| | PAINTING DETAIL IN SHEET A6-401. NEEDS TO MATCH CITY |
| | STANDARD IN SECT 94-485 FOR LINE PAINTING WITH THE ADA |
| | DIMENSIONS.- PARKING STALL PAINTING DETAIL SHALL FOLLOW |
| | CITY STANDARD (SEC 94-485) PLEASE REVISE DETAIL IN |
| | SHEET A6-401. |
| | ADDITIONAL COMMENTS: |
| | 26. SHEET A1-101 IDENTIFIES THE MICROMOBILITY STATION |
| | IS THE WRONG LOCATION (NW CORNER OF BUILDING) PLEASE |
| | REMOVE NOT TO AVOID CONFUSION. |
| | |
| | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA |
| | APONTE AT 561-822-1439 |