| 2022-07-29 08:54:33 | 3RD REVIEW FMC |
| | PERMIT: 21091343 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THERE SEEMS TO BE SEVERAL CHANGES THROUGHOUT THE |
| | REVISED DRAWINGS WITH NO MENTION OF THESE CHANGES IN A |
| | NARRATIVE. PLEASE SUBMIT A NARRATIVE FOR THESE CHANGES. |
| | BELOW IS A PARTIAL LIST OF COMMENTS TO THESE CHANGES. I |
| | CANNOT DO A COMPLETE REVIEW WITHOUT THE NARRATIVE FOR |
| | THE CHANGES. FBC 107.2.1 |
| | |
| | 1) SHEET M-2.03: THE 48 INCH X 26 INCH FLAME-BAR DUCT |
| | AND SPF-1A HAS BEEN REMOVED IN THIS CYCLE OF REVIEWS, |
| | PLEASE EXPLAIN. FBC 107.2.1 |
| | |
| | 2) SHEET M-3.04: THE 100 PERCENT O/A ROOF TOP UNIT |
| | SCHEDULE IS MISSING FROM THIS LATEST SUBMITTAL. PLEASE |
| | EXPLAIN. FBC 107.2.1 |
| | |
| | 3) SHEET M-4.00: THE SMOKE CONTROL RISER DIAGRAM HAS |
| | BEEN OMITTED FROM THIS LATEST SUBMITTAL. PLEASE |
| | EXPLAIN. FBC 107.2.1 |
| | |
| | 4) SHEET M-402: EXPLAIN WHY THE SMOKE CONTROL DESIGN |
| | HAS CHANGED. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |