Plan Review Notes
Plan Review Notes For Permit 21091343
Permit Number 21091343
Review Stop M
Sequence Number 3
Notes
Date Text
2022-07-29 08:54:333RD REVIEW FMC
 PERMIT: 21091343
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 THERE SEEMS TO BE SEVERAL CHANGES THROUGHOUT THE
 REVISED DRAWINGS WITH NO MENTION OF THESE CHANGES IN A
 NARRATIVE. PLEASE SUBMIT A NARRATIVE FOR THESE CHANGES.
 BELOW IS A PARTIAL LIST OF COMMENTS TO THESE CHANGES. I
 CANNOT DO A COMPLETE REVIEW WITHOUT THE NARRATIVE FOR
 THE CHANGES. FBC 107.2.1
  
 1) SHEET M-2.03: THE 48 INCH X 26 INCH FLAME-BAR DUCT
 AND SPF-1A HAS BEEN REMOVED IN THIS CYCLE OF REVIEWS,
 PLEASE EXPLAIN. FBC 107.2.1
  
 2) SHEET M-3.04: THE 100 PERCENT O/A ROOF TOP UNIT
 SCHEDULE IS MISSING FROM THIS LATEST SUBMITTAL. PLEASE
 EXPLAIN. FBC 107.2.1
  
 3) SHEET M-4.00: THE SMOKE CONTROL RISER DIAGRAM HAS
 BEEN OMITTED FROM THIS LATEST SUBMITTAL. PLEASE
 EXPLAIN. FBC 107.2.1
  
 4) SHEET M-402: EXPLAIN WHY THE SMOKE CONTROL DESIGN
 HAS CHANGED. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  