| Plan Review Notes For Permit 21091343 |
| Permit Number |
21091343 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-07-28 17:16:19 | 3RD REVIEW FBC-2020 FUEL GAS | | | PERMIT- 21091343 | | | 7/28/22 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | 1) P105 & P402: BASED ON THE COMMENT RESPONSES FROM THE | | | ENGINEER THE MANUFACTURER?S SPECIFICATIONS FOR THE BBQ | | | GRILLS AND THE ENGINEERING FOR INSTALLATION ARE TO BE | | | DEFERRED SUBMITTALS, PLEASE PROVIDE A LIST OF DEFFERRED | | | SUBMITTALS ON THE PLANS THAT INCLUDES THE BBQ GRILLS, | | | THE GRILL ENGINEERING, AND THE REGULATORS- SEC. | | | 107.3.4.1 WPB. | | | | | | 2) P104 & P402: PLEASE PROVIDE NOTES ON THE PLAN TO | | | INDICATE THE POOL HEATER AND COMBUSTION AND VENTING | | | PLANS WILL BE UNDER A SEPARATE PERMIT- SECS. 107.2.1 7 | | | 107.3.4.2 WPB. | | | | | | 3) NEW COMMENT BASED ON RESUBMITTED P402: PLEASE SHOW | | | THE REQUIRED PIPE UNIONS LOCATED WITH 1 FT. OF EITHER | | | SIDE OF THE REGULATOR- SEC. 410.2(7) FBC FG. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|