| 2022-03-31 17:50:08 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21091343 |
| | 3/28/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. |
| | |
| | 1) FAILED. SHEET A0-000 & P101: PLEASE PROVIDE ON THE |
| | PLANS A LIST OF REQUIRED SEPARATE PERMITS INCLUDING: |
| | POOL, POOL HEATERS, GREASE INTERCEPTOR, IRRIGATION, |
| | GENERATOR, POTABLE WATER BACKFLOW PREVENTER, IRRIGATION |
| | SYSTEM BACKFLOW PREVENTER, POOL SERVICE BACKFLOW |
| | PREVENTER, FIRE LINE BACKFLOW PREVENTER, FIRE LINE, |
| | FIRE SPRINKLER, AND THE FIRE PUMP- SECTIONS 105.1 & |
| | 107.2.1 WPB. THE LIST WAS NOT PROVIDED. PLEASE NOTE |
| | THAT DUE TO A CHANGE IN PROCESS THE WPB BUILDING DEPT. |
| | REQUIRES PERMIT APPLICATIONS BE SUBMITTED FOR THE |
| | GREASE INTERCEPTOR AND THE BACKFLOW PREVENTERS- |
| | POTABLE, FIRE, IRRIGATION, AND POOL SERVICE BE |
| | SUBMITTED PRIOR TO ISSUANCE OF THE MAIN (PRIMARY) |
| | BUILDING PERMIT- SECS. 105 & 107 WPB. FAILURE TO SUBMIT |
| | APPLICATIONS WILL RESULT ON A HOLD BEING PLACED ON THE |
| | MAIN BUILDING PERMIT. |
| | YOU CAN SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF |
| | YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A |
| | COMPLETED PERMIT APPLICATION TO [email protected] |
| | . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD |
| | PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE |
| | DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE |
| | RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE |
| | SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED, |
| | NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS |
| | TO PASS. |
| | |
| | 2) FAILURE. P101- DEFERRED SUBMITTALS: MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION GUIDELINES FOR PLUMBING |
| | AND GAS EQUIPMENT, APPLIANCES, FIXTURES, CONTROLS, |
| | PIPING AND MATERIALS THAT ARE NOT SUBMITTED FOR REVIEW |
| | CAN BE DEFERRED SUBMITTALS IN ACCORDANCE WITH SECTION |
| | PROVIDE A LIST OF DEFERRED SUBMITTALS ON THE PLAN |
| | INCLUDING BUT NOT LIMITED TO THE DOMESTIC WATER PUMP, |
| | WATER HEATERS, KITCHEN AND BATH FIXTURES APPLIANCES, |
| | EXPANSION TANKS, FULL OPEN VALVES, MIXING VALVES, |
| | BACKFLOW PREVENTERS, RECIRCULATION PUMPS, WATER HAMMER |
| | ARRESTORS, TRAP PRIMERS, ROOF DRAINS, TERMINATION CAPS |
| | ETC.- SECTION 107.3.4.1 WPB. DEFERRED SUBMITTALS LIST |
| | NOT PROVIDED. FOR THE PURPOSES OF THIS SECTION, |
| | DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF |
| | THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION. DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED |
| | SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL |
| | REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL |
| | WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 3) FAILED. P101- SWIMMING POOL WASTE WATER: THE POOL |
| | SHALL BE UNDER SEPARATE PERMIT HOWEVER DISPOSAL OF POOL |
| | WASTE WATER MAY IMPACT THE MAIN STORM DRAIN PLANS. |
| | PLEASE REVIEW THE FOLLOWING GUIDELINES FOR DISPOSAL OF |
| | THE WASTE WATER- |
| | SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY |
| | SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES |
| | DEPARTMENT. |
| | SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| | STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| | ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| | BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER?S |
| | SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW |
| | AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| | WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| | A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH |
| | TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| | INLET). |
| | B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| | INLET TO DISCHARGE EFFLUENT. |
| | C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| | ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL |
| | OWNER?S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| | D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| | PROPERTY. |
| | E) FOR TECHNICAL QUESTIONS, DON'T HESITATE TO CONTACT |
| | O&M SUPERINTENDENT STEPHON HARRIS AT [email protected] OR |
| | 561-822-2168. |
| | F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, |
| | PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| | SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| | 822-2062 OR [email protected]. THE ARCHITECT?S RESPONSE |
| | NARRATIVE INDICATES A STORM PIPE HAS BEEN PROVIDED BUT |
| | NO ACKNOWLEDGEMENT THAT DECHLORINATION WILL BE |
| | PROVIDED. PLEASE CLARIFY THE LOCATION OF THE STORM PIPE |
| | ON THE PLAN- WHICH PLAN SHEET & DETAIL NO. |
| | |
| | 10) FAILED ITEMS B, C, D, & E. P101 GREASE INTERCEPTOR- |
| | SECS. 1003.1- 1003.3.8 FBC P. |
| | B) FAILED. PROVIDE AN INTERCEPTOR EQUIPMENT SCHEDULE- |
| | MAKE AND MODEL, GALLON SIZE. THERE IS A NOTE BY THE |
| | LOADING AREA SPECIFYING SCHIER GB-1000. PLEASE RELOCATE |
| | THE NOTE TO THE INTERCEPTOR LOCATION IF THIS THE MODEL |
| | TO BE INSTALLED. THE DETAIL ON P401 INDICATES MIAMI |
| | DERM FOG EFFICIENCY RATING HOWEVER THE PROJECT IS |
| | LOCATED IN WEST PALM BEACH. FOR WEST PALM BEACH |
| | REQUIREMENTS PLEASE CONTACT BRYAN SEALEY, CESCO, CESLO |
| | IPP/FOG COORDINATOR CITY OF WEST PALM BEACH PUBLIC |
| | UTILITIES DEPARTMENT IPP PROGRAM PHONE: (561) 822-2065 |
| | CELL: (561) 662-2381 EMAIL: [email protected]. |
| | C) FAILED. PROVIDE GREASE WASTE CALCULATIONS. NOT |
| | PROVIDED. |
| | D) FAILED. SHOW THE SAMPLING PORT AND VENTING |
| | LOCATIONS. NOT PROVIODED. |
| | E) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS. NOT PROVIDED, MAY REQUEST TO |
| | BE DEFERRED. |
| | D) FAILED. PLEASE NOTE INSTALLATION OF THE GREASE |
| | INTERCEPTOR SHALL BE UNDER SEPARATE PERMIT. THE |
| | REQUESTED SUBMITTAL MAY BE DEFERRED BY REQUEST- SECS. |
| | 105.1 & 107.3.4.1 WPB. LIST OF SEPARATE PERMITS NOT |
| | PROVIDED- SEE COMMENT #1 ABOVE. |
| | |
| | 11) FAILED ITEMS A, B ,C. P101- THERE ARE MANY MISSING |
| | DRAIN POINTS OF CONNECTION TO STORM OR SANITARY MAINS, |
| | OR CONTINUATIONS TO APPROVED DISPOSAL LOCATIONS. PLEASE |
| | PLACE NOTES ON THE PLAN TO INDICATE DISCHARGE OR |
| | CONNECTION LOCATIONS OF THE DP, CD, PD, AD, & O.F. |
| | PIPES- SEC. 107.2.1 WPB. |
| | A) FAILED. THE DP LINES SHALL TERMINATE OVER INDIRECT |
| | WASTE RECEPTORS OR TO THE EXTERIOR OF THE BUILDING- |
| | SEC. 504.7.2 FBC P. THE PLAN SHOWS THE LINES |
| | DISCHARGING ONTO THE TRASHROOM FLOOR. THE NEW SHEET |
| | P101B SH0WS THE ROOF DRAINAGE OVERFLOW LINES (OF) |
| | DISCHARGING ONTO THE GARAGE FLOORS WHICH IS NOT |
| | APPROVED PER SEC. 1101.2 FBC P. THE LINES SHALL |
| | DISCHARGE ABOVE GRADE A MINIMUM OF 12-INCHES FROM THE |
| | BUILDING IN A LOCATION THAT WOULD NORMALLY BE OBSERVED |
| | BY OCCUPANTS OR MAINTENANCE PERSONNEL- SEC. 1108.2 FBC |
| | P. |
| | B) FAILED. O.F. DRAINS SHOWN TERMINATING IN RETAIL 104, |
| | CORRIDOR 127, & BICYCLE STORAGE 100. PLEASE NOTE THAT |
| | IF THE DRAINS ARE TO CONNECT DIRECTLY TO THE GD PIPE, |
| | PLEASE CLARIFY HOW EMERGENCY OVERFLOW WILL BE OBSERVED |
| | MY BUILDING OCCUPANTS OR MAINTENANCE PERSONNEL- SEC. |
| | 1108.2 FBC P. THE NEW SHEET P101B SH0WS THE ROOF |
| | DRAINAGE OVERFLOW LINES (OF) DISCHARGING ONTO THE ROOM |
| | AND GARAGE FLOORS WHICH IS NOT APPROVED PER SEC. 1101.2 |
| | FBC P. THE LINES SHALL DISCHARGE ABOVE GRADE A MINIMUM |
| | OF 12-INCHES FROM THE BUILDING IN A LOCATION THAT WOULD |
| | NORMALLY BE OBSERVED BY OCCUPANTS OR MAINTENANCE |
| | PERSONNEL- SEC. 1108.2 FBC P. |
| | C) FAILED. REFER TO SECTION 1503.7 FBC B AND PROVIDE A |
| | DETAIL SHOWING THE O.F. DISCHARGE TERMINATION CAP AND |
| | MINIMUM 12-INCH DISCHARGE DISTANCE FROM THE STRUCTURE |
| | SIDEWALLS. DETAIL NOT PROVIDED & SEE NOTES ABOVE. |
| | |
| | 12) FAILED. P101 & P301: SANITARY DRAINS FROM UNITS |
| | 107, 110, & 11 TO MAIN SS NOT SHOWN- SEC. 107.2.1 WPB. |
| | NOT SHOWN ON P101A, P101B, P201. A) PLEASE CLEARLY |
| | IDENTIFY THE LOCATION AND SUIZE OF THE FD IN THE |
| | BOOSTER PUMP ROOM SHOWN ON P101A- SEC. 606.5 FBC P. |
| | |
| | 13) FAILED. P101 & P301: SHOW THE WATER SERVICE PIPING |
| | ENTRANCES TO UNITS 107, 110, & 111 ON P101- SEC. 602.1 |
| | FBC P. MAIN SHUTOFFS AND WATER METER LOCATIONS NOT |
| | SHOWN- SEC. |
| | |
| | 15) FAILED. P101, P102, P103, P104, P105, P106: PLEASE |
| | PROVIDE THE MAIN PLUMBING RISER DRAWINGS THAT CORRELATE |
| | WITH THE CIRCLE SYMBOLS AT THE BASE OF EACH VERTICAL |
| | STACK LOCATION INCLUDING THE (SS- SANITARY). (CD- |
| | CONDENSATE PIPES), (DP- DISCHARGE PIPES FROM WATER |
| | HEATERS), (RWL- RAIN WATER LEADERS), (PD-PLANTER |
| | DRAINS) - SEC. 107.3.5.1.3 WPB. PLEASE PROVIDE SUPPORT |
| | AND BRACING DETAILS FOR THE RISERS- SECS. 308.1- 308.9 |
| | FBC P. NEW SHEETS P305, P306, P308, P309: MINIMUM |
| | 4-INCH STACK VENTS ARE REQUIRED FOR THE 4-INCH WASHING |
| | MACHINE WASTE STACKS- SEC. 913.3 FBC P. A) |
| | |
| | 16) P101: PROVIDE TOTAL DFU CALCULATIONS AND THE MAIN |
| | SANITARY PIPE SIZES ALONG THE HORIZONTAL RUN FROM THE |
| | SOUTH END OF THE CORRIDOR TO THE EXIT ON THE NORTH END- |
| | SECS. 709 AND 710 FBC P. SHEETS P101A, P310, & P311: |
| | THE TOTAL DFU CALCULATIONS ON THE RISERS ARE DIFFERENT |
| | FROM THE FLOOR PLAN- WHICH IS CORRECT? |
| | |
| | 18) FAILED. P101: PROVIDE WSFU CALCULATIONS AND MAIN |
| | WATER RISER DRAWING- SECS. 603.1, E103 FBC P, AND SEC. |
| | 107.3.5.1.3 WPB. BASIS OF CALCULATIONS NOT PROVIDED. |
| | PLEASE VERIFY COMPLIANCE WITH SEC. 604.3 FBC P. |
| | |
| | 20) FAILED. P101, P102, P103, P104: PROVIDE A GARAGE |
| | DRAIN RISER DRAWING- SEC. 107.3.5.1.3 WPB. SHEET P316: |
| | PROVIDE DRAIN-PIPE SIZING CALCULATIONS- SEC. 107.2.1 |
| | WPB. A) PROVIDE A TYPICAL PIPE SLOPE FOR THE SYSTEM- |
| | TABLE 1106.2 FBC P. C) PROVIDE CLEANOUT LOCATIONS- SEC. |
| | 1101.8 FBC P. |
| | |
| | 22) FAILED. P104 & P107- ROOF DRAINAGE: SHEETS P101B, |
| | P312: A) PROVIDE A TYPICAL PIPE SLOPE FPR THE SYSTEM IN |
| | ACCORDANCE WITH TABLE 1106.2 FBC P. B) PROVIDE CLEANOUT |
| | LOCATIONS- SEC. 1101.8 FBC P. |
| | A) FAILED. PROVIDE PRIMARY AND OVERFLOW ROOF DRAIN |
| | RISER DRAWINGS- SECTION 107.3.5.1.3 WPB, AND SECS. |
| | 1106.1, 1106.1, & 1108.1 FBC P. SHEETS P101B & P312: |
| | ROOF DRAINAGE OVERFLOW LINES (OF) DISCHARGING ONTO THE |
| | ROOM AND GARAGE FLOORS NOT APPROVED PER SEC. 1101.2 FBC |
| | P. THE LINES SHALL DISCHARGE ABOVE GRADE A MINIMUM OF |
| | 12-INCHES FROM THE BUILDING IN A LOCATION THAT WOULD |
| | NORMALLY BE OBSERVED BY OCCUPANTS OR MAINTENANCE |
| | PERSONNEL- SEC. 1108.2 FBC P. |
| | |
| | 24) FAILED. P201A: PLEASE INDICATE HOW TEMPERED WATER |
| | WILL BE DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC |
| | P. COLD WATER IS ALLOWED TO BE DEIVERED FROM THE |
| | LAVATORIES HOWEVER THE REVISED DRAWING SHOWS ONLY COLD |
| | WATER DELIVERED FROM THE MOP SINK- HOT WATER IS |
| | REQUIRED PER SEC. 607.1 FBC P. A) WATER RISER FOR THE |
| | BATHROOMS NOT PROVIDED- SEC. 107.3.5.1.3 WPB. PLEASE |
| | NOTE THAT A MEANS OF LIMITING THE HOT WATER TEMPERATURE |
| | TO THE MOP SINK AND OTHER FIXTURES WILL BE REQUIRED PER |
| | SEC. 607.1.1 FBC P. |
| | |
| | 26) FAILED. P205: PLEASE INDICATE HOW TEMPERED WATER |
| | WILL BE DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC |
| | P. COLD WATER PASSED. A) NEW #3 & #4 SANITARY |
| | ISOMETRIC: THE DF FIXTURE DRAINS SHALL DISCHARGE INTO |
| | THE 4-INCH DRAIN DOWNSREAM OF THE WC FIXTURE DRAIN- |
| | SEC. 912.1 FBC P. B) TWO OF THE FOUR WATER CLOSETS THAT |
| | ARE FURTHEST DOWNSTREAM ARE WET VENTED. THE TWO |
| | FURTHEST UPSTREAM MUST BE INDIVUALLY OR COMMONLY |
| | VENTED- SECS. 910.1, 911.1, & 912.1 FBC P. C) THE FLOOR |
| | DRAIN FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE |
| | 4-INCH DRAIN DOWNSTREAM OF THE LAVATORY DRAIN |
| | CONNECTION- SEC. 912.1. |
| | |
| | 35) A0-003: PLEASE CORRECT ZONING REFERENCE INDICATING |
| | THE CITY OF HOLLYWOOD- SECTION 107.2.1 WPB. |
| | |
| | 36) FAILED. A0-003 DESIGN CRITERIA: INDICATE WHICH |
| | CODES AND/OR STANDARDS WERE USED IN THE DESIGN OF THE |
| | PUBLIC BATHROOMS AND PRIVATE KITCHEN AND BATHROOMS- |
| | SECTION 107.2.1 WPB. PLEASE NOTE THAT THE FBC-2020 7TH |
| | EDITION ACCESSIBILITY CODE IS THE CURRENT CODE USED IN |
| | THE CITY OF WPB FOR PLUMBING FIXTURE INSTALLATIONS IN |
| | PLACES OF PUBLIC ACCOMMODATION AND COMMERCIAL |
| | FACILITIES- SEC. 210.1 FBC ACC. THE FBC ACC SHALL BE |
| | USED FOR DESIGN OF THE 1ST AND 7TH FLOOR BATHROOMS. |
| | CONCERNING THE PRIVATE APARTMENT KITCHENS AND BATHS, |
| | THE DESIGN AND INSTALLATION OF PLUMBING FIXTURES IN THE |
| | PRIVATE KITCHENS AND BATHROOMS SHALL BE IN COMPLIANCE |
| | WITH THE FAIR HOUSING ACT DESIGN MANUAL OR THE FAIR |
| | HOUSING ACCESSIBILITY GUIDELINES. THE GUIDELINES WHICH |
| | ARE FOUND IN THE FBC ACC PROVIDE SAFE HARBOR FOR |
| | COMPLIANCE WITH THE ACCESSIBILITY REQUIREMENTS OF THE |
| | FAIR HOUSING ACT. THE DESIGNER OF RECORD SHALL CHOOSE |
| | WHICH DESIGN METHOD WILL BE USED AND PROVIDE DRAWINGS |
| | AND DETAILS INDICATING COMPLIANCE. THE FAIR HOUSING |
| | DESIGN COMPLIANCE NOT CALLED OUT IN THE CODES AND |
| | STANDARDS BLOCK ON THE PLAN. |
| | |
| | 37) FAILED B. A0-101 & A1-101- PLUMBING FIXTURE |
| | CALCULATIONS- SECTION AND TABLE 403.1 FBC P. |
| | B) FAILED. PROVIDE SEPARATE FIXTURE CALCULATION TABLES |
| | FOR RETAIL- 102, RETAIL- 104, OFFICE/RETAIL- 105. |
| | PLEASE REVISE THE PLANS TO SHOW THE LOCATIONS OF THE |
| | FIXTURES AND PLUMBING PIPING REQUIREMENTS. THE REQUIRED |
| | FIXTURES FOR THESE OCCUPANCIES CAN BE LISTED AS |
| | "FUTURE" IF NECESSARY. ACKNOWLEDGED THAT THE REQUIRED |
| | 1ST FLOOR PLUMBING FIXTURES ARE FUTURE AND TO BE |
| | DETERMINED, HOWEVER PLEASE PROVIDE CALCULATIONS FOR THE |
| | WOMENS AND MENS RESTROOMS 124 AND 126 IN ACCORDANCE |
| | WITH TABLE 403.1 FBC P. |
| | |
| | 38) FAILED. A0-106 & A1-106: THE OCCUPANT LOAD OF 456 |
| | SHOWN IN THE PLUMBING FIXTURE CALCULATION TABLE IS |
| | INCORRECT BASED ON THE LIFE SAFETY LOAD TABLE WHICH |
| | INDICATES 562- TABLE 403.1 FBC P. THE OCCUPANT LOADS |
| | SHOWN IN THE TABLE ON A0-106 HAVE BEEN OVERLAYED BY |
| | GENERAL NOTES ON THE PLAN AND NOT ENTIRELY LEGIBLE. |
| | |
| | 39) FAILED. A1-106: PLEASE PROVIDE THE CODE SECTION |
| | ASSOCIATED WITH THE SWIMMING POOL EXCEPTION AND SHOW |
| | THE 200-FOOT HORIZONTAL RADIUS TO VERIFY COMPLIANCE- |
| | SECTION 403.6 FBC P. IT APPEARS DESPITE THE EXCEPTION, |
| | THE PLANS INDICATE COMBINED POOLSIDE AND AMENITIES |
| | BATHROOMS. PLEASE CLARIFY IF FLOOR DRAINS WILL BE |
| | INSTALLED- NONE SHOWN ON P205- SEC. 403.6.3 FBC P. |
| | PLEASE LABEL THE 200 FT. RADIUS. PLEASE NOTE THE PLAN |
| | APPEARS TO SHOW THERE IS NOT AN ACCESSIBLE ROUTE TO THE |
| | POOL DECK- REQUIRMENT 2 FAIR HOUSING ACCESSIBILITY |
| | GUIDELINES FBC ACC, AND PG. 2.7 FAIR HOUSING DESIGN |
| | MANUAL. |
| | |
| | 40) FAILED C, D, G, H . A1-320- FBC- ACC MISSING AND |
| | INCORRECT COMPLIANCE DETAILS. PLEASE NOTE THAT NEW |
| | CONSTRUCTION ACCESSIBLE COMPARTMENTS SHALL BE DESIGNED |
| | IN ACCORDANCE WITH 604.8.1.6 & 604.8.1.7.: |
| | C) FAILED. SHOW TURNING SPACE DIAMETERS- 304.3. NOT |
| | PROVIDED. |
| | D) FAILED. THE DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACES FOR THE FIXTURES- 603.2.3. DETAIL 3 NOT IN |
| | COMPLIANCE. |
| | G) FAILED. SHOW THE HEIGHTS OF THE MIRRORS FROM THE |
| | FINISHED FLOORS NOT SHOWN TO THE REFLECTIVE SURFACES- |
| | SECTION 603.3 SHEET A2-210: NOTE INDICATING MEASUREMENT |
| | TO THE REFLECTIVE SURFACE NOT PROVIDED. |
| | H) FAILED. SHOW THE LOCATIONS, LENGTHS, AND MOUNTING |
| | HEIGHTS OF GRAB BARS FOR THE WATER CLOSETS IN |
| | COMPLIANCE WITH - SECTION 604.5 & 609.4, FIGURES |
| | 604.5.1 & 604.5.2. SHEET A6-301: REFER TO THE FIGURES |
| | LISTED- 604.5.1 & 604.5.2. INDICATE SIDE WALL GRAB BAR |
| | TO EXTEND MINIMUM 54-INCHES FROM THE WALL. INDICATE |
| | REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM AND |
| | EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 |
| | INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE |
| | OTHER SIDE. |
| | J) FAILED. CENTERLINES OF THE TOILET PAPER DISPENSERS |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. DETAIL ON A6-301 REFERENCED IN NARRATIVE |
| | IS INCORRECT. TP SHALL BE 7 INCHES MINIMUM AND 9 INCHES |
| | MAXIMUM MEASURED FROM THE FRONTS OF THE WATER CLOSETS. |
| | K) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES- |
| | SECTION 606.2. REFER TO FIGURES 306.2 7 306.3 FBC ACC |
| | AND MAKE CORRECTIONS. |
| | M) FAILED. CLEAR WIDTHS OF THE ACCESSIBLE COMPARTMENT |
| | DOORS- 404.2.3. NOT PROVIDED. |
| | |
| | 44 & 45) FAILED. SHEET A1-301, A1-303, A1-305- UNITS |
| | A1, A2, B2, & B7: THE REVISED BATH FLOOR PLANS SHOWING |
| | SHOWERS INSTEAD OF BATHTUBS ARE NOT IN COMPLIANCE WITH |
| | THE FAIR HOUSING DESIGN ACT MANUAL- PGS. 7.56- 7.59 A) |
| | REQUIRED PARALLEL APPROACH 30X48-INCH UNOBSTRUCTED |
| | CLEAR FLOOR SPACE NOT PROVIDED. B) MINIMUM 36-INCH WIDE |
| | SHOWER NOT PROVIDED. |
| | |
| | 49) FAILED. A1-305 UNITS C1: THE REVISED FLOOR PLAN |
| | SHOWS THE CONTROLS FOR THE SHOWER ON THE REAR WALL |
| | INSTEAD OF THE SIDE WALL ADJACENT TO THE CLEAR FLOOR |
| | SPACE- SEE PGS. 7.56- 7.59 FHDA MANUAL. |
| | |
| | 51) FAILED. A1-306 UNITS C2 & C3: THE REVISED FLOOR |
| | PLAN SHOWS THE CONTROLS FOR THE SHOWER ON THE REAR WALL |
| | INSTEAD OF THE SIDE WALL ADJACENT TO THE CLEAR FLOOR |
| | SPACE- SEE PGS. 7.56- 7.59 FHDA MANUAL. SHOW THE |
| | MINIMUM REQUIRED 30X48-INCH CLEAR FLOOR SPACE DIAGRAMS |
| | FOR PARALLEL APPROACHES TO THE BATHTUBS- FHA MANUAL |
| | 7.53- 7.55, AND FHA GUIDELINES FIGURE 8. PLEASE NOTE |
| | THAT COMPLIANCE IN C3 WILL NOT BE POSSIBLE UNLESS A |
| | WALL HUNG LAVATORY SINK WITH KNEE AND TOE CLEARANCES IS |
| | PROVIDED. A) UNIT C3: THE WATER CLOSET AND LAVATORY |
| | SPACING MEASURMENTS ARE NOT SHOWN- PG. 7.43 FHDA |
| | MANUAL. |
| | |
| | 53) FAILED. A1-307 UNIT C5, A1-308 UNIT C6: THE REVISED |
| | FLOOR PLANS SHOW THE CONTROLS FOR THE SHOWERS ON THE |
| | REAR WALL INSTEAD OF THE SIDE WALL ADJACENT TO THE |
| | CLEAR FLOOR SPACE- SEE PGS. 7.56- 7.59 FHDA MANUAL. |
| | |
| | 55) FAILED. A1-309 UNIT D-1: THE REVISED FLOOR PLANS |
| | SHOW THE CONTROLS FOR THE SHOWERS ON THE REAR WALL |
| | INSTEAD OF THE SIDE WALL ADJACENT TO THE CLEAR FLOOR |
| | SPACE- SEE PGS. 7.56- 7.59 FHDA MANUAL. |
| | |
| | NEW COMMENTS BASED ON NEW OR CORRECT PLAN SHEETS: |
| | |
| | 1) P313: PROVIDE PLANTER DRAIN-PIPE SIZING |
| | CALCULATIONS- SECS. 1105.2 & 1106.1 FBC P. A) PROVIDE A |
| | TYPICAL PIPE SLOPE FOR THE SYSTEM- TABLE 1106.2 FBC P. |
| | C) PROVIDE CLEANOUT LOCATIONS- SEC. 1101.8 FBC P. |
| | |
| | 2) P106, P315: SHOW THE LOCATION OF THE 80-GALLON |
| | HYDROPNEUMATIC TANK ON THE ROOF- SEC. 107.2.1 WPB. A) |
| | PROVIDE DETAILS SHOWING TANK ANCHORING, WATER PIPING |
| | DETAILS, OVERFLOW, RELIEF AND DRAIN PIPING DETAILS, AND |
| | SUBMIT MANUFACTURER?S SPECIFICATIONS- SECS. 606.5- |
| | 606.5.7 FBC P. |
| | |
| | 3) A1-310: FAIR HOUSING DIAGRAMS AND DIMENSIONS NOT |
| | SHOWN ON THE FLOOR PLAN- SEC. 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |