Plan Review Notes
Plan Review Notes For Permit 21091343
Permit Number 21091343
Review Stop P
Sequence Number 2
Notes
Date Text
2022-03-31 17:50:082ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21091343
 3/28/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 1) FAILED. SHEET A0-000 & P101: PLEASE PROVIDE ON THE
 PLANS A LIST OF REQUIRED SEPARATE PERMITS INCLUDING:
 POOL, POOL HEATERS, GREASE INTERCEPTOR, IRRIGATION,
 GENERATOR, POTABLE WATER BACKFLOW PREVENTER, IRRIGATION
 SYSTEM BACKFLOW PREVENTER, POOL SERVICE BACKFLOW
 PREVENTER, FIRE LINE BACKFLOW PREVENTER, FIRE LINE,
 FIRE SPRINKLER, AND THE FIRE PUMP- SECTIONS 105.1 &
 107.2.1 WPB. THE LIST WAS NOT PROVIDED. PLEASE NOTE
 THAT DUE TO A CHANGE IN PROCESS THE WPB BUILDING DEPT.
 REQUIRES PERMIT APPLICATIONS BE SUBMITTED FOR THE
 GREASE INTERCEPTOR AND THE BACKFLOW PREVENTERS-
 POTABLE, FIRE, IRRIGATION, AND POOL SERVICE BE
 SUBMITTED PRIOR TO ISSUANCE OF THE MAIN (PRIMARY)
 BUILDING PERMIT- SECS. 105 & 107 WPB. FAILURE TO SUBMIT
 APPLICATIONS WILL RESULT ON A HOLD BEING PLACED ON THE
 MAIN BUILDING PERMIT.
 YOU CAN SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF
 YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO [email protected]
 . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD
 PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE
 DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE
 RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE
 SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED,
 NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS
 TO PASS.
  
 2) FAILURE. P101- DEFERRED SUBMITTALS: MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION GUIDELINES FOR PLUMBING
 AND GAS EQUIPMENT, APPLIANCES, FIXTURES, CONTROLS,
 PIPING AND MATERIALS THAT ARE NOT SUBMITTED FOR REVIEW
 CAN BE DEFERRED SUBMITTALS IN ACCORDANCE WITH SECTION
 PROVIDE A LIST OF DEFERRED SUBMITTALS ON THE PLAN
 INCLUDING BUT NOT LIMITED TO THE DOMESTIC WATER PUMP,
 WATER HEATERS, KITCHEN AND BATH FIXTURES APPLIANCES,
 EXPANSION TANKS, FULL OPEN VALVES, MIXING VALVES,
 BACKFLOW PREVENTERS, RECIRCULATION PUMPS, WATER HAMMER
 ARRESTORS, TRAP PRIMERS, ROOF DRAINS, TERMINATION CAPS
 ETC.- SECTION 107.3.4.1 WPB. DEFERRED SUBMITTALS LIST
 NOT PROVIDED. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION. DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
 3) FAILED. P101- SWIMMING POOL WASTE WATER: THE POOL
 SHALL BE UNDER SEPARATE PERMIT HOWEVER DISPOSAL OF POOL
 WASTE WATER MAY IMPACT THE MAIN STORM DRAIN PLANS.
 PLEASE REVIEW THE FOLLOWING GUIDELINES FOR DISPOSAL OF
 THE WASTE WATER-
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER?S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL
 OWNER?S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 E) FOR TECHNICAL QUESTIONS, DON'T HESITATE TO CONTACT
 O&M SUPERINTENDENT STEPHON HARRIS AT [email protected] OR
 561-822-2168.
 F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS,
 PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected]. THE ARCHITECT?S RESPONSE
 NARRATIVE INDICATES A STORM PIPE HAS BEEN PROVIDED BUT
 NO ACKNOWLEDGEMENT THAT DECHLORINATION WILL BE
 PROVIDED. PLEASE CLARIFY THE LOCATION OF THE STORM PIPE
 ON THE PLAN- WHICH PLAN SHEET & DETAIL NO.
  
 10) FAILED ITEMS B, C, D, & E. P101 GREASE INTERCEPTOR-
 SECS. 1003.1- 1003.3.8 FBC P.
 B) FAILED. PROVIDE AN INTERCEPTOR EQUIPMENT SCHEDULE-
 MAKE AND MODEL, GALLON SIZE. THERE IS A NOTE BY THE
 LOADING AREA SPECIFYING SCHIER GB-1000. PLEASE RELOCATE
 THE NOTE TO THE INTERCEPTOR LOCATION IF THIS THE MODEL
 TO BE INSTALLED. THE DETAIL ON P401 INDICATES MIAMI
 DERM FOG EFFICIENCY RATING HOWEVER THE PROJECT IS
 LOCATED IN WEST PALM BEACH. FOR WEST PALM BEACH
 REQUIREMENTS PLEASE CONTACT BRYAN SEALEY, CESCO, CESLO
 IPP/FOG COORDINATOR CITY OF WEST PALM BEACH PUBLIC
 UTILITIES DEPARTMENT IPP PROGRAM PHONE: (561) 822-2065
 CELL: (561) 662-2381 EMAIL: [email protected].
 C) FAILED. PROVIDE GREASE WASTE CALCULATIONS. NOT
 PROVIDED.
 D) FAILED. SHOW THE SAMPLING PORT AND VENTING
 LOCATIONS. NOT PROVIODED.
 E) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS. NOT PROVIDED, MAY REQUEST TO
 BE DEFERRED.
 D) FAILED. PLEASE NOTE INSTALLATION OF THE GREASE
 INTERCEPTOR SHALL BE UNDER SEPARATE PERMIT. THE
 REQUESTED SUBMITTAL MAY BE DEFERRED BY REQUEST- SECS.
 105.1 & 107.3.4.1 WPB. LIST OF SEPARATE PERMITS NOT
 PROVIDED- SEE COMMENT #1 ABOVE.
  
 11) FAILED ITEMS A, B ,C. P101- THERE ARE MANY MISSING
 DRAIN POINTS OF CONNECTION TO STORM OR SANITARY MAINS,
 OR CONTINUATIONS TO APPROVED DISPOSAL LOCATIONS. PLEASE
 PLACE NOTES ON THE PLAN TO INDICATE DISCHARGE OR
 CONNECTION LOCATIONS OF THE DP, CD, PD, AD, & O.F.
 PIPES- SEC. 107.2.1 WPB.
 A) FAILED. THE DP LINES SHALL TERMINATE OVER INDIRECT
 WASTE RECEPTORS OR TO THE EXTERIOR OF THE BUILDING-
 SEC. 504.7.2 FBC P. THE PLAN SHOWS THE LINES
 DISCHARGING ONTO THE TRASHROOM FLOOR. THE NEW SHEET
 P101B SH0WS THE ROOF DRAINAGE OVERFLOW LINES (OF)
 DISCHARGING ONTO THE GARAGE FLOORS WHICH IS NOT
 APPROVED PER SEC. 1101.2 FBC P. THE LINES SHALL
 DISCHARGE ABOVE GRADE A MINIMUM OF 12-INCHES FROM THE
 BUILDING IN A LOCATION THAT WOULD NORMALLY BE OBSERVED
 BY OCCUPANTS OR MAINTENANCE PERSONNEL- SEC. 1108.2 FBC
 P.
 B) FAILED. O.F. DRAINS SHOWN TERMINATING IN RETAIL 104,
 CORRIDOR 127, & BICYCLE STORAGE 100. PLEASE NOTE THAT
 IF THE DRAINS ARE TO CONNECT DIRECTLY TO THE GD PIPE,
 PLEASE CLARIFY HOW EMERGENCY OVERFLOW WILL BE OBSERVED
 MY BUILDING OCCUPANTS OR MAINTENANCE PERSONNEL- SEC.
 1108.2 FBC P. THE NEW SHEET P101B SH0WS THE ROOF
 DRAINAGE OVERFLOW LINES (OF) DISCHARGING ONTO THE ROOM
 AND GARAGE FLOORS WHICH IS NOT APPROVED PER SEC. 1101.2
 FBC P. THE LINES SHALL DISCHARGE ABOVE GRADE A MINIMUM
 OF 12-INCHES FROM THE BUILDING IN A LOCATION THAT WOULD
 NORMALLY BE OBSERVED BY OCCUPANTS OR MAINTENANCE
 PERSONNEL- SEC. 1108.2 FBC P.
 C) FAILED. REFER TO SECTION 1503.7 FBC B AND PROVIDE A
 DETAIL SHOWING THE O.F. DISCHARGE TERMINATION CAP AND
 MINIMUM 12-INCH DISCHARGE DISTANCE FROM THE STRUCTURE
 SIDEWALLS. DETAIL NOT PROVIDED & SEE NOTES ABOVE.
  
 12) FAILED. P101 & P301: SANITARY DRAINS FROM UNITS
 107, 110, & 11 TO MAIN SS NOT SHOWN- SEC. 107.2.1 WPB.
 NOT SHOWN ON P101A, P101B, P201. A) PLEASE CLEARLY
 IDENTIFY THE LOCATION AND SUIZE OF THE FD IN THE
 BOOSTER PUMP ROOM SHOWN ON P101A- SEC. 606.5 FBC P.
  
 13) FAILED. P101 & P301: SHOW THE WATER SERVICE PIPING
 ENTRANCES TO UNITS 107, 110, & 111 ON P101- SEC. 602.1
 FBC P. MAIN SHUTOFFS AND WATER METER LOCATIONS NOT
 SHOWN- SEC.
  
 15) FAILED. P101, P102, P103, P104, P105, P106: PLEASE
 PROVIDE THE MAIN PLUMBING RISER DRAWINGS THAT CORRELATE
 WITH THE CIRCLE SYMBOLS AT THE BASE OF EACH VERTICAL
 STACK LOCATION INCLUDING THE (SS- SANITARY). (CD-
 CONDENSATE PIPES), (DP- DISCHARGE PIPES FROM WATER
 HEATERS), (RWL- RAIN WATER LEADERS), (PD-PLANTER
 DRAINS) - SEC. 107.3.5.1.3 WPB. PLEASE PROVIDE SUPPORT
 AND BRACING DETAILS FOR THE RISERS- SECS. 308.1- 308.9
 FBC P. NEW SHEETS P305, P306, P308, P309: MINIMUM
 4-INCH STACK VENTS ARE REQUIRED FOR THE 4-INCH WASHING
 MACHINE WASTE STACKS- SEC. 913.3 FBC P. A)
  
 16) P101: PROVIDE TOTAL DFU CALCULATIONS AND THE MAIN
 SANITARY PIPE SIZES ALONG THE HORIZONTAL RUN FROM THE
 SOUTH END OF THE CORRIDOR TO THE EXIT ON THE NORTH END-
 SECS. 709 AND 710 FBC P. SHEETS P101A, P310, & P311:
 THE TOTAL DFU CALCULATIONS ON THE RISERS ARE DIFFERENT
 FROM THE FLOOR PLAN- WHICH IS CORRECT?
  
 18) FAILED. P101: PROVIDE WSFU CALCULATIONS AND MAIN
 WATER RISER DRAWING- SECS. 603.1, E103 FBC P, AND SEC.
 107.3.5.1.3 WPB. BASIS OF CALCULATIONS NOT PROVIDED.
 PLEASE VERIFY COMPLIANCE WITH SEC. 604.3 FBC P.
  
 20) FAILED. P101, P102, P103, P104: PROVIDE A GARAGE
 DRAIN RISER DRAWING- SEC. 107.3.5.1.3 WPB. SHEET P316:
 PROVIDE DRAIN-PIPE SIZING CALCULATIONS- SEC. 107.2.1
 WPB. A) PROVIDE A TYPICAL PIPE SLOPE FOR THE SYSTEM-
 TABLE 1106.2 FBC P. C) PROVIDE CLEANOUT LOCATIONS- SEC.
 1101.8 FBC P.
  
 22) FAILED. P104 & P107- ROOF DRAINAGE: SHEETS P101B,
 P312: A) PROVIDE A TYPICAL PIPE SLOPE FPR THE SYSTEM IN
 ACCORDANCE WITH TABLE 1106.2 FBC P. B) PROVIDE CLEANOUT
 LOCATIONS- SEC. 1101.8 FBC P.
 A) FAILED. PROVIDE PRIMARY AND OVERFLOW ROOF DRAIN
 RISER DRAWINGS- SECTION 107.3.5.1.3 WPB, AND SECS.
 1106.1, 1106.1, & 1108.1 FBC P. SHEETS P101B & P312:
 ROOF DRAINAGE OVERFLOW LINES (OF) DISCHARGING ONTO THE
 ROOM AND GARAGE FLOORS NOT APPROVED PER SEC. 1101.2 FBC
 P. THE LINES SHALL DISCHARGE ABOVE GRADE A MINIMUM OF
 12-INCHES FROM THE BUILDING IN A LOCATION THAT WOULD
 NORMALLY BE OBSERVED BY OCCUPANTS OR MAINTENANCE
 PERSONNEL- SEC. 1108.2 FBC P.
  
 24) FAILED. P201A: PLEASE INDICATE HOW TEMPERED WATER
 WILL BE DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC
 P. COLD WATER IS ALLOWED TO BE DEIVERED FROM THE
 LAVATORIES HOWEVER THE REVISED DRAWING SHOWS ONLY COLD
 WATER DELIVERED FROM THE MOP SINK- HOT WATER IS
 REQUIRED PER SEC. 607.1 FBC P. A) WATER RISER FOR THE
 BATHROOMS NOT PROVIDED- SEC. 107.3.5.1.3 WPB. PLEASE
 NOTE THAT A MEANS OF LIMITING THE HOT WATER TEMPERATURE
 TO THE MOP SINK AND OTHER FIXTURES WILL BE REQUIRED PER
 SEC. 607.1.1 FBC P.
  
 26) FAILED. P205: PLEASE INDICATE HOW TEMPERED WATER
 WILL BE DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC
 P. COLD WATER PASSED. A) NEW #3 & #4 SANITARY
 ISOMETRIC: THE DF FIXTURE DRAINS SHALL DISCHARGE INTO
 THE 4-INCH DRAIN DOWNSREAM OF THE WC FIXTURE DRAIN-
 SEC. 912.1 FBC P. B) TWO OF THE FOUR WATER CLOSETS THAT
 ARE FURTHEST DOWNSTREAM ARE WET VENTED. THE TWO
 FURTHEST UPSTREAM MUST BE INDIVUALLY OR COMMONLY
 VENTED- SECS. 910.1, 911.1, & 912.1 FBC P. C) THE FLOOR
 DRAIN FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE
 4-INCH DRAIN DOWNSTREAM OF THE LAVATORY DRAIN
 CONNECTION- SEC. 912.1.
  
 35) A0-003: PLEASE CORRECT ZONING REFERENCE INDICATING
 THE CITY OF HOLLYWOOD- SECTION 107.2.1 WPB.
  
 36) FAILED. A0-003 DESIGN CRITERIA: INDICATE WHICH
 CODES AND/OR STANDARDS WERE USED IN THE DESIGN OF THE
 PUBLIC BATHROOMS AND PRIVATE KITCHEN AND BATHROOMS-
 SECTION 107.2.1 WPB. PLEASE NOTE THAT THE FBC-2020 7TH
 EDITION ACCESSIBILITY CODE IS THE CURRENT CODE USED IN
 THE CITY OF WPB FOR PLUMBING FIXTURE INSTALLATIONS IN
 PLACES OF PUBLIC ACCOMMODATION AND COMMERCIAL
 FACILITIES- SEC. 210.1 FBC ACC. THE FBC ACC SHALL BE
 USED FOR DESIGN OF THE 1ST AND 7TH FLOOR BATHROOMS.
 CONCERNING THE PRIVATE APARTMENT KITCHENS AND BATHS,
 THE DESIGN AND INSTALLATION OF PLUMBING FIXTURES IN THE
 PRIVATE KITCHENS AND BATHROOMS SHALL BE IN COMPLIANCE
 WITH THE FAIR HOUSING ACT DESIGN MANUAL OR THE FAIR
 HOUSING ACCESSIBILITY GUIDELINES. THE GUIDELINES WHICH
 ARE FOUND IN THE FBC ACC PROVIDE SAFE HARBOR FOR
 COMPLIANCE WITH THE ACCESSIBILITY REQUIREMENTS OF THE
 FAIR HOUSING ACT. THE DESIGNER OF RECORD SHALL CHOOSE
 WHICH DESIGN METHOD WILL BE USED AND PROVIDE DRAWINGS
 AND DETAILS INDICATING COMPLIANCE. THE FAIR HOUSING
 DESIGN COMPLIANCE NOT CALLED OUT IN THE CODES AND
 STANDARDS BLOCK ON THE PLAN.
  
 37) FAILED B. A0-101 & A1-101- PLUMBING FIXTURE
 CALCULATIONS- SECTION AND TABLE 403.1 FBC P.
 B) FAILED. PROVIDE SEPARATE FIXTURE CALCULATION TABLES
 FOR RETAIL- 102, RETAIL- 104, OFFICE/RETAIL- 105.
 PLEASE REVISE THE PLANS TO SHOW THE LOCATIONS OF THE
 FIXTURES AND PLUMBING PIPING REQUIREMENTS. THE REQUIRED
 FIXTURES FOR THESE OCCUPANCIES CAN BE LISTED AS
 "FUTURE" IF NECESSARY. ACKNOWLEDGED THAT THE REQUIRED
 1ST FLOOR PLUMBING FIXTURES ARE FUTURE AND TO BE
 DETERMINED, HOWEVER PLEASE PROVIDE CALCULATIONS FOR THE
 WOMENS AND MENS RESTROOMS 124 AND 126 IN ACCORDANCE
 WITH TABLE 403.1 FBC P.
  
 38) FAILED. A0-106 & A1-106: THE OCCUPANT LOAD OF 456
 SHOWN IN THE PLUMBING FIXTURE CALCULATION TABLE IS
 INCORRECT BASED ON THE LIFE SAFETY LOAD TABLE WHICH
 INDICATES 562- TABLE 403.1 FBC P. THE OCCUPANT LOADS
 SHOWN IN THE TABLE ON A0-106 HAVE BEEN OVERLAYED BY
 GENERAL NOTES ON THE PLAN AND NOT ENTIRELY LEGIBLE.
  
 39) FAILED. A1-106: PLEASE PROVIDE THE CODE SECTION
 ASSOCIATED WITH THE SWIMMING POOL EXCEPTION AND SHOW
 THE 200-FOOT HORIZONTAL RADIUS TO VERIFY COMPLIANCE-
 SECTION 403.6 FBC P. IT APPEARS DESPITE THE EXCEPTION,
 THE PLANS INDICATE COMBINED POOLSIDE AND AMENITIES
 BATHROOMS. PLEASE CLARIFY IF FLOOR DRAINS WILL BE
 INSTALLED- NONE SHOWN ON P205- SEC. 403.6.3 FBC P.
 PLEASE LABEL THE 200 FT. RADIUS. PLEASE NOTE THE PLAN
 APPEARS TO SHOW THERE IS NOT AN ACCESSIBLE ROUTE TO THE
 POOL DECK- REQUIRMENT 2 FAIR HOUSING ACCESSIBILITY
 GUIDELINES FBC ACC, AND PG. 2.7 FAIR HOUSING DESIGN
 MANUAL.
  
 40) FAILED C, D, G, H . A1-320- FBC- ACC MISSING AND
 INCORRECT COMPLIANCE DETAILS. PLEASE NOTE THAT NEW
 CONSTRUCTION ACCESSIBLE COMPARTMENTS SHALL BE DESIGNED
 IN ACCORDANCE WITH 604.8.1.6 & 604.8.1.7.:
 C) FAILED. SHOW TURNING SPACE DIAMETERS- 304.3. NOT
 PROVIDED.
 D) FAILED. THE DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACES FOR THE FIXTURES- 603.2.3. DETAIL 3 NOT IN
 COMPLIANCE.
 G) FAILED. SHOW THE HEIGHTS OF THE MIRRORS FROM THE
 FINISHED FLOORS NOT SHOWN TO THE REFLECTIVE SURFACES-
 SECTION 603.3 SHEET A2-210: NOTE INDICATING MEASUREMENT
 TO THE REFLECTIVE SURFACE NOT PROVIDED.
 H) FAILED. SHOW THE LOCATIONS, LENGTHS, AND MOUNTING
 HEIGHTS OF GRAB BARS FOR THE WATER CLOSETS IN
 COMPLIANCE WITH - SECTION 604.5 & 609.4, FIGURES
 604.5.1 & 604.5.2. SHEET A6-301: REFER TO THE FIGURES
 LISTED- 604.5.1 & 604.5.2. INDICATE SIDE WALL GRAB BAR
 TO EXTEND MINIMUM 54-INCHES FROM THE WALL. INDICATE
 REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM AND
 EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
 J) FAILED. CENTERLINES OF THE TOILET PAPER DISPENSERS
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7. DETAIL ON A6-301 REFERENCED IN NARRATIVE
 IS INCORRECT. TP SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM MEASURED FROM THE FRONTS OF THE WATER CLOSETS.
 K) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 SECTION 606.2. REFER TO FIGURES 306.2 7 306.3 FBC ACC
 AND MAKE CORRECTIONS.
 M) FAILED. CLEAR WIDTHS OF THE ACCESSIBLE COMPARTMENT
 DOORS- 404.2.3. NOT PROVIDED.
  
 44 & 45) FAILED. SHEET A1-301, A1-303, A1-305- UNITS
 A1, A2, B2, & B7: THE REVISED BATH FLOOR PLANS SHOWING
 SHOWERS INSTEAD OF BATHTUBS ARE NOT IN COMPLIANCE WITH
 THE FAIR HOUSING DESIGN ACT MANUAL- PGS. 7.56- 7.59 A)
 REQUIRED PARALLEL APPROACH 30X48-INCH UNOBSTRUCTED
 CLEAR FLOOR SPACE NOT PROVIDED. B) MINIMUM 36-INCH WIDE
 SHOWER NOT PROVIDED.
  
 49) FAILED. A1-305 UNITS C1: THE REVISED FLOOR PLAN
 SHOWS THE CONTROLS FOR THE SHOWER ON THE REAR WALL
 INSTEAD OF THE SIDE WALL ADJACENT TO THE CLEAR FLOOR
 SPACE- SEE PGS. 7.56- 7.59 FHDA MANUAL.
  
 51) FAILED. A1-306 UNITS C2 & C3: THE REVISED FLOOR
 PLAN SHOWS THE CONTROLS FOR THE SHOWER ON THE REAR WALL
 INSTEAD OF THE SIDE WALL ADJACENT TO THE CLEAR FLOOR
 SPACE- SEE PGS. 7.56- 7.59 FHDA MANUAL. SHOW THE
 MINIMUM REQUIRED 30X48-INCH CLEAR FLOOR SPACE DIAGRAMS
 FOR PARALLEL APPROACHES TO THE BATHTUBS- FHA MANUAL
 7.53- 7.55, AND FHA GUIDELINES FIGURE 8. PLEASE NOTE
 THAT COMPLIANCE IN C3 WILL NOT BE POSSIBLE UNLESS A
 WALL HUNG LAVATORY SINK WITH KNEE AND TOE CLEARANCES IS
 PROVIDED. A) UNIT C3: THE WATER CLOSET AND LAVATORY
 SPACING MEASURMENTS ARE NOT SHOWN- PG. 7.43 FHDA
 MANUAL.
  
 53) FAILED. A1-307 UNIT C5, A1-308 UNIT C6: THE REVISED
 FLOOR PLANS SHOW THE CONTROLS FOR THE SHOWERS ON THE
 REAR WALL INSTEAD OF THE SIDE WALL ADJACENT TO THE
 CLEAR FLOOR SPACE- SEE PGS. 7.56- 7.59 FHDA MANUAL.
  
 55) FAILED. A1-309 UNIT D-1: THE REVISED FLOOR PLANS
 SHOW THE CONTROLS FOR THE SHOWERS ON THE REAR WALL
 INSTEAD OF THE SIDE WALL ADJACENT TO THE CLEAR FLOOR
 SPACE- SEE PGS. 7.56- 7.59 FHDA MANUAL.
  
 NEW COMMENTS BASED ON NEW OR CORRECT PLAN SHEETS:
  
 1) P313: PROVIDE PLANTER DRAIN-PIPE SIZING
 CALCULATIONS- SECS. 1105.2 & 1106.1 FBC P. A) PROVIDE A
 TYPICAL PIPE SLOPE FOR THE SYSTEM- TABLE 1106.2 FBC P.
 C) PROVIDE CLEANOUT LOCATIONS- SEC. 1101.8 FBC P.
  
 2) P106, P315: SHOW THE LOCATION OF THE 80-GALLON
 HYDROPNEUMATIC TANK ON THE ROOF- SEC. 107.2.1 WPB. A)
 PROVIDE DETAILS SHOWING TANK ANCHORING, WATER PIPING
 DETAILS, OVERFLOW, RELIEF AND DRAIN PIPING DETAILS, AND
 SUBMIT MANUFACTURER?S SPECIFICATIONS- SECS. 606.5-
 606.5.7 FBC P.
  
 3) A1-310: FAIR HOUSING DIAGRAMS AND DIMENSIONS NOT
 SHOWN ON THE FLOOR PLAN- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected].
  
  
  
  