Plan Review Notes
Plan Review Notes For Permit 21091343
Permit Number 21091343
Review Stop M
Sequence Number 2
Notes
Date Text
2022-03-31 15:44:522ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21091343
  
 CODES IN EFFECT:
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.01: THE EQUIPMENT LABELS HAVE BEEN REMOVED
 ON THIS CYCLE, PLEASE PUT THEM BACK ON THE DRAWING AND
 CHECK THE OTHER SHEETS. FBC 107.2.1
  
 2) THE NO2 AND CO SENSORS HAVE BEEN REMOVED FROM THIS
 CYCLE, PLEASE PUT THEM BACK ON THE DRAWING. PROVIDE THE
 CALCULATIONS FOR THE FIRST LEVEL PARKING GARAGE
 VENTILATION SYSTEM. FMC 404.1
  
 3) SHEET M1.01: IT APPEARS THAT THE OUTDOOR AIR DUCT
 THAT IS NOW SHOWN FOR AHU-1L-6 IS CONNECTING TO THE
 SUPPLY SIDE OF THE UNIT. AND THERE IS NOW A DAMPER
 SHOWN ON THE RETURN SIDE OF THE UNIT. PLEASE PROVIDE A
 DETAIL DRAWING EXPLAINING WHY THE DUCT IS CONNECTING TO
 THE SUPPLY AND THE NEED FOR THE DAMPER IN THE RETURN AT
 THE AHU-1L-6. FBC 107.2.1
  
 4) SHEET M1.01: PLEASE IDENTIFY THE INTAKE LOUVER FOR
 THE GENERATOR ROOM. FBC 107.2.1
  
 5) PLEASE SHOW THE REQUIRED PROTECTION FOR THE 3-HOUR
 RATED WALLS WHERE THE ELEC. ROOM AND GENERATOR ROOM
 EXHAUST PENETRATES THE WALLS. FMC 607
  
 6) PLEASE CLEARLY IDENTIFY THE FIRE DAMPERS AT THE
 REQUIRED LOCATIONS. FBC 107.2.1
  
 7) PROVIDE DRYER DUCT LENGTHS FOR EACH UNIT AND SHOWING
 EACH WILL MEET FMC 504.8.4.1 35 FOOT MAX. LENGTH OR
 PROVIDE THE MANUFACTURER?S INSTRUCTIONS FOR THE
 SPECIFIC DRYER USED IN EACH UNIT. FMC 504.8.4.2
  
 8) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS
 BUILDING ACCORDING TO FMC TABLE 403.3.1.1 AND NOT THE
 ARCHITECTURAL EGRESS OCCUPANT LOAD. PLEASE IDENTIFY
 EACH SPACE ACCORDING TO THE OCCUPANT CLASSIFICATION
 FROM TABLE 403.3.1.1 SO THIS REVIEWER CAN CALCULATE THE
 SPACES AS YOU HAVE. FMC 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  