| 2022-03-31 15:44:52 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21091343 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1.01: THE EQUIPMENT LABELS HAVE BEEN REMOVED |
| | ON THIS CYCLE, PLEASE PUT THEM BACK ON THE DRAWING AND |
| | CHECK THE OTHER SHEETS. FBC 107.2.1 |
| | |
| | 2) THE NO2 AND CO SENSORS HAVE BEEN REMOVED FROM THIS |
| | CYCLE, PLEASE PUT THEM BACK ON THE DRAWING. PROVIDE THE |
| | CALCULATIONS FOR THE FIRST LEVEL PARKING GARAGE |
| | VENTILATION SYSTEM. FMC 404.1 |
| | |
| | 3) SHEET M1.01: IT APPEARS THAT THE OUTDOOR AIR DUCT |
| | THAT IS NOW SHOWN FOR AHU-1L-6 IS CONNECTING TO THE |
| | SUPPLY SIDE OF THE UNIT. AND THERE IS NOW A DAMPER |
| | SHOWN ON THE RETURN SIDE OF THE UNIT. PLEASE PROVIDE A |
| | DETAIL DRAWING EXPLAINING WHY THE DUCT IS CONNECTING TO |
| | THE SUPPLY AND THE NEED FOR THE DAMPER IN THE RETURN AT |
| | THE AHU-1L-6. FBC 107.2.1 |
| | |
| | 4) SHEET M1.01: PLEASE IDENTIFY THE INTAKE LOUVER FOR |
| | THE GENERATOR ROOM. FBC 107.2.1 |
| | |
| | 5) PLEASE SHOW THE REQUIRED PROTECTION FOR THE 3-HOUR |
| | RATED WALLS WHERE THE ELEC. ROOM AND GENERATOR ROOM |
| | EXHAUST PENETRATES THE WALLS. FMC 607 |
| | |
| | 6) PLEASE CLEARLY IDENTIFY THE FIRE DAMPERS AT THE |
| | REQUIRED LOCATIONS. FBC 107.2.1 |
| | |
| | 7) PROVIDE DRYER DUCT LENGTHS FOR EACH UNIT AND SHOWING |
| | EACH WILL MEET FMC 504.8.4.1 35 FOOT MAX. LENGTH OR |
| | PROVIDE THE MANUFACTURER?S INSTRUCTIONS FOR THE |
| | SPECIFIC DRYER USED IN EACH UNIT. FMC 504.8.4.2 |
| | |
| | 8) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS |
| | BUILDING ACCORDING TO FMC TABLE 403.3.1.1 AND NOT THE |
| | ARCHITECTURAL EGRESS OCCUPANT LOAD. PLEASE IDENTIFY |
| | EACH SPACE ACCORDING TO THE OCCUPANT CLASSIFICATION |
| | FROM TABLE 403.3.1.1 SO THIS REVIEWER CAN CALCULATE THE |
| | SPACES AS YOU HAVE. FMC 403.3.1.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |