Plan Review Notes
Plan Review Notes For Permit 21091343
Permit Number 21091343
Review Stop G
Sequence Number 2
Notes
Date Text
2022-04-05 11:18:052ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21091343
 4/5/22
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 2) FAILED. P102- P104: SHOW GAS PIPING HORIZONTAL RUNS
 AND RISER LOCATIONS- - SEC. 107.2.1 WPB, AND SECS.
 401.1 & 402.1 FBC FG. PIPE SIZES SHOWN AT THE NEW RISER
 ON P402 DO NOT MATCH SIZES SHOWN ON THE PLANS- PLEASE
 CORRECT.
  
 3) FAILED. P104, P105, & P402: THE PLANS SHOW BRANCH
 PIPING CONTINUATIONS TO APPLIANCES (BBQ GRILLS?) ON THE
 AMENITIES DECK. PLEASE REVISE THE RISER DRAWING TO
 INCLUDE THE PIPING AND APPLIANCE LOADS AND IDENTIFY THE
 APPLIANCES ON THE PLAN VIEW- SEC. 402.1 & 402.2 FBC FG.
 PIPE SIZES SHOWN AT THE NEW RISER ON P402 DO NOT MATCH
 SIZES SHOWN ON THE PLANS- PLEASE CORRECT.
  
 7) FAILED. P402: PROVIDE EQUIPMENT SCHEDULES FOR THE
 POOL HEATERS AND THE AMENITY APPLIANCES ON THE PLAN AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 MANUALS- SECTION 305.1 FBC FG. ACKNOWLEDGED THAT THE
 POOL HEATERS SPECS WILL BE SUBMITTED UNDER A SEPARATE
 GAS PERMIT HOWEVER THE REQUESTED BBQ SPECS AND INSTALL
 MANUALS WERE NOT PROVIDED. PLEASE PROVIDE THE SPECS AND
 WIND LOAD ANCHORING DETAILS FOR THE APPLIANCES- SECS.
 301.10 & 623.1 FBC FG.
  
 8) FAILED. P402: PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE POOL HEATERS AND INDICATE HOW THE AIR WILL BE
 PROVIDED- SEC. 304.1 FBC FG. THE NARRATIVE RESPONSE
 INDICATES PLAN SHEET M104, HOWEVER COMBUSTION CALCS ARE
 NOT PROVIDED ON THE PLAN.
  
 9) FAILED. P402: PROVIDE POOL HEATER GAS VENTING PLANS
 INCLUDING A DIAGRAM SHOWING THE TYPE AND SIZE OF VENT
 PIPING, THE VENT RUN AND TERMINATION LOCATION- SECS.
 305.1, 503.1 FBC FG. PLEASE INCLUDE VENT TERMINATION
 CLEARANCES AND SUBMIT SPECS FOR THE VENT MATERIALS-
 503.8. THE NARRATIVE RESPONSE INDICATES PLAN SHEET
 M104, HOWEVER VENTING DETAILS ARE NOT PROVIDED ON THE
 PLAN.
  
 NEW COMMENT:
  
 1) SHEET P402: PROVIDE ELECTRICAL BONDING DETAILS- SEC.
 310.1 FBC FG. PIPING LIKELY TO BECOME ENERGIZED SHALL
 BE ELECTRICALLY CONTINUOUS AND BONDED TO AN EFFECTIVE
 GROUND-FAULT CURRENT PATH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  