| 2022-04-05 11:18:05 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21091343 |
| | 4/5/22 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. |
| | |
| | 2) FAILED. P102- P104: SHOW GAS PIPING HORIZONTAL RUNS |
| | AND RISER LOCATIONS- - SEC. 107.2.1 WPB, AND SECS. |
| | 401.1 & 402.1 FBC FG. PIPE SIZES SHOWN AT THE NEW RISER |
| | ON P402 DO NOT MATCH SIZES SHOWN ON THE PLANS- PLEASE |
| | CORRECT. |
| | |
| | 3) FAILED. P104, P105, & P402: THE PLANS SHOW BRANCH |
| | PIPING CONTINUATIONS TO APPLIANCES (BBQ GRILLS?) ON THE |
| | AMENITIES DECK. PLEASE REVISE THE RISER DRAWING TO |
| | INCLUDE THE PIPING AND APPLIANCE LOADS AND IDENTIFY THE |
| | APPLIANCES ON THE PLAN VIEW- SEC. 402.1 & 402.2 FBC FG. |
| | PIPE SIZES SHOWN AT THE NEW RISER ON P402 DO NOT MATCH |
| | SIZES SHOWN ON THE PLANS- PLEASE CORRECT. |
| | |
| | 7) FAILED. P402: PROVIDE EQUIPMENT SCHEDULES FOR THE |
| | POOL HEATERS AND THE AMENITY APPLIANCES ON THE PLAN AND |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| | MANUALS- SECTION 305.1 FBC FG. ACKNOWLEDGED THAT THE |
| | POOL HEATERS SPECS WILL BE SUBMITTED UNDER A SEPARATE |
| | GAS PERMIT HOWEVER THE REQUESTED BBQ SPECS AND INSTALL |
| | MANUALS WERE NOT PROVIDED. PLEASE PROVIDE THE SPECS AND |
| | WIND LOAD ANCHORING DETAILS FOR THE APPLIANCES- SECS. |
| | 301.10 & 623.1 FBC FG. |
| | |
| | 8) FAILED. P402: PROVIDE COMBUSTION AIR CALCULATIONS |
| | FOR THE POOL HEATERS AND INDICATE HOW THE AIR WILL BE |
| | PROVIDED- SEC. 304.1 FBC FG. THE NARRATIVE RESPONSE |
| | INDICATES PLAN SHEET M104, HOWEVER COMBUSTION CALCS ARE |
| | NOT PROVIDED ON THE PLAN. |
| | |
| | 9) FAILED. P402: PROVIDE POOL HEATER GAS VENTING PLANS |
| | INCLUDING A DIAGRAM SHOWING THE TYPE AND SIZE OF VENT |
| | PIPING, THE VENT RUN AND TERMINATION LOCATION- SECS. |
| | 305.1, 503.1 FBC FG. PLEASE INCLUDE VENT TERMINATION |
| | CLEARANCES AND SUBMIT SPECS FOR THE VENT MATERIALS- |
| | 503.8. THE NARRATIVE RESPONSE INDICATES PLAN SHEET |
| | M104, HOWEVER VENTING DETAILS ARE NOT PROVIDED ON THE |
| | PLAN. |
| | |
| | NEW COMMENT: |
| | |
| | 1) SHEET P402: PROVIDE ELECTRICAL BONDING DETAILS- SEC. |
| | 310.1 FBC FG. PIPING LIKELY TO BECOME ENERGIZED SHALL |
| | BE ELECTRICALLY CONTINUOUS AND BONDED TO AN EFFECTIVE |
| | GROUND-FAULT CURRENT PATH. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |