| Plan Review Notes For Permit 21091343 |
| Permit Number |
21091343 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-11-24 08:15:14 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | RISER SHOWS NO GROUNDING ELECTRODE SYSTEM TO MAINS 2 OF | | | 3 AND 3 OF 3. 250.66 | | | | | | NO FAUL CURRENT CALCULATION FOR THE SERVICE 110.9, | | | 110.10 | | | | | | NO LOAD CALCULATION SHOW FOR THE SERVICE 215.5 | | | | | | UNITS AE, B7, D3 UNITS MISSING OUTLETS ON BALCONIES | | | 210.52 (E)(3) | | | | | | THE FOLLOWING REQUIRE SEPARATE PERMITS | | | | | | FIRE ALARAM | | | GENERATOR | | | POOL | | | LOW VOLTAGE WIRING TELEPHONE DATA | | | BDA SYSTEM | | | LIGHTNING PROTECTION | | | ACCESS CONTROL | | | CCTV | | | | | | | | | | | | |
|