Plan Review Notes
Plan Review Notes For Permit 21091343
Permit Number 21091343
Review Stop E
Sequence Number 2
Notes
Date Text
2021-11-24 08:15:14ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER SHOWS NO GROUNDING ELECTRODE SYSTEM TO MAINS 2 OF
 3 AND 3 OF 3. 250.66
  
 NO FAUL CURRENT CALCULATION FOR THE SERVICE 110.9,
 110.10
  
 NO LOAD CALCULATION SHOW FOR THE SERVICE 215.5
  
 UNITS AE, B7, D3 UNITS MISSING OUTLETS ON BALCONIES
 210.52 (E)(3)
  
 THE FOLLOWING REQUIRE SEPARATE PERMITS
  
 FIRE ALARAM
 GENERATOR
 POOL
 LOW VOLTAGE WIRING TELEPHONE DATA
 BDA SYSTEM
 LIGHTNING PROTECTION
 ACCESS CONTROL
 CCTV
  
  
  
  