Plan Review Notes
Plan Review Notes For Permit 21091343
Permit Number 21091343
Review Stop B
Sequence Number 2
Notes
Date Text
2022-03-30 12:58:37NEW RESIDENTIAL HI RISE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) GARAGE OPENING AREA CALCULATIONS SHOWS 18% FOR THE
 2ND FLOOR - SHOULD BE 20% - FBC 406.5.2 OPENINGS.
 FOR NATURAL VENTILATION PURPOSES, THE EXTERIOR SIDE OF
 THE STRUCTURE SHALL HAVE UNIFORMLY DISTRIBUTED OPENINGS
 ON TWO OR MORE SIDES. THE AREA OF SUCH OPENINGS IN
 EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20
 PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER.
 THE AGGREGATE LENGTH OF THE OPENINGS CONSIDERED TO BE
 PROVIDING NATURAL VENTILATION SHALL BE NOT LESS THAN 40
 PERCENT OF THE PERIMETER OF THE TIER. INTERIOR WALLS
 SHALL BE NOT LESS THAN 20 PERCENT OPEN WITH UNIFORMLY
 DISTRIBUTED OPENINGS.
  
 2) DRAWING A2-210 DETAIL 4 AND 5 AND DRAWING A2-211
 DETAIL 2 AND 4 - PLEASE SHOW RESTROOMS AND SERVICE SINK
 ROOM WALL AND FLOOR AND BASEBOARD FINISHES TO COMPLY
 WITH - FBC 1210.2.1 FLOORS AND WALL BASES. - 1210.2.2
 WALLS AND PARTITIONS. (DRYWALL IS NOT CONSIDERED A HARD
 SURFACE)
  
 3) GRAB BAR BACKING DETAILS PROVIDED NEED TO SHOW THE
 BACKING HEIGHT (SHOWER AREA SHOWS BACKING STARTING AT 2
 FEET FROM THE FLOOR BUT DOES NOT SHOW HOW HIGH) - ALL
 DIMENSIONS ARE NEEDED TO SHOW COMPLIANCE - FBC
 ACCESSIBILITY FHA REQUIREMENT 6 - REINFORCED BATHROOM
 WALLS TO ALLOW LATER INSTALLATION OF GRAB BARS AROUND
 THE TOILET, TUB, SHOWER STALL AND SHOWER SEAT, WHERE
 SUCH FACILITIES ARE PROVIDED, WOULD MEET SECTION
 100.205(C)(3)(III) IF REINFORCED AREAS ARE PROVIDED AT
 LEAST AT THOSE POINTS WHERE GRAB BARS WILL BE MOUNTED.
  
 4) PLEASE USE THE WORDS "REFLECTIVE SURFACE" - COMMON
 AREA RESTROOMS - PLEASE SHOW MIRROR DIMENSION FROM THE
 FINISHED FLOOR TO THE BOTTOM OF THE "REFLECTIVE
 SURFACE" - FBC ACCESSIBILITY FHA REQUIREMENT 2 WHERE
 PROVIDED IN PUBLIC-USE AND COMMON-USE FACILITIES, AT
 LEAST ONE OF EACH FIXTURE PROVIDED PER ROOM. (ANSI)
 A117.1-1986 - 4.19.6* MIRRORS. MIRRORS SHALL BE MOUNTED
 WITH THE BOTTOM EDGE OF THE REFLECTING SURFACE NO
 HIGHER THAN 40 IN (1015 MM) FROM THE FLOOR (SEE FIG.
 31).
  
 5) DRAWING A4-301 - TRASH CHUTE DOOR SHOULD BE (1 1/2 )
 HOUR FIRE RATED PER FBC 716.5
  
 6) DRAWING A1-104 AND A0-104 PLEASE SHOW THE FIRE RATED
 SEPARATION - STAIRWELL AND TRASH CHUTE - FBC 713.13.1
 WASTE AND LINEN.
 A SHAFT ENCLOSURE CONTAINING A RECYCLING, OR WASTE OR
 LINEN CHUTE SHALL NOT BE USED FOR ANY OTHER PURPOSE
  
 7) DRAWING A1-103 - PLEASE SHOW THE FIRE RATED TRASH
 CHUTE ROOM DOOR - FBC 713.13.3 CHUTE ACCESS ROOMS.
 ACCESS OPENINGS FOR WASTE OR LINEN CHUTES SHALL BE
 LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY NOT LESS
 THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE
 WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED
 IN ACCORDANCE WITH SECTION 711, OR BOTH. OPENINGS INTO
 THE ACCESS ROOMS SHALL BE PROTECTED BY OPENING
 PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS
 THAN 3/4 HOUR. DOORS SHALL BE SELF- OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 716.5.9.4.
  
 8) DRAWINGS A0-103, A0-104, A0-105, A0-107 - PLEASE
 SHOW THE HOURLY SHAFT FOR THE TRASH CHUTE FIRE RATING -
 FBC 713.4 FIRE-RESISTANCE RATING.
 SHAFT ENCLOSURES SHALL HAVE A FIRE-RESISTANCE RATING OF
 NOT LESS THAN 2 HOURS
  
 9) DRAWING A1-303 DETAIL 10 - THE CLEAR FLOOR SPACE FOR
 THE SINK DOES NOT APPEAR TO BE CENTERED ON THE SINK
 BASED ON THE DIMENSIONS SHOWN FOR THE SINK. FBC FHA
 REQUIREMENT 7 (2)
  
 10) DOOR SWINGS INTO THE REQUIRED CLEAR FLOOR SPACE -
 DRAWINGS A1-304 DETAIL 1, DRAWING A1-303 DETAIL 2,
 DRAWING A1-302 DETAIL 3 - FBC FHA REQUIREMENT 7 (2)
  
 11) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD SHALL CONTAIN A STATEMENT THAT,
 TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND CHAPTER 633 FLORIDA
 STATUTES.
  
 12) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
 ( FOR FLOORS OTHER THAN CARPET )
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 13) FLOORING IIC AND STC REQUIRED TEST REPORTS AND
 ROOFTOP EQUIPMENT SCREENING DETAILS CAN BE ADDED TO THE
 DEFERRED SUBMITTALS LIST - PLEASE LIST ITEMS TO BE
 DEFERRED ON THE CONSTRUCTION DOCUMENTS - 107.3.4.1
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
  
  
  
  