Plan Review Notes
Plan Review Notes For Permit 21091343
Permit Number 21091343
Review Stop P
Sequence Number 1
Notes
Date Text
2021-12-15 09:35:001ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21091343
 12/14/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A0-000 & P101: PLEASE PROVIDE ON THE PLANS A
 LIST OF REQUIRED SEPARATE PERMITS INCLUDING: POOL, POOL
 HEATERS, GREASE INTERCEPTOR, IRRIGATION, GENERATOR,
 POTABLE WATER BACKFLOW PREVENTER, IRRIGATION SYSTEM
 BACKFLOW PREVENTER, POOL SERVICE BACKFLOW PREVENTER,
 FIRE LINE BACKFLOW PREVENTER, FIRE LINE, FIRE
 SPRINKLER, AND THE FIRE PUMP- SECTIONS 105.1 & 107.2.1
 WPB.
  
 2) P101- DEFERRED SUBMITTALS: MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION GUIDELINES FOR PLUMBING
 AND GAS EQUIPMENT, APPLIANCES, FIXTURES, CONTROLS,
 PIPING AND MATERIALS THAT ARE NOT SUBMITTED FOR REVIEW
 CAN BE DEFERRED SUBMITTALS IN ACCORDANCE WITH SECTION
 PROVIDE A LIST OF DEFERRED SUBMITTALS ON THE PLAN
 INCLUDING BUT NOT LIMITED TO THE DOMESTIC WATER PUMP,
 WATER HEATERS, KITCHEN AND BATH FIXTURES APPLIANCES,
 EXPANSION TANKS, FULL OPEN VALVES, MIXING VALVES,
 BACKFLOW PREVENTERS, RECIRCULATION PUMPS, WATER HAMMER
 ARRESTORS, TRAP PRIMERS, ROOF DRAINS, TERMINATION CAPS
 ETC.- SECTION 107.3.4.1 WPB.
  
 3) P101- SWIMMING POOL WASTE WATER: THE POOL SHALL BE
 UNDER SEPARATE PERMIT HOWEVER DISPOSAL OF POOL WASTE
 WATER MAY IMPACT THE MAIN STORM DRAIN PLANS. PLEASE
 REVIEW THE FOLLOWING GUIDELINES FOR DISPOSAL OF THE
 WASTE WATER-
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER?S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL
 OWNER?S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 E) FOR TECHNICAL QUESTIONS, DON'T HESITATE TO CONTACT
 O&M SUPERINTENDENT STEPHON HARRIS AT [email protected] OR
 561-822-2168.
 F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS,
 PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
 4) P101 & P400: TO HELP EXPEDITE THE REVIEW, PLEASE ADD
 THE ABBREVIATIONS DP, OF, AND SPK TO THE ABBREVIATION
 LEGEND- SEC. 107.2.1 WPB.
  
 5) P101: PROVIDE THE TEXT FOR CIRCLED KEYNOTES 1, 2, &
 3- SEC. 107.2.1 WPB.
  
 6) P101: PLEASE CORRECT THE SHEET TITLE INDICATING THE
 6TH FLOOR- SEC. 107.2.1 WPB.
  
 7) P101: PLEASE SHOW THE SS- 28, 28A, AND 29 PIPE
 CONNECTIONS INTO THE 6-INCH SANITARY LINE- SEC. 107.2.1
 WPB.
  
 8) P101: PLEASE IDENTIFY THE STORM DRAIN MANHOLE AND
 SHOW THE DRAINAGE CONTINUATION OUT OF THE BUILDING-
 SEC. 1101.2 FBC P.
  
 9) P101 & P400: INDICATE HOW THE ELEVATOR SUMP PITS
 WILL BE VENTED AND SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE PUMP AND THE PIT- SEC. 712.3 FBC P.
  
 10) P101 GREASE INTERCEPTOR- SECS. 1003.1- 1003.3.8 FBC
 P.
 A) SHOW THE GREASE WASTE PIPE POINT OF CONNECTION TO
 THE SANITARY.
 B) PROVIDE AN INTERCEPTOR EQUIPMENT SCHEDULE- MAKE AND
 MODEL, GALLON SIZE. THERE IS A NOTE BY THE LOADING AREA
 SPECIFYING SCHIER GB-1000. PLEASE RELOCATE THE NOTE TO
 THE INTERCEPTOR LOCATION IF THIS THE MODEL TO BE
 INSTALLED.
 C) PROVIDE GREASE WASTE CALCULATIONS.
 D) SHOW THE SAMPLING PORT AND VENTING LOCATIONS.
 E) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS.
  
 PLEASE NOTE INSTALLATION OF THE GREASE INTERCEPTOR
 SHALL BE UNDER SEPARATE PERMIT. THE REQUESTED SUBMITTAL
 MAY BE DEFERRED BY REQUEST- SECS. 105.1 & 107.3.4.1
 WPB.
  
 11) P101- THERE ARE MANY MISSING DRAIN POINTS OF
 CONNECTION TO STORM OR SANITARY MAINS, OR CONTINUATIONS
 TO APPROVED DISPOSAL LOCATIONS. PLEASE PLACE NOTES ON
 THE PLAN TO INDICATE DISCHARGE OR CONNECTION LOCATIONS
 OF THE DP, CD, PD, AD, & O.F. PIPES- SEC. 107.2.1 WPB.
 A) THE MAIN 4-INCH GARAGE DRAIN PIPE (GD) IS SHOWN
 EXITING THE BUILDING TO AN UNIDENTIFIED LOCATION- SEC.
 107.2.1 WPB.
 B) O.F. DRAINS SHOWN TERMINATING IN RETAIL 104,
 CORRIDOR 127, & BICYCLE STORAGE 100. PLEASE NOTE THAT
 IF THE DRAINS ARE TO CONNECT DIRECTLY TO THE GD PIPE,
 PLEASE CLARIFY HOW EMERGENCY OVERFLOW WILL BE OBSERVED
 MY BUILDING OCCUPANTS OR MAINTENANCE PERSONNEL- SEC.
 1108.2 FBC P.
 C) REFER TO SECTION 1503.7 FBC B AND PROVIDE A DETAIL
 SHOWING THE O.F. DISCHARGE TERMINATION CAP AND MINIMUM
 12-INCH DISCHARGE DISTANCE FROM THE STRUCTURE
 SIDEWALLS.
  
 12) P101 & P301: SANITARY DRAINS FROM UNITS 107, 110, &
 11 TO MAIN SS NOT SHOWN- SEC. 107.2.1 WPB.
  
 13) P101 & P301: SHOW THE WATER SERVICE PIPING
 ENTRANCES TO UNITS 107, 110, & 111 ON P101- SEC. 602.1
 FBC P.
  
 14) P101 & P400: PROVIDE FIXTURE SCHEDULES FOR THE
 GARAGE DRAINS, TRENCH DRAINS, FLOOR DRAINS, AND FLOOR
 SINKS- SECS. 413, 414 FBC P. PROVIDE HEAVY DUTY TRAFFIC
 RATED COVERS FOR THE GARAGE AND TRENCH DRAINS.
  
 15) P101, P102, P103, P104, P105, P106: PLEASE PROVIDE
 THE MAIN PLUMBING RISER DRAWINGS THAT CORRELATE WITH
 THE CIRCLE SYMBOLS AT THE BASE OF EACH VERTICAL STACK
 LOCATION INCLUDING THE (SS- SANITARY). (CD- CONDENSATE
 PIPES), (DP- DISCHARGE PIPES FROM WATER HEATERS), (RWL-
 RAIN WATER LEADERS), (PD-PLANTER DRAINS) - SEC.
 107.3.5.1.3 WPB. PLEASE PROVIDE SUPPORT AND BRACING
 DETAILS FOR THE RISERS- SECS. 308.1- 308.9 FBC P.
  
 16) P101: PROVIDE TOTAL DFU CALCULATIONS AND THE MAIN
 SANITARY PIPE SIZES ALONG THE HORIZONTAL RUN FROM THE
 SOUTH END OF THE CORRIDOR TO THE EXIT ON THE NORTH END-
 SECS. 709 AND 710 FBC P.
  
 17) P101: SHOW LOCATIONS OF CLEANOUTS IN ACCORDANCE
 WITH SECS. 708.1.1, 708.1.3, & 708.1.4 FBC P.
  
 18) P101: PROVIDE WSFU CALCULATIONS AND MAIN WATER
 RISER DRAWING- SECS. 603.1, E103 FBC P, AND SEC.
 107.3.5.1.3 WPB.
  
 19) P101, P102, P103, P104: PROVIDE A HOSE BIB WATER
 RISER DRAWING- SEC. 107.3.5.1.3 WPB.
  
 20) P101, P102, P103, P104: PROVIDE A GARAGE DRAIN
 RISER DRAWING- SEC. 107.3.5.1.3 WPB.
  
 21) P102, P103, P104: SOME OF THE CIRCLED SYMBOLS ARE
 MISSING PIPE IDENTIFICATIONS. PLEASE REVIEW AND
 CORRECT- SEC. 107.2.1 WPB.
  
 22) P104 & P107- ROOF DRAINAGE:
 A) PROVIDE PRIMARY AND OVERFLOW ROOF DRAIN RISER
 DRAWINGS- SECTION 107.3.5.1.3 WPB, AND SECS. 1106.1,
 1106.1, & 1108.1 FBC P.
 B) INDICATE THE RAINFALL RATE PER SEC. 1106.1 AND
 PROVIDE ROOF DRAINAGE CALCULATIONS BASED ON THE RATE-
 SECS. 1106.1- 1106.3 FBC P. P
 C) VERIFY THE ROOF AND DRAINAGE SYSTEM HAS BEEN
 DESIGNED IN COMPLIANCE WITH SECTION 1101.7 FOR MAXIMUM
 DEPTH OF PONDING WATER AND DEFLECTED STRUCTURAL
 ELEMENTS.
 D) PROVIDE THE MAKES AND MODELS OF THE ROOF AND
 OVERFLOW DRAINS AND SUBMIT MANUFACTURER?S
 SPECIFICATIONS PER SEC. 1105.1 FBC P.
  
 23) P201, P201A: PLEASE LABEL WHAT FLOOR THIS PLAN
 SHEET IS FOR AND PROVIDE ROOM NUMBERS FOR THE ENLARGED
 #2 SANITARY AND WATER LAYOUT DRAWINGS- SEC. 107.2.1
 WPB.
  
 24) P201A: PLEASE INDICATE HOW TEMPERED WATER WILL BE
 DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC P.
  
 25) P201A: THE PLAN APPEARS TO SHOW THE 1/2-INCH HW
 PIPES TO THE LAVATORIES HAVE EXCEEDED THE MAXIMUM
 ALLOWABLE LENGTHS OF 2 FT. FROM THE SOURCE OF THE HW-
 SEE TABLE C404.5.1 FBC EC. PROVIDE EITHER RECIRCULATION
 PUMPS OR POINT OF USE WATER HEATERS.
  
 26) P205: PLEASE INDICATE HOW TEMPERED WATER WILL BE
 DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC P.
  
 27) P205: SHOW THE VENT LOCATIONS AND VENT SIZES IN THE
 ENLARGED SANITARY DRAWINGS- SECS. 909-912 FBC P.
  
 28) P301, P303, P305, P401: SHOW THE LOCATIONS OF THE
 REQUIRED EXPANSION TANKS FOR THE WATER HEATERS- SEC.
 607.3 FBC P.
  
 29) P301, P303, P305, P401: BASED ON THE WATER HEATER
 DETAILS ON P401, PLEASE SHOW THE HW RECIRCULATION LINES
 IN THE ISOMETRIC DRAWINGS- SEC. 107.2.1 WPB, AND 607.2
 FBC P.
  
 30) P301, P303, P305, P401: PROVIDE BACKFLOW PREVENTION
 FOR THE WATER SUPPLY LINES TO THE DISHWASHER AND
 REFRIGERATOR ICE MAKERS- SECTIONS 409.2 & 608.3 FBC P.
  
 31) P302: PLEASE PROVIDE THE DRAIN AND VENT PIPE SIZES
 FOR THE WM AND SK/DW RISERS- SECS. 406.2 & 409.2 FBC P.
  
 32) P400: DOMESTIC DISHWASHERS SHALL CONFORM TO NSF
 184, NOT ASSE 1006 AS THE SCHEDULE INDICATES- SEC.
 409.1 FBC P.
  
 33) P401- CORRELATE THE WATER HEATER DISCHARGE PIPING
 DETAIL TO MATCH THE PLUMBING PLANS WHICH SHOW COMMON
 RISER PIPES CONVEYING THE DISCHARGES TO THE STORM DRAIN
 SYSTEM- SEC. 107.2.1 WPB, & SECS. 504.6- 504.7.2 FBC P.
  
 34) P401: WATER HEATER UNIT LOCATIONS NOT INDICATED
 BELOW THE DETAILS- SEC. 107.2.1 WPB.
  
 35) A0-003: PLEASE CORRECT ZONING REFERENCE INDICATING
 THE CITY OF HOLLYWOOD- SECTION 107.2.1 WPB.
  
 36) A0-003 DESIGN CRITERIA: INDICATE WHICH CODES AND/OR
 STANDARDS WERE USED IN THE DESIGN OF THE PUBLIC
 BATHROOMS AND PRIVATE KITCHEN AND BATHROOMS- SECTION
 107.2.1 WPB. PLEASE NOTE THAT THE FBC-2020 7TH EDITION
 ACCESSIBILITY CODE IS THE CURRENT CODE USED IN THE CITY
 OF WPB FOR PLUMBING FIXTURE INSTALLATIONS IN PLACES OF
 PUBLIC ACCOMMODATION AND COMMERCIAL FACILITIES- SEC.
 210.1 FBC ACC. THE FBC ACC SHALL BE USED FOR DESIGN OF
 THE 1ST AND 7TH FLOOR BATHROOMS. CONCERNING THE PRIVATE
 APARTMENT KITCHENS AND BATHS, THE DESIGN AND
 INSTALLATION OF PLUMBING FIXTURES IN THE PRIVATE
 KITCHENS AND BATHROOMS SHALL BE IN COMPLIANCE WITH THE
 FAIR HOUSING ACT DESIGN MANUAL OR THE FAIR HOUSING
 ACCESSIBILITY GUIDELINES. THE GUIDELINES WHICH ARE
 FOUND IN THE FBC ACC PROVIDE SAFE HARBOR FOR COMPLIANCE
 WITH THE ACCESSIBILITY REQUIREMENTS OF THE FAIR HOUSING
 ACT. THE DESIGNER OF RECORD SHALL CHOOSE WHICH DESIGN
 METHOD WILL BE USED AND PROVIDE DRAWINGS AND DETAILS
 INDICATING COMPLIANCE.
  
 37) A0-101 & A1-101- PLUMBING FIXTURE CALCULATIONS-
 SECTION AND TABLE 403.1 FBC P..
  
 A) CORRECT THE NOTE IN THE TABLE REFERENCING A0.105 FOR
 BREAKDOWN. NO BREAKDOWN IS SHOWN ON THAT PLAN SHEET.
 B) PROVIDE SEPARATE FIXTURE CALCULATION TABLES FOR
 RETAIL- 102, RETAIL- 104, OFFICE/RETAIL- 105. PLEASE
 REVISE THE PLANS TO SHOW THE LOCATIONS OF THE FIXTURES
 AND PLUMBING PIPING REQUIREMENTS. THE REQUIRED FIXTURES
 FOR THESE OCCUPANCIES CAN BE LISTED AS "FUTURE" IF
 NECESSARY.
  
 38) A0-106 & A1-106: THE OCCUPANT LOAD OF 456 SHOWN IN
 THE PLUMBING FIXTURE CALCULATION TABLE IS INCORRECT
 BASED ON THE LIFE SAFETY LOAD TABLE WHICH INDICATES
 562- TABLE 403.1 FBC P.
  
 39) A1-106: PLEASE PROVIDE THE CODE SECTION ASSOCIATED
 WITH THE SWIMMING POOL EXCEPTION AND SHOW THE 200-FOOT
 HORIZONTAL RADIUS TO VERIFY COMPLIANCE- SECTION 403.6
 FBC P. IT APPEARS DESPITE THE EXCEPTION, THE PLANS
 INDICATE COMBINED POOLSIDE AND AMENITIES BATHROOMS.
 PLEASE CLARIFY IF FLOOR DRAINS WILL BE INSTALLED- NONE
 SHOWN ON P205- SEC. 403.6.3 FBC ZP.
  
 40) A1-320- FBC- ACC MISSING AND INCORRECT COMPLIANCE
 DETAILS. PLEASE NOTE THAT NEW CONSTRUCTION ACCESSIBLE
 COMPARTMENTS SHALL BE DESIGNED IN ACCORDANCE WITH
 604.8.1.6 & 604.8.1.7.:
 A) SHOW CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR
 THE WATER CLOSETS- SEC. 604.3.
 B) SHOW CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR
 THE LAVATORIES- 606.2.
 C) SHOW TURNING SPACE DIAMETERS- 304.3.
 D) THE DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACES FOR THE FIXTURES- 603.2.3.
 E) SHOW CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR
 THE ACCESSIBLE URINALS- 605.3.
 F) THE CENTERLINE OF THE WATER CLOSET FROM THE SIDE
 WALL IN THE MEN?S 724 COMPARTMENT EXCEEDS THE MAXIMUM
 18 INCHES - SECTION 604.2.
 G) SHOW THE HEIGHTS OF THE MIRRORS FROM THE FINISHED
 FLOORS NOT SHOWN TO THE REFLECTIVE SURFACES- SECTION
 603.3
 H) SHOW THE LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS IN COMPLIANCE WITH -
 SECTION 604.5 & 609.4, FIGURES 604.5.1 & 604.5.2.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS SHALL BE
 7 INCHES MINIMUM AND 9 INCHES MAXIMUM MEASURED FROM THE
 FRONTS OF THE WATER CLOSETS- SECTION AND FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
 L) DEPTH OF THE ACCESSIBLE URINAL- 605.2.
 M) CLEAR WIDTHS OF THE ACCESSIBLE COMPARTMENT DOORS-
 404.2.3.
  
 41) A1-320: SHOW THE DEPTH AND WIDTH DIMENSIONS OF THE
 STANDARD WATER CLOSET COMPARTMENTS- SEC 405.3 FBC P.
  
 42) A1-301: BASED ON THE NOTE INDICATING SPECIFICATION
 A, IT IS ASSUMED THE PRIVATE ROOMS HAVE BEEN DESIGNED
 IN ACCORDANCE WITH THE FAIR HOUSING DESIGN ACT MANUAL
 WHICH IS BASED ON THE (ANSI) A117.1.1986.
  
 43) A1-301 UNIT A2: THE CLEAR FLOOR SPACE FORWARD
 APPROACH DIAGRAMS FOR THE KITCHEN SINK AND RANGE DO NOT
 SHOW THE REQUIRED EXTENSIONS NEEDED FOR KNEE AND TOE
 CLEARANCES. PLEASE SEE FHA MANUAL- PAGE 7.4. UNLESS
 KNEE SPACE IS PROVIDED, SPACE TO EXECUTE A PARALLEL
 APPROACH MUST BE PROVIDED AT RANGES, COOKTOPS AND
 SINKS. PLEASE CORRECT THE DRAWING OR PROVIDE A DETAIL
 TO INDICATE HOW KNEE SPACE WILL BE PROVIDED.
  
 44) A1-303 UNIT B1 & A1- 304 UNITS B2, B3: PROVIDE A
 60-INCH DIAMETER TURNING CIRCLE IN THE KITCHEN- FHA
 MANUAL- PAGE 7.9.
  
 45) A1-301 THRU A1-311: PROVIDE THE CLEAR FLOOR SPACE
 DIAGRAMS AND DIMENSIONS FOR THE WATER CLOSETS, AND THE
 CENTERLINES OF THE WATER CLOSETS- FHA MANUAL 7.43-
 7.46. PLEASE INDICATE THE DIRECTIONAL APPROACH TO THE
 WATER CLOSET USING AN ARROW SYMBOL, AND THE DEPTH OF
 THE LAVATORY AND/OR VANITY CABINET.
  
 46) A1-301 UNITS A1, A2, A3: THE CLEAR FLOOR SPACES FOR
 THE LAVATORIES ARE BEING OBSTRUCTED BY THE WATER
 CLOSETS- FHA MANUAL PGS. 7.39 & 7.47.
  
 47) A1-302 UNIT A5: THE CLEAR FLOOR SPACE FOR THE
 LAVATORY IS BEING OBSTRUCTED BY THE WATER CLOSETS- FHA
 MANUAL PGS. 7.39 & 7.47.
  
 48) A1-304 UNITS B2 & B3: SHOW A 30X48-INCH MINIMUM
 UNOBSTRUCTED CLEAR FLOOR SPACE DIAGRAM OUTSIDE THE ARC
 OF THE IN-SWINGING DOOR- FHA MANUAL 7.40.
  
 49) A1-305 UNITS B7 & C2: SHOW A 30X48-INCH MINIMUM
 UNOBSTRUCTED CLEAR FLOOR SPACE DIAGRAM OUTSIDE THE ARC
 OF THE IN-SWINGING DOOR- FHA MANUAL 7.40.
  
 50) A1-305 UNIT C1: SHOW THE MINIMUM REQUIRED
 30X48-INCH CLEAR FLOOR SPACE DIAGRAM FOR A PARALLEL
 APPROACH TO THE BATHTUB- FHA MANUAL 7.53- 7.55, AND FHA
 GUIDELINES FIGURE 8.
  
 51) A1-306 UNITS C2 & C3: SHOW THE MINIMUM REQUIRED
 30X48-INCH CLEAR FLOOR SPACE DIAGRAMS FOR PARALLEL
 APPROACHES TO THE BATHTUBS- FHA MANUAL 7.53- 7.55, AND
 FHA GUIDELINES FIGURE 8. PLEASE NOTE THAT COMPLIANCE IN
 C3 WILL NOT BE POSSIBLE UNLESS A WALL HUNG LAVATORY
 SINK WITH KNEE AND TOE CLEARANCES IS PROVIDED.
  
 52) A1-306 UNIT C3: SHOW A 30X48-INCH MINIMUM
 UNOBSTRUCTED CLEAR FLOOR SPACE DIAGRAM OUTSIDE THE ARC
 OF THE IN-SWINGING DOOR- FHA MANUAL 7.40.
  
 53) A1-307 UNITS C4 & C5: SHOW 30X48-INCH MINIMUM
 UNOBSTRUCTED CLEAR FLOOR SPACE DIAGRAMS OUTSIDE THE
 ARCS OF THE IN-SWINGING DOORS- FHA MANUAL 7.40.
  
 54) A1-307 UNIT C5: SHOW THE MINIMUM REQUIRED
 30X48-INCH CLEAR FLOOR SPACE DIAGRAM FOR A PARALLEL
 APPROACH TO THE BATHTUB- FHA MANUAL 7.53- 7.55, AND FHA
 GUIDELINES FIGURE 8. PLEASE NOTE THAT COMPLIANCE WILL
 NOT BE POSSIBLE UNLESS A WALL HUNG LAVATORY SINK WITH
 KNEE AND TOE CLEARANCES IS PROVIDED.
  
 55) A1-309 & A1-310 UNIT D1 MASTER BATH: SHOW THE
 MINIMUM REQUIRED 30X48-INCH CLEAR FLOOR SPACE DIAGRAM
 FOR A PARALLEL APPROACH TO THE BATHTUB- FHA MANUAL
 7.53- 7.55, AND FHA GUIDELINES FIGURE 8. PLEASE NOTE
 THAT COMPLIANCE WILL NOT BE POSSIBLE BASED ON THE
 LOCATION OF THE WATER CLOSET.
  
 56) A1-311 UNIT D-3: SHOW 30X48-INCH MINIMUM
 UNOBSTRUCTED CLEAR FLOOR SPACE DIAGRAMS OUTSIDE THE
 ARCS OF THE IN-SWINGING DOORS- FHA MANUAL 7.40.
  
 57) PROVIDE PLUMBING FIXTURE GRAB BAR REINFORCMENT
 DETAILS. PROVIDE DRAWINGS THAT INDICATE THE LOCATIONS,
 LENGTHS, MOUNTING HEIGHTS, AND WIDTH OF REINFORCEMENTS
 FOR WATER CLOSETS AND BATHTUBS- SEE FHA MANAUAL PGS 6.1
 - 6.16. PLEASE INDICATE THE TYPE AND THICKNESS OF
 BACKING MATERIAL AND FASTENING DETAILS.
  
 58) P103- P105: THE AD PIPE SHALL NOT PENETRATE INTO
 THE INTERIOR EXIST STAIRWAY- SECTION 1023.5 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  