| 2021-11-15 14:50:28 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21091343 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) SHEET M1/01: IN UNIT B-7 PLEASE SHOW THE EXHAUST |
| | TERMINATION LOCATION IS ON THE EXTERIOR OF THE BUILDING |
| | AND NOT INSIDE THE PARKING GARAGE. FBC M 501.3 |
| | |
| | 2) SHEET M1/01: PLEASE SHOW THE OUTDOOR AIR DUCT FOR |
| | AHU-1L-6. FBC M 107.2.1 |
| | |
| | 3) SHEET M1/01: PLEASE SHOW THE FIRE DAMPER AT THE |
| | RATED WALLS WHERE THE OUTDOOR AIR PENETRATES FOR THE |
| | PET WASH AND THE STORAGE ROOMS AND THE RATED CORRIDOR |
| | WALL. FBC M 607 |
| | |
| | 4) SHEET M1/01: PLEASE SHOW HOW THE GENERATOR ROOM WILL |
| | BE SUPPLIED WITH OUTDOOR AIR FROM THE EXTERIOR OF THE |
| | BUILDING AND NOT THE PARKING GARAGE. FBC 107.2.1 |
| | |
| | 5) PLEASE PROVIDE VENTILATION CALCULATIONS FOR THE |
| | PARKING GARAGES. FBC M 404 |
| | |
| | 6) PLEASE SHOW THE PARKING GARAGE FANS AND EXHAUST |
| | TERMINATION LOCATIONS FOR EACH FLOOR. FBC 107.2.1 |
| | |
| | 7) SHEET M1/05B: PLEASE SHOW THE OUTDOOR AIR DUCT FOR |
| | AHU-7-2 IN THE FITNESS CENTER. FBC 107.2.1 |
| | |
| | 8) SHEET M1/05B: PLEASE SHOW THE REQUIRED FIRE DAMPERS |
| | FOR THE OUTDOOR AIR FOR THE TENANTS AS THE DESIGN DOES |
| | NOT MEET FBC M 607.5.3-3.3: THE DUCT SHALL NOT HAVE |
| | OPENINGS THAT COMMUNICATE THE CORRIDOR WITH ADJACENT |
| | SPACES OR ROOMS. |
| | |
| | 9) PLEASE PROVIDE INFORMATION ON THE DRYER DUCT FOR |
| | EACH UNIT. FBC M 504.6, 504.8.4 |
| | |
| | 10) SHEET M201: UNIT B-7, PLEASE SHOW THE RETURN AIR |
| | PATH FROM THE BEDROOM BACK TO THE FCU-C. FBC M 601.5 |
| | |
| | 11) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR |
| | THIS BUILDING, PLEASE USE TABLE 403.3.1.1 OCCUPANCY |
| | CLASSIFICATION TO DETERMINE THE USE OF EACH SPACE. FBC |
| | M 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | 12) A1-110: PLEASE SHOW THAT THE CLEARANCES FROM THE |
| | MECHANICAL UNITS TO THE ROOF EDGE WILL MEET THE 10 FT. |
| | CLEARANCE OR GUARD PROTECTION. FBC M 304.11 |
| | |
| | 13) PLEASE ADD A NOTE ON THE DRAWINGS THAT STATES THE |
| | GENERATOR WILL REQUIRE SEPARATE PERMIT APPLICATION, |
| | REVIEW AND DOCUMENTS FOR REVIEW AS THE GENERATOR WILL |
| | REQUIRE A SEPARATE PERMIT. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |