2021-11-15 14:50:281ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21091343
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) SHEET M1/01: IN UNIT B-7 PLEASE SHOW THE EXHAUST
 TERMINATION LOCATION IS ON THE EXTERIOR OF THE BUILDING
 AND NOT INSIDE THE PARKING GARAGE. FBC M 501.3
  
 2) SHEET M1/01: PLEASE SHOW THE OUTDOOR AIR DUCT FOR
 AHU-1L-6. FBC M 107.2.1
  
 3) SHEET M1/01: PLEASE SHOW THE FIRE DAMPER AT THE
 RATED WALLS WHERE THE OUTDOOR AIR PENETRATES FOR THE
 PET WASH AND THE STORAGE ROOMS AND THE RATED CORRIDOR
 WALL. FBC M 607
  
 4) SHEET M1/01: PLEASE SHOW HOW THE GENERATOR ROOM WILL
 BE SUPPLIED WITH OUTDOOR AIR FROM THE EXTERIOR OF THE
 BUILDING AND NOT THE PARKING GARAGE. FBC 107.2.1
  
 5) PLEASE PROVIDE VENTILATION CALCULATIONS FOR THE
 PARKING GARAGES. FBC M 404
  
 6) PLEASE SHOW THE PARKING GARAGE FANS AND EXHAUST
 TERMINATION LOCATIONS FOR EACH FLOOR. FBC 107.2.1
  
 7) SHEET M1/05B: PLEASE SHOW THE OUTDOOR AIR DUCT FOR
 AHU-7-2 IN THE FITNESS CENTER. FBC 107.2.1
  
 8) SHEET M1/05B: PLEASE SHOW THE REQUIRED FIRE DAMPERS
 FOR THE OUTDOOR AIR FOR THE TENANTS AS THE DESIGN DOES
 NOT MEET FBC M 607.5.3-3.3: THE DUCT SHALL NOT HAVE
 OPENINGS THAT COMMUNICATE THE CORRIDOR WITH ADJACENT
 SPACES OR ROOMS.
  
 9) PLEASE PROVIDE INFORMATION ON THE DRYER DUCT FOR
 EACH UNIT. FBC M 504.6, 504.8.4
  
 10) SHEET M201: UNIT B-7, PLEASE SHOW THE RETURN AIR
 PATH FROM THE BEDROOM BACK TO THE FCU-C. FBC M 601.5
  
 11) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR
 THIS BUILDING, PLEASE USE TABLE 403.3.1.1 OCCUPANCY
 CLASSIFICATION TO DETERMINE THE USE OF EACH SPACE. FBC
 M 403.3.1.1 AND TABLE 403.3.1.1
  
 12) A1-110: PLEASE SHOW THAT THE CLEARANCES FROM THE
 MECHANICAL UNITS TO THE ROOF EDGE WILL MEET THE 10 FT.
 CLEARANCE OR GUARD PROTECTION. FBC M 304.11
  
 13) PLEASE ADD A NOTE ON THE DRAWINGS THAT STATES THE
 GENERATOR WILL REQUIRE SEPARATE PERMIT APPLICATION,
 REVIEW AND DOCUMENTS FOR REVIEW AS THE GENERATOR WILL
 REQUIRE A SEPARATE PERMIT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  