Plan Review Notes
Plan Review Notes For Permit 21091343
Permit Number 21091343
Review Stop G
Sequence Number 1
Notes
Date Text
2021-12-15 11:53:381ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21091343
 12/15/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS C-08 & P101: SHOW THE GAS PIPING RUNS FROM
 THE MAIN LINE ONSITE TO THE METER AT THE BUILDING, AND
 FROM THE METER THROUGH THE BUILDING TO THE RISER
 LOCATION- SEC. 107.2.1 WPB, AND SECS. 401.1 & 402.1 FBC
 FG.
  
 2) P102- P104: SHOW GAS PIPING HORIZONTAL RUNS AND
 RISER LOCATIONS- - SEC. 107.2.1 WPB, AND SECS. 401.1 &
 402.1 FBC FG.
  
 3) P104, P105, & P402: THE PLANS SHOW BRANCH PIPING
 CONTINUATIONS TO APPLIANCES (BBQ GRILLS?) ON THE
 AMENITIES DECK. PLEASE REVISE THE RISER DRAWING TO
 INCLUDE THE PIPING AND APPLIANCE LOADS AND IDENTIFY THE
 APPLIANCES ON THE PLAN VIEW- SEC. 402.1 & 402.2 FBC FG.
  
 4) P104 & P402: THE PLAN SHOWS ONE POOL HEATER, THE ISO
 SHOWS TWO- PLEASE CORRECT.
  
 5) P402: PROVIDE THE MAKE AND MODEL OF THE REGULATORS
 AND INDICATE THE OUTPUT PRESSURES- SEC. 410.2 FBC FG.
 A) PLEASE SHOW THE REQUIRED TEST TEE FITTINGS UPSTREAM
 AND DOWNSTREAM OF THE REGULATORS, AND THE REQUIRED PIPE
 UNIONS WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR-
 SEC.410.2 (ITEMS 6 & 7).
  
 6) P402: PROVIDE VENTING DETAILS FOR THE REGULATORS IF
 THE REGULATORS ARE NOT EQUIPPED WITH APPROVED
 VENT-LIMITING DEVICES- SEC. 410.2 FBC FG.
  
 7) P402: PROVIDE EQUIPMENT SCHEDULES FOR THE POOL
 HEATERS AND THE AMENITY APPLIANCES ON THE PLAN AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 MANUALS- SECTION 305.1 FBC FG.
  
 8) P402: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 POOL HEATERS AND INDICATE HOW THE AIR WILL BE PROVIDED-
 SEC. 304.1 FBC FG.
  
 9) P402: PROVIDE POOL HEATER GAS VENTING PLANS
 INCLUDING A DIAGRAM SHOWING THE TYPE AND SIZE OF VENT
 PIPING, THE VENT RUN AND TERMINATION LOCATION- SECS.
 305.1, 503.1 FBC FG. PLEASE INCLUDE VENT TERMINATION
 CLEARANCES AND SUBMIT SPECS FOR THE VENT MATERIALS-
 503.8.
  
 10) P104: A VESTIBULE IS REQUIRED FOR THE POOL
 EQUIPMENT ROOM 602 BASED ON SECTION 305.3.2 FBC FG.
 CONNECTION OF A PARKING GARAGE WITH ANY ROOM IN WHICH
 THERE IS A FUEL-FIRED APPLIANCE SHALL BE BY MEANS OF A
 VESTIBULE PROVIDING A TWO-DOORWAY SEPARATION, EXCEPT
 THAT A SINGLE DOOR IS PERMITTED WHERE THE SOURCES OF
 IGNITION IN THE APPLIANCE ARE ELEVATED IN ACCORDANCE
 WITH SECTION 305.3.2.
 11) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 BOTH THE POOL AND THE POOL HEATER- SECTION 105.1 &
 107.2.1 WPB.
  
 12) PLEASE NOTE THE REQUESTED SPECIFICATIONS FOR THE
 POOL HEATERS, AMENITY APPLIANCES, VENT PIPING,
 REGULATORS MAY BE DEFERRED IN ACCORDANCE WITH SEC.
 107.3.4.1 WPB. PLEASE PROVIDE A LITS OF DEFERRED
 SUBMITTALS IF APPLICABLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719