| 2021-12-15 11:53:38 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21091343 |
| | 12/15/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS C-08 & P101: SHOW THE GAS PIPING RUNS FROM |
| | THE MAIN LINE ONSITE TO THE METER AT THE BUILDING, AND |
| | FROM THE METER THROUGH THE BUILDING TO THE RISER |
| | LOCATION- SEC. 107.2.1 WPB, AND SECS. 401.1 & 402.1 FBC |
| | FG. |
| | |
| | 2) P102- P104: SHOW GAS PIPING HORIZONTAL RUNS AND |
| | RISER LOCATIONS- - SEC. 107.2.1 WPB, AND SECS. 401.1 & |
| | 402.1 FBC FG. |
| | |
| | 3) P104, P105, & P402: THE PLANS SHOW BRANCH PIPING |
| | CONTINUATIONS TO APPLIANCES (BBQ GRILLS?) ON THE |
| | AMENITIES DECK. PLEASE REVISE THE RISER DRAWING TO |
| | INCLUDE THE PIPING AND APPLIANCE LOADS AND IDENTIFY THE |
| | APPLIANCES ON THE PLAN VIEW- SEC. 402.1 & 402.2 FBC FG. |
| | |
| | 4) P104 & P402: THE PLAN SHOWS ONE POOL HEATER, THE ISO |
| | SHOWS TWO- PLEASE CORRECT. |
| | |
| | 5) P402: PROVIDE THE MAKE AND MODEL OF THE REGULATORS |
| | AND INDICATE THE OUTPUT PRESSURES- SEC. 410.2 FBC FG. |
| | A) PLEASE SHOW THE REQUIRED TEST TEE FITTINGS UPSTREAM |
| | AND DOWNSTREAM OF THE REGULATORS, AND THE REQUIRED PIPE |
| | UNIONS WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR- |
| | SEC.410.2 (ITEMS 6 & 7). |
| | |
| | 6) P402: PROVIDE VENTING DETAILS FOR THE REGULATORS IF |
| | THE REGULATORS ARE NOT EQUIPPED WITH APPROVED |
| | VENT-LIMITING DEVICES- SEC. 410.2 FBC FG. |
| | |
| | 7) P402: PROVIDE EQUIPMENT SCHEDULES FOR THE POOL |
| | HEATERS AND THE AMENITY APPLIANCES ON THE PLAN AND |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| | MANUALS- SECTION 305.1 FBC FG. |
| | |
| | 8) P402: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | POOL HEATERS AND INDICATE HOW THE AIR WILL BE PROVIDED- |
| | SEC. 304.1 FBC FG. |
| | |
| | 9) P402: PROVIDE POOL HEATER GAS VENTING PLANS |
| | INCLUDING A DIAGRAM SHOWING THE TYPE AND SIZE OF VENT |
| | PIPING, THE VENT RUN AND TERMINATION LOCATION- SECS. |
| | 305.1, 503.1 FBC FG. PLEASE INCLUDE VENT TERMINATION |
| | CLEARANCES AND SUBMIT SPECS FOR THE VENT MATERIALS- |
| | 503.8. |
| | |
| | 10) P104: A VESTIBULE IS REQUIRED FOR THE POOL |
| | EQUIPMENT ROOM 602 BASED ON SECTION 305.3.2 FBC FG. |
| | CONNECTION OF A PARKING GARAGE WITH ANY ROOM IN WHICH |
| | THERE IS A FUEL-FIRED APPLIANCE SHALL BE BY MEANS OF A |
| | VESTIBULE PROVIDING A TWO-DOORWAY SEPARATION, EXCEPT |
| | THAT A SINGLE DOOR IS PERMITTED WHERE THE SOURCES OF |
| | IGNITION IN THE APPLIANCE ARE ELEVATED IN ACCORDANCE |
| | WITH SECTION 305.3.2. |
| | 11) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR |
| | BOTH THE POOL AND THE POOL HEATER- SECTION 105.1 & |
| | 107.2.1 WPB. |
| | |
| | 12) PLEASE NOTE THE REQUESTED SPECIFICATIONS FOR THE |
| | POOL HEATERS, AMENITY APPLIANCES, VENT PIPING, |
| | REGULATORS MAY BE DEFERRED IN ACCORDANCE WITH SEC. |
| | 107.3.4.1 WPB. PLEASE PROVIDE A LITS OF DEFERRED |
| | SUBMITTALS IF APPLICABLE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |