| 2021-11-23 11:29:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET LS AO 101 - EXIT STAIR # 1 DISCHARGERS INTO A |
| | SMALL CORRIDOR OFF OF THE MAIN LOBBY AREA THAT MAY NOT |
| | COMPLY WITH THE CODE |
| | |
| | PER NFPA 101, MEANS OF EGRESS. |
| | |
| | 7.2.3.5 DISCHARGE. |
| | 7.2.3.5.1 EVERY SMOKEPROOF ENCLOSURE SHALL DISCHARGE |
| | INTO A PUBLIC WAY, |
| | INTO A YARD OR COURT HAVING DIRECT ACCESS TO A PUBLIC |
| | WAY, OR INTO AN EXIT |
| | PASSAGEWAY. SUCH EXIT PASSAGEWAYS SHALL BE WITHOUT |
| | OPENINGS, OTHER |
| | THAN THE ENTRANCE TO THE SMOKEPROOF ENCLOSURE AND THE |
| | DOOR OPENING TO |
| | THE OUTSIDE YARD, COURT, OR PUBLIC WAY. THE EXIT |
| | PASSAGEWAY SHALL BE |
| | SEPARATED FROM THE REMAINDER OF THE BUILDING BY A |
| | 2-HOUR FIRE RESISTANCE |
| | RATING. |
| | 7.2.3.5.2 THE SMOKEPROOF ENCLOSURE SHALL BE PERMITTED |
| | TO DISCHARGE |
| | THROUGH INTERIOR BUILDING AREAS, PROVIDED THAT ALL OF |
| | THE FOLLOWING CRITERIA |
| | ARE MET: |
| | (1) THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 9.7. |
| | (2) THE DISCHARGE FROM THE SMOKEPROOF ENCLOSURE SHALL |
| | LEAD TO A FREE |
| | AND UNOBSTRUCTED WAY TO AN EXTERIOR EXIT, AND SUCH WAY |
| | SHALL BE |
| | READILY VISIBLE AND IDENTIFIABLE FROM THE POINT OF |
| | DISCHARGE FROM |
| | THE SMOKEPROOF ENCLOSURE. |
| | (3) NOT MORE THAN 50 PERCENT OF THE REQUIRED NUMBER AND |
| | CAPACITY OF |
| | EXITS COMPRISED OF SMOKEPROOF ENCLOSURES SHALL |
| | DISCHARGE THROUGH |
| | INTERIOR BUILDING AREAS IN ACCORDANCE WITH 7.7.2. |
| | |
| | |
| | PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS COMPLYING |
| | WITH THE CODE OF CORRECT. |
| | |
| | |
| | |
| | |
| | 2) SHEET LS AO 102 - EXIT STAIR # 2 EXITS INTO AN |
| | ELEVATOR LOBBY. |
| | |
| | 7.2.3.5 DISCHARGE. |
| | 7.2.3.5.1 EVERY SMOKEPROOF ENCLOSURE SHALL DISCHARGE |
| | INTO A PUBLIC WAY, |
| | INTO A YARD OR COURT HAVING DIRECT ACCESS TO A PUBLIC |
| | WAY, OR INTO AN EXIT |
| | PASSAGEWAY. SUCH EXIT PASSAGEWAYS SHALL BE WITHOUT |
| | OPENINGS, OTHER |
| | THAN THE ENTRANCE TO THE SMOKEPROOF ENCLOSURE AND THE |
| | DOOR OPENING TO |
| | THE OUTSIDE YARD, COURT, OR PUBLIC WAY. THE EXIT |
| | PASSAGEWAY SHALL BE |
| | SEPARATED FROM THE REMAINDER OF THE BUILDING BY A |
| | 2-HOUR FIRE RESISTANCE |
| | RATING. |
| | 7.2.3.5.2 THE SMOKEPROOF ENCLOSURE SHALL BE PERMITTED |
| | TO DISCHARGE |
| | THROUGH INTERIOR BUILDING AREAS, PROVIDED THAT ALL OF |
| | THE FOLLOWING CRITERIA |
| | ARE MET: |
| | (1) THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 9.7. |
| | (2) THE DISCHARGE FROM THE SMOKEPROOF ENCLOSURE SHALL |
| | LEAD TO A FREE |
| | AND UNOBSTRUCTED WAY TO AN EXTERIOR EXIT, AND SUCH WAY |
| | SHALL BE |
| | READILY VISIBLE AND IDENTIFIABLE FROM THE POINT OF |
| | DISCHARGE FROM |
| | THE SMOKEPROOF ENCLOSURE. |
| | (3) NOT MORE THAN 50 PERCENT OF THE REQUIRED NUMBER AND |
| | CAPACITY OF |
| | EXITS COMPRISED OF SMOKEPROOF ENCLOSURES SHALL |
| | DISCHARGE THROUGH |
| | INTERIOR BUILDING AREAS IN ACCORDANCE WITH 7.7.2. |
| | |
| | |
| | |
| | 2A) SHEET LS AO102 - THE EVEVATOR LOBBY DOORS OF # 2 |
| | ABOVE SWING INTO THE LOBBY AND AGAINST THE PATH OF |
| | TRAVEL. |
| | |
| | 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES |
| | REQUIRED TO BE OF |
| | THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN |
| | THE DIRECTION |
| | OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| | OF 50 OR MORE, |
| | EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| | REQUIRED TO SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY |
| | 7.2.4.3.8.1 |
| | OR 7.2.4.3.8.2. |
| | (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| | TO SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH |
| | CARE OCCUPANCIES, |
| | AS PROVIDED IN CHAPTER 19. |
| | (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| | ENCLOSURE, UNLESS THE |
| | DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT |
| | OPENS DIRECTLY |
| | INTO AN EXIT ENCLOSURE |
| | (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD |
| | CONTENTS AREA |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 3) SHEET LS AO106 - THERE APPEARS TO BE A DOUBLE DOOR |
| | GATE FROM THE POOL AREA THAT OPEN UP OBSTRUCTING THE |
| | EXIT TRAVEL PATH. |
| | |
| | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL |
| | LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF |
| | AN AISLE, A CORRIDOR, |
| | A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF |
| | THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING |
| | BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF |
| | 7.2.1.4.3.2. |
| | 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL |
| | NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED |
| | WIDTH OF AN AISLE, |
| | A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR |
| | LEAF IS EQUIPPED |
| | WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT |
| | REQUIRED BY THE PROVISIONS |
| | OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS |
| | TRAVEL. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH A DETAILED |
| | NARRATIVE AND CODE REFERENCES |
| | |
| | |
| | |
| | |
| | 4) SHEET A1 101 - THE FIRE COMMAND ROOM INDICATES A MIN |
| | WALL DIMENSION OF 10' 31/2"; HOWEVER, THAT IS FROM |
| | CENTER WALL TO CENTER WALL. |
| | |
| | PER NFPA 1 |
| | |
| | 11.9.3 THE EMERGENCY COMMAND CENTER ROOM SHALL BE A |
| | MINIMUM OF 200 FT2 (19 M2) WITH A MINIMUM DIMENSION OF |
| | 10 FT (3050 MM). |
| | |
| | PLEASE CONFIRM/VERIFY THAT IN CLEAR ROOM WIDTH |
| | DIMENSION MEETS THE MINUMUM CODE. |
| | |
| | |
| | |
| | 5) SHEET FP 109 - THERE ARE TWO ROOMS ON THE ROOF |
| | INDICATED AS ELEC 2301 & MECH 2301 THAT DO NOT AAPPEAR |
| | TO HAVE FIRE SPRINKLER PROTECTION. |
| | |
| | PER NFPA 1 & 101 THE BUILDING IS TO BE EQUIPPED WITH |
| | FIRE SPRINKLER PROTECTION. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES AND NARRATIVE OR PROVIDE AN APPLICABLE NOTE |
| | OF ACKNOWLEDGEMENT TO PROVIDE ON SHOP DRAWINGS. |
| | |
| | |
| | |
| | 6) SHEET FP 402 - THERE ARE NO INDICATIONS OF PRV |
| | WITHIN THE STAIRWELLS AT THE FDV'S WERE APPLICABLE. |
| | |
| | PER NFPA 14 |
| | |
| | 7.2.3* MAXIMUM PRESSURE AT HOSE CONNECTIONS. |
| | 7.2.3.1 WHERE THE RESIDUAL PRESSURE AT A 11?2 IN. (40 |
| | MM) OUTLET |
| | ON A HOSE CONNECTION AVAILABLE FOR TRAINED PERSONNEL |
| | USE |
| | EXCEEDS 100 PSI (6.9 BAR), AN APPROVED |
| | PRESSURE-REGULATING |
| | DEVICE SHALL BE PROVIDED TO LIMIT THE RESIDUAL PRESSURE |
| | AT THE |
| | FLOW REQUIRED BY SECTION 7.10 TO 100 PSI (6.9 BAR). |
| | 7.2.3.1.1 PARAGRAPH 7.2.3.1 SHALL NOT APPLY TO THE 11?2 |
| | IN. |
| | (40 MM) OUTLET ON A 21?2 IN. ? 11?2 IN. (65MM? 40 MM) |
| | REDUCER |
| | AS ALLOWED BY 5.3.3.2 AND 7.3.4.1. |
| | 7.2.3.2* WHERE THE STATIC PRESSURE AT A 21?2 IN. (65 |
| | MM) HOSE |
| | CONNECTION EXCEEDS 175 PSI (12.1 BAR), AN APPROVED |
| | PRESSUREREGULATING |
| | DEVICE SHALL BE PROVIDED TO LIMIT STATIC AND RESIDUAL |
| | PRESSURES AT THE OUTLET OF THE HOSE CONNECTION TO 175 |
| | PSI |
| | (12.1 BAR). |
| | 7.2.3.3 THE PRESSURE ON THE INLET SIDE OF THE |
| | PRESSUREREGULATING |
| | DEVICE SHALL NOT EXCEED THE RATED WORKING PRESSURE |
| | OF THE DEVICE. |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE AN APPLICABLE NOTE |
| | OF ACKNOWLEDGEMENT TO PROVIDE ON SHOP DRAWINGS. |
| | |
| | |
| | |
| | 7) SHEET FP 401 - THERE APPEARS TO BE AN INDICATION OF |
| | AN ELECTRIC FIRE PUMP. |
| | |
| | AN ELECTRICAL FIRE PUMP IS REQUIRED TO BE PROVIDED WITH |
| | A RELIABLE BACKUP POWER SOURCE. |
| | |
| | PER NFPA 70 |
| | |
| | 695.3 POWER SOURCE(S) FOR ELECTRIC MOTOR-DRIVEN FIRE |
| | PUMPS. ELECTRIC MOTOR-DRIVEN FIRE PUMPS SHALL HAVE A |
| | RELIABLE |
| | SOURCE OF POWER. |
| | |
| | (B) MULTIPLE SOURCES. IF RELIABLE POWER CANNOT BE |
| | OBTAINED |
| | FROM A SOURCE DESCRIBED IN 695.3(A), POWER SHALL BE |
| | SUPPLIED BY ONE OF THE FOLLOWING: [20:9.3.2] |
| | (1) INDIVIDUAL SOURCES. AN APPROVED COMBINATION OF TWO |
| | OR MORE OF THE SOURCES FROM 695.3(A). |
| | (2) INDIVIDUAL SOURCE AND ON-SITE STANDBY GENERATOR. |
| | AN APPROVED COMBINATION OF ONE OR MORE OF THE SOURCES |
| | IN |
| | 695.3(A) AND AN ON-SITE STANDBY GENERATOR COMPLYING |
| | WITH |
| | 695.3(D). [20:9.3.4] |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE AN APPLICABLE NOTE |
| | OF ACKNOWLEDGEMENT TO CONNECT TO THE ON-SITE GENERATOR |
| | PROPOSED. |
| | |
| | |
| | 8) SHEET C 08 - ALL FIRE LINE LINE UNDERGROUND |
| | (INCLUDING, FDC, DDCV AND PRIVATE FIRE HYDRANTS) SHALL |
| | BE SUBMITTED UNDER SEPARATE PERMIT & SHOP DRAWINGS, |
| | INSTALLED BY A FLORIDA CERTIFIED UNDERGROUND CONTRACTOR |
| | AND INSPECTED PER NFPA 24 |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN |
| | APPLICABLE NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 9) THERE IS NO INDICATION OF THE SMOKE CONTROL RATIONAL |
| | ANALYSIS. |
| | |
| | PLEASE PROVIDE SMOKE CONTROL DETAILS. |
| | |
| | |
| | |
| | 10) SHEET ELECTICAL - THERE IS NO INDICATION TO PROVIDE |
| | FOR EMERGENCY RADIO COMMUNICATIONS. |
| | |
| | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY |
| | RADIO ENHANCEMENT SERVICES. |
| | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT |
| | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL |
| | DETERMINED BY THE AHJ. |
| | NFPA 72, 24.9 TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT |
| | SYSTEMS. |
| | 24.9.1 GENERAL. |
| | 24.9.1.1 NON-INTERFERENCE. NO AMPLIFICATION SYSTEM |
| | CAPABLE |
| | OF OPERATING ON FREQUENCIES OR CAUSING INTERFERENCE ON |
| | FREQUENCIES |
| | ASSIGNED TO THE JURISDICTION BY THE FCC SHALL BE |
| | INSTALLED |
| | WITHOUT PRIOR COORDINATION AND APPROVAL OF THE |
| | AUTHORITY |
| | HAVING JURISDICTION. THE BUILDING MANAGER/OWNER SHALL |
| | SUSPEND AND CORRECT OTHER EQUIPMENT INSTALLATIONS THAT |
| | DEGRADE |
| | THE PERFORMANCE OF THE PUBLIC SAFETY RADIO SYSTEM OR |
| | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM. |
| | 24.9.1.2 APPROVAL AND PERMIT. PLANS SHALL BE SUBMITTED |
| | FOR |
| | APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF |
| | SUCCESSFUL |
| | ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED |
| | FOR THE |
| | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED |
| | BY |
| | THE AUTHORITY HAVING JURISDICTION. |
| | |
| | THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL |
| | STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST |
| | PALM BEACH FIRE DEPARTMENT. TESTING SHALL BE BY AN |
| | ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES |
| | NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE |
| | PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A |
| | BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH |
| | A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP. |
| | PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC |
| | SAFETY RADIO SYSTEMS MANAGER, [email protected], |
| | 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR |
| | DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 11) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 12) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |