| 2021-10-18 08:37:51 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT- 21091332 |
| | 10/18/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION MANUAL FOR THE GAS GRILL- G2408.1 & |
| | G2447.1 FBC RES. THE SUBMITTALS MAY BE DEFERRED AND ON |
| | SITE FOR INSPECTION, HOWEVER PLEASE NOTE THAT TYPICALLY |
| | GAS GRILLS MUST BE INSTALLED WITH CLEARANCES TO |
| | COMBUSTIBLES PER MANUFACTURER'S RECOMMENDATIONS, AND |
| | ARE ALSO NOT ALLOWED TO BE INSTALLED IN ENCLOSED OR |
| | PARTIALLY ENCLOSED STRUCTURES WITH OVERHEAD |
| | CONSTRUCTION UNLESS A HOOD AND EXHAUST VENT SYSTEM IS |
| | INSTALLED. PLEASE REVIEW THE INSTALL MANUAL GUIDELINES |
| | AND PROVIDE MORE INFORMATION- SECTION 107.2.1 WPB. |
| | |
| | 2) GAS RISER: PLEASE CORRECT THE BTU LOAD OF THE |
| | GENERATOR PER THE SPECS SUBMITTED UNDER PERMIT |
| | 21031115. THE SPECS INDICATE 756,000 BTUS. PROVIDE THE |
| | SIZE OF THE PIPE FROM THE METER TO THE 1ST TEE. |
| | ACCORDING TO TABLE 402.4(5) FBC FG A MINIMUM 1-INCH |
| | PIPE IS REQUIRED FOR THE TOTAL 1,200,000 AT 140 FT. |
| | DEVELOPED LENGTH. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |