| Plan Review Notes For Permit 21091324 |
| Permit Number |
21091324 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-10-22 17:04:25 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. SEE TABLE 3A OF THE MULLION PRODUCT APPROVAL. 50" IS | | | CIRCLED. IT APPEARS THAT THE OPENING WIDTH IS 72". | | | PROPOSED INSTALLATION AND COMPLIANCE WITH WIND | | | RESISTANCE IS NOT CLEAR, FBC B 1609. CALCLUATIONS ARE | | | REQUIRED, SEE SHEETS 1 (INSTRUCTIONS) AND 24 | | | (EXAMPLES). EITHER PROVIDE THE CALCULATIONS, | | | CORRELATING WITH CIRCLED DETAILS ON THE PRODUCT | | | APPROVAL, OR PROVIDE ENOUGH INFORMATION FOR ME TO DO | | | THE CALCULATIONS FOR YOU. | | | | | | | | | | | | |
|