| Plan Review Notes For Permit 21091319 |
| Permit Number |
21091319 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-12-08 11:22:29 | ELECTRICAL REVIEW STATUS DENIED. SEE COMMENTS BELOW. | | | | | | | | | | | | I FAILED FOR SIGNATURE THE PLAN E-1 DRAWN BY AN | | | ENGINEER WITH NO S+S 12/1/21 | | | | | | PLAN E-1 DOES NOT HAVE SYMBOL LEGEND. FBC 107.2.1 | | | | | | PLAN DOES NOT INDICATE WHAT IS EXISTING OR NEW? FBC | | | 107.2.1 | | | | | | IS THERE A NEW SUB PANEL? FBC 107.2.1 | | | | | | WHERE IS THE MAIN PANEL LOCATED? FBC 107.2.1 | | | | | | IS THE BOAT LIFT EXISTING? WAS THIS A PERMITTED | | | INSTALLATION? FBC 107.2.1 FBC 105.1 | | | | | | WHICH CIRCUITS ARE GFI PROTECTED? FBC 107.2.1 | | | | | | WHAT IS THE LOAD ON THE 200-AMP PANEL? WHERE IS THIS | | | PANEL LOCATED? THE HOUSE IS LOCATED ON THE WEST SIDE OF | | | FLAGLER AND DOCK ON THE OTHER SIDE OF THE ROAD. FBC | | | 107.2.1 NEC 215 220 | | | | | | WHAT WIRING METHODS ARE USED? FBC 107.2.1 NEC 300 | | | | | | ARE THERE LED STRIP LIGHTS BEING INSTALLED? FBC 107.2.1 | | | | | | WHAT ARE THE SPECIFICATIONS OF THE STRIP LIGHTS? FBC | | | 107.2.1 NEC 110.3B | | | | | | HAND DRAWN PLAN IS NOT CLEARLY UNDERSTANDABLE. PROVIDE | | | CLEAR AND CONCISE PLAN. | | | | | | VALUE LOW FOR AMOUNT OF WORK SHOWN FBC 109.3 PROVIDE | | | ACCURATE VALUE AND CONTRACT SIGNED BY BOTH OWNER AND | | | ELECTRICAL CONTRACTOR QUALIFIER. | | | | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPT. | | | 561-805-6746 | | | |
|