2021-12-08 11:22:29ELECTRICAL REVIEW STATUS DENIED. SEE COMMENTS BELOW.
  
  
  
 I FAILED FOR SIGNATURE THE PLAN E-1 DRAWN BY AN
 ENGINEER WITH NO S+S 12/1/21
  
 PLAN E-1 DOES NOT HAVE SYMBOL LEGEND. FBC 107.2.1
  
 PLAN DOES NOT INDICATE WHAT IS EXISTING OR NEW? FBC
 107.2.1
  
 IS THERE A NEW SUB PANEL? FBC 107.2.1
  
 WHERE IS THE MAIN PANEL LOCATED? FBC 107.2.1
  
 IS THE BOAT LIFT EXISTING? WAS THIS A PERMITTED
 INSTALLATION? FBC 107.2.1 FBC 105.1
  
 WHICH CIRCUITS ARE GFI PROTECTED? FBC 107.2.1
  
 WHAT IS THE LOAD ON THE 200-AMP PANEL? WHERE IS THIS
 PANEL LOCATED? THE HOUSE IS LOCATED ON THE WEST SIDE OF
 FLAGLER AND DOCK ON THE OTHER SIDE OF THE ROAD. FBC
 107.2.1 NEC 215 220
  
 WHAT WIRING METHODS ARE USED? FBC 107.2.1 NEC 300
  
 ARE THERE LED STRIP LIGHTS BEING INSTALLED? FBC 107.2.1
  
 WHAT ARE THE SPECIFICATIONS OF THE STRIP LIGHTS? FBC
 107.2.1 NEC 110.3B
  
 HAND DRAWN PLAN IS NOT CLEARLY UNDERSTANDABLE. PROVIDE
 CLEAR AND CONCISE PLAN.
  
 VALUE LOW FOR AMOUNT OF WORK SHOWN FBC 109.3 PROVIDE
 ACCURATE VALUE AND CONTRACT SIGNED BY BOTH OWNER AND
 ELECTRICAL CONTRACTOR QUALIFIER.
  
  