Plan Review Notes
Plan Review Notes For Permit 21091315
Permit Number 21091315
Review Stop P
Sequence Number 1
Notes
Date Text
2021-10-28 08:15:53PLUMBING REVIEW BY JERALD SMITH
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21091315 360 S ROSEMARY AVE 1440
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
 1.RE: A0.2 ADA; PER WPB FBC 107.2.1, TO SHOW COMPLIANCE
 WITH FBC ACC CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND
 ELEVATION DETAILS FOR NEW TOILET ROOM INDICATING THE
 FOLLOWING:
 ?A) RE: MOUNTING HEIGHT DETAIL FOR THE TOILET ROOM; THE
 WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2. NOT 18 INCHES MINIMUM AS INDICATED.
 ?B) RE: MOUNTING HEIGHT DETAIL FOR THE TOILET ROOM;
 REMOVE THE 6 INCH DIMENSION BETWEEN THE SIDE WALL AND
 THE AND THE REAR WALL GRAB BAR TO ALLOW FOR THE
 FLUCTUATION OF THE 16-18 INCHES CENTERLINE OF THE WATER
 CLOSET.
 ?C) FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6.
 NOTE ON DETAIL THE CONTROL TO THE OPEN SIDE AWAY FROM
 WALL
 ?D) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 PER WPB FBC 107.2.1, INDICATE MOUNTING HEIGHT OF
 DISPENSER.
 ?E) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 ?F) RE: TYPICAL ELEVATIONS DETAIL FOR THE TOILET ROOM
 REAR WALL; MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 603.3.
  
 2.RE: P0.1 CONCERNING MATERIAL SPECIFICATIONS FOR WATER
 DISTRIBUTION AND FOR SANITARY WASTE AND VENTS. WATER
 CALLS FOR TYPE L COPPER OR SDR 11 CPVC. SANITARY WASTE
 AND VENTS CALL FOR WASTE ABOVE THE SLAB TO BE TO BE
 CAST IRON; BELOW SLAB, VENTS AND SINK P-TRAP MAY BE
 PVC. NO PVC ALLOWED THROUGH FIRE RATED ASSEMBLIES. P4.1
 SHOWS A FIRE RATED ASSEMBLY THROUGH A RATED FLOOR, THE
 FLOOR BEING CORRUGATED METAL WITH LIGHTWEIGHT CONCRETE.
 ADDITIONALLY, A4.1 PROVIDES UL ASSEMBLIES INCLUDING
 THROUGH THE FLOOR ASSEMBLIES FOR BOTH PLASTIC AND METAL
 PIPES.
 OBSERVATION: IT IS ADVISABLE TO CHOOSE A CONSISTENT
 MATERIAL SPECIFICATION FOR EACH SYSTEM TO AVOID
 CONFUSION.
 PER WPB FBC 107.2.1, PROVIDE THE FOLLOWING
 CLARIFICATIONS:
 ?A) WHICH UL PENETRATION DETAILS SHALL BE USED
 ?B) IS PVC PIPING TO BE ALLOWED IN THROUGH FLOOR RATED
 ASSEMBLIES? PLEASE CONFIRM THAT METAL PIPE THROUGH A
 RATED FLOOR ASSEMBLY WHEN THE UNDERSLAB PIPING AND
 ABOVE GROUND VENTS WILL PROTECT THE FLOOR
  
 3.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR
 VALVES; ALL COMPONENTS IN THE POTABLE WATER SYSTEM
 SHALL COMPLY WITH FBC PL 605.2.1 FOR LEAD CONTENT.
  
 4. PER WPB FBC 107.2.1, PROVIDE ON THE PIPE HANGER
 DETAIL ANCHOR METHOD AND A NOTE STATING, "HORIZONTAL
 PIPE SHALL BE SUPPORTED IN ACCORDANCE WITH FBC PL TABLE
 308.5."
  
 5.RE: P4.1/DETAIL 5; TYPICAL POINT OF USE HEATER
 (EWH-1) INSTALLATION. PER WPB FBC 107.2.1 PROVIDE THE
 FOLLOWING;
 ?A) PER FBC PL 602.1, PROVIDE A TEE BETWEEN THE POINT
 THE COLD WATER OUTLET PROTRUDES FROM THE WALL PLACED
 BETWEEN THE LAVATORY SHUTOFF VALVE AND THE WATER HEATER
 SERVICE VALVE
  
 6. FOR THE HEATER (EWH-2) SERVICING MORE THAN ONE
 FIXTURE (BREAKROOM SINK WITH DISHWASHER) PROVIDE A
 SECOND DETAIL SHOW A TEE BETWEEN THE POINT THE COLD
 WATER OUTLET PROTRUDES FROM THE WALL PLACED BETWEEN THE
 LAVATORY SHUTOFF VALVE AND THE WATER HEATER SERVICE
 VALVE AND A TEE IN HOT WATER PIPING WITH SHUTOFF VALVE
 TO EACH FIXTURE/APPLIANCE.
 ?A) ADD NOTE ON P2.1 ADDRESSING THE SAME. NOTE 3
 REFERRING TO P4.1/DETAIL 5 ONLY APPLIES TO BATHROOM
 HEATERS.
  
 7. PER WPB FBC 107.2.1, PROVIDE NOTE AT WATER HAMMER
 ARRESTER SCHEDULE STATING PER FLORIDA PLUMBING CODE
 604.9, PROVIDE WATER HAMMER ARRESTER AT DISHWASHER AND
 ICEMAKER
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS