| Plan Review Notes For Permit 21091315 |
| Permit Number |
21091315 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-10-20 14:30:27 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21091315 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M3.1: THE VAV TERMINAL BOX SCHEDULE LISTS THE | | | DESIGN COOLING AIRFLOW CFM?S FOR VAV 14-2 IS 1600 CFM. | | | SHEET M2.1: AFTER ADDING THE CFM?S AT EACH SUPPLY | | | GRILLE THE TOTAL AIRFLOW IS 1825 CFM?S. PLEASE REVIEW. | | | FBC 107.2.1 | | | | | | 2) SHEET M3.1: PLEASE SHOW THE VAV 14-4 IN THE VAV | | | TERMINAL BOX SCHEDULE. FBC 107.2.1 | | | | | | 3) PLEASE PROVIDE A DETAIL SHOWING THE RETURN AIR PATH | | | FROM THE TENANT SPACE BACK TO THE MECHANICAL ROOM. FBC | | | M 601.6 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|