2021-10-20 14:30:271ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21091315
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M3.1: THE VAV TERMINAL BOX SCHEDULE LISTS THE
 DESIGN COOLING AIRFLOW CFM?S FOR VAV 14-2 IS 1600 CFM.
 SHEET M2.1: AFTER ADDING THE CFM?S AT EACH SUPPLY
 GRILLE THE TOTAL AIRFLOW IS 1825 CFM?S. PLEASE REVIEW.
 FBC 107.2.1
  
 2) SHEET M3.1: PLEASE SHOW THE VAV 14-4 IN THE VAV
 TERMINAL BOX SCHEDULE. FBC 107.2.1
  
 3) PLEASE PROVIDE A DETAIL SHOWING THE RETURN AIR PATH
 FROM THE TENANT SPACE BACK TO THE MECHANICAL ROOM. FBC
 M 601.6
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  