| Plan Review Notes For Permit 21091315 |
| Permit Number |
21091315 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-03 13:00:32 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E2.1 | | | | | | NO OVERCURRENT PROTECTION SIZE SHOWN FOR THE PRIMARY OF | | | THE TRANSFORMER. 30KVA 450.3(B)(1), 240.4 125% | | | | | | WIRE SIZE ON THE PRIMARY OF THE TRANSFORMER SHOULD BE | | | #6 UNLESS YOU CAN SHOW CALCULATION 215.2(A)(1)(A), | | | 110.14(C)(1)(A)(2), 310.15(B)(16) 125% | | | | | | AIC RATING OF PANELS ? PLEASE SHOW CALCULATION. 110.9, | | | 110.10, 110.24 |
|