2021-11-03 13:00:32ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E2.1
  
 NO OVERCURRENT PROTECTION SIZE SHOWN FOR THE PRIMARY OF
 THE TRANSFORMER. 30KVA 450.3(B)(1), 240.4 125%
  
 WIRE SIZE ON THE PRIMARY OF THE TRANSFORMER SHOULD BE
 #6 UNLESS YOU CAN SHOW CALCULATION 215.2(A)(1)(A),
 110.14(C)(1)(A)(2), 310.15(B)(16) 125%
  
 AIC RATING OF PANELS ? PLEASE SHOW CALCULATION. 110.9,
 110.10, 110.24