| Plan Review Notes For Permit 21091315 |
| Permit Number |
21091315 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-10-21 11:02:12 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE BATHROOM DOORS AS SHOWN ON THE FLOOR PLAN DO NOT | | | COMPLY WITH FBC ACCESSIBILITY 603.2.3 EXCEPTION 2. THE | | | ARC OF THE DOOR SWING DOES NOT CLEAR OF THE 30" X 48" | | | CLEAR FLOOR SPACE REQUIRED BY SECTION 305.3. | | | | | | 2) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION DETAILS FOR THE TEKNION OPTOS FURNITURE | | | SYSTEM. FBC 107.2.1 | | | | | | 3) SUBMIT DETAILS FOR THE TEKNION OPTOS SLIDING DOORS | | | THAT SHOW THEY WILL COMPLY WITH FBC ACCESSIBILITY 404. | | | | | | 4) ON SHEET A1.1, THERE IS AN ID TAG FOR NOTE #8. IT | | | APPEARS THAT THIS TAG SHOULD BE FOR NOTE #15. PLEASE | | | CLARIFY. FBC 107.2.1 |
|