| Plan Review Notes For Permit 21091314 |
| Permit Number |
21091314 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-10-25 10:14:17 | RESIDENTIAL (R3) RE-ROOF, THIRD BUILDING REVIEW | | | COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #21091314 | | | | | | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK | | | SHALL COMPLY WITH THE MATERIALS AND METHODS | | | REQUIREMENTS IN THE FLORIDA BUILDING CODE. | | | | | | | | | 1- FLAT ROOF PRODUCT APPROVAL FL14672-R6 SUBMITTED: | | | SELECTED ASSEMBLY W-46 IS A FULLY BONDED ROOF COVER | | | ASSEMBLY. THE MAXIMUM DESIGN PRESSURES FOR THIS | | | ASSEMBLY IS -75.0PSF. THIS ASSEMBLY DOESN'T MEET THE | | | DESIGN PRESSURES FOR ALL ROOF ZONES. ACCORDING TO NOTE | | | # 6 PM PAGE 1 OF 7 OF PRODUCT APPROVAL SUBMITTED, THIS | | | ASSEMBLY CAN NOT BE USED BECAUSE IT DOESN'T ALLOW | | | RATIONAL ANALYSIS. NEED TO SELECT ANOTHER ASSEMBLY THAT | | | MEETS THE DESIGN PRESSURES OF ALL ROOF ZONES. | | | NOTE: ANY ONE OF ASSEMBLIES W-48, W-49 AND W-50 WILL | | | WORK. | | | SEC. R301.2.1 FBC-RESIDENTIAL. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|