| 2022-05-11 09:05:02 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21091249 |
| | 5/11/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST |
| | REVIEW COPIED BELOW WERE NOT ADDRESSED. NO CORRECTED |
| | PLANS OR COMMENT RESPONSES WERE UPLOADED FOR REVIEW. |
| | |
| | 1) SHEET MP-1 & MP-2 STORM DRAIN SUMP PUMP SYSTEM: A) |
| | PROVIDE AN EQUIPMENT SCHEDULE FOR THE PUMP, THE PUMP |
| | CURVE AND SIZING CALCULATIONS- SEC. 1113.1.1 FBC P. B) |
| | PROVIDE A DIMENSIONED DETAIL SHOWING THE SUMP PIT, SUMP |
| | PUMP, AND DISCHARGE PIPING RUN. PLEASE INCLUDE THE |
| | LOCATIONS OF THE REQUIRED GATE AND CHECK VALVES- |
| | SEC.1113.2- 1113.1.4 FBC P. C) SUBMIT SHEET B1-424 |
| | WHICH IS REFERENCED ON THE DRAWING BUT NOT INCLUDED IN |
| | THE PLAN SET- SEC. 107.2.1 WPB. |
| | |
| | 2) MP-1: PROVIDE EQUIPMENT SCHEDULES FOR THE NEW WATER |
| | HEATERS AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SEC. |
| | 502.1 FBC P. |
| | |
| | 3) MP-4 & MP-8: HOT WATER SHALL BE DELIVERED FROM THE |
| | SERVICE SINK, HOWEVER NO HW LINE HAS BEEN PROVIDED- |
| | SEC. 607.1 FBC P. |
| | |
| | 4) MP-4 & MP-8: THE EWH SHALL NOT SERVE AS THE |
| | TEMPERATURE LIMITING MEANS FOR MAXIMUM HOT WATER |
| | DELIVERY TEMPERATURE AT THE P3 & P4 SINKS- SEC 607.1.1 |
| | FBC P. PLEASE PROVIDE A THERMOSTATIC MIXING VALVE. A) |
| | COLD OR TEMPERED WATER SHALL BE DELIVERED FROM THE |
| | LAVATORY SINK- P2- SEC. 419.5 FBC P. IF USING A MIXING |
| | VALVE FOR THAT PURPOSE, THE DEVICE SHALL CONFORM TO |
| | ASSE 1070- SEC. 607.1.2 FBC P. |
| | |
| | 5) MP-4: PROVIDE A BACKWATER VALVE DETAIL, AND INDICATE |
| | HOW ACCESS TO THE VALVE WILL BE PROVIDED- SEC. 714.1- |
| | 714.3 FBC P. |
| | |
| | 6) MP-1 & MP-8: ADA WATER CLOSET AND SINK ARE SPECIFIED |
| | FOR THE NEW TOILET ROOM. THERE ARE NO ARCHITECTURAL |
| | DRAWINGS INCLUDED IN THE PLAN SETS AND NO INTERIOR |
| | ELEVATION DETAILS. IF THE INTENTION IS TO DESIGN THE |
| | TOILET ROOM AS ACCESSIBLE, PLEASE PROVIDE THE FOLLOWING |
| | LIST OF FBC ACC COMPLIANCE DETAILS: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSET- SEC. 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORY- SEC. 606.2. |
| | C) TURNING SPACE DIAMETER- SEC. 304.3. |
| | D) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALLS- |
| | SEC. 604.2. |
| | E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED |
| | FLOOR- SEC. 604.4. |
| | F) HEIGHT OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| | FROM THE FINISHED FLOOR- SEC. 606.3. |
| | G) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOOR TO THE |
| | REFLECTIVE SURFACES SEC. 603.3 |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. |
| | I) LOCATION OF THE WATER CLOSET FLUSH CONTROLS- SEC. |
| | 604.6. |
| | J) CENTERLINE OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SEC. |
| | 606.2. |
| | |
| | 7) MP-8: BASED ON SEC. 212.3 FBC ACC, THE P-3 SINK |
| | SHALL BE ACCESSIBLE. PLEASE CLARIFY THE USE OF THE SINK |
| | AND PROVIDE ENLARGED DETAILS IN ACCORDANCE WITH SECTION |
| | 606.2 FBC ACC. |
| | |
| | 8) MP-8: PLEASE PROVIDE PLUMBING FIXTURE CALCULATIONS |
| | IN COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A |
| | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDE NUMBER |
| | OF PLUMBING FIXTURES. A) PLEASE LABEL THE TOILET ROOM |
| | AS EITHER MALE, FEMALE, OR FAMILY- SECS. 403.2 & 403.4 |
| | FBC P. |
| | |
| | 9) B1-62: PROVIDE HANGER SPACINGS FOR EACH OF THE DRAIN |
| | PIPE RUNS- TABLE 308.5 FBC P. |
| | |
| | 10) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB |
| | WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE |
| | AROUND THE PIPING. PROVIDE A ULL TESTED AND APPROVED |
| | FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1 |
| | FBC P AND SECTION 714.4.1.2 FBC B. |
| | |
| | 11) DEFERRED SUBMITTALS: MANUFACTURER'S SPECIFICATIONS, |
| | PRODUCT DATA SHEETS FOR ALL PLUMBING FIXTURES, |
| | APPLIANCES AND DEVICES SHALL BE UPLOADED FOR REVIEW OR |
| | SHOULD BE DESIGNATED AS DEFERRED SUBMITTALS- SEC. |
| | 107.3.4.1 WPB. ALL ITEMS NOT SUBMITTED FOR REVIEW SHALL |
| | BE LISTED AS DEFERRED SUBMITTALS INCLUDING BUT NOT |
| | LIMITED TO: |
| | WATER HEATERS |
| | PLUMBING FIXTURES |
| | SUMP PUMPS AND PITS |
| | MIXING VALVES |
| | BACKWATER VALVE |
| | FIRESTOPPING |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |