Plan Review Notes
Plan Review Notes For Permit 21091249
Permit Number 21091249
Review Stop P
Sequence Number 1
Notes
Date Text
2022-03-14 13:27:091ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21091249
 3/14/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET MP-1 & MP-2 STORM DRAIN SUMP PUMP SYSTEM: A)
 PROVIDE AN EQUIPMENT SCHEDULE FOR THE PUMP, THE PUMP
 CURVE AND SIZING CALCULATIONS- SEC. 1113.1.1 FBC P. B)
 PROVIDE A DIMENSIONED DETAIL SHOWING THE SUMP PIT, SUMP
 PUMP, AND DISCHARGE PIPING RUN. PLEASE INCLUDE THE
 LOCATIONS OF THE REQUIRED GATE AND CHECK VALVES-
 SEC.1113.2- 1113.1.4 FBC P. C) SUBMIT SHEET B1-424
 WHICH IS REFERENCED ON THE DRAWING BUT NOT INCLUDED IN
 THE PLAN SET- SEC. 107.2.1 WPB.
  
 2) MP-1: PROVIDE EQUIPMENT SCHEDULES FOR THE NEW WATER
 HEATERS AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SEC.
 502.1 FBC P.
  
 3) MP-4 & MP-8: HOT WATER SHALL BE DELIVERED FROM THE
 SERVICE SINK, HOWEVER NO HW LINE HAS BEEN PROVIDED-
 SEC. 607.1 FBC P.
  
 4) MP-4 & MP-8: THE EWH SHALL NOT SERVE AS THE
 TEMPERATURE LIMITING MEANS FOR MAXIMUM HOT WATER
 DELIVERY TEMPERATURE AT THE P3 & P4 SINKS- SEC 607.1.1
 FBC P. PLEASE PROVIDE A THERMOSTATIC MIXING VALVE. A)
 COLD OR TEMPERED WATER SHALL BE DELIVERED FROM THE
 LAVATORY SINK- P2- SEC. 419.5 FBC P. IF USING A MIXING
 VALVE FOR THAT PURPOSE, THE DEVICE SHALL CONFORM TO
 ASSE 1070- SEC. 607.1.2 FBC P.
  
 5) MP-4: PROVIDE A BACKWATER VALVE DETAIL, AND INDICATE
 HOW ACCESS TO THE VALVE WILL BE PROVIDED- SEC. 714.1-
 714.3 FBC P.
  
 6) MP-1 & MP-8: ADA WATER CLOSET AND SINK ARE SPECIFIED
 FOR THE NEW TOILET ROOM. THERE ARE NO ARCHITECTURAL
 DRAWINGS INCLUDED IN THE PLAN SETS AND NO INTERIOR
 ELEVATION DETAILS. IF THE INTENTION IS TO DESIGN THE
 TOILET ROOM AS ACCESSIBLE, PLEASE PROVIDE THE FOLLOWING
 LIST OF FBC ACC COMPLIANCE DETAILS:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SEC. 606.2.
 C) TURNING SPACE DIAMETER- SEC. 304.3.
 D) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALLS-
 SEC. 604.2.
 E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- SEC. 604.4.
 F) HEIGHT OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SEC. 606.3.
 G) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACES SEC. 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROLS- SEC.
 604.6.
 J) CENTERLINE OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SEC.
 606.2.
  
 7) MP-8: BASED ON SEC. 212.3 FBC ACC, THE P-3 SINK
 SHALL BE ACCESSIBLE. PLEASE CLARIFY THE USE OF THE SINK
 AND PROVIDE ENLARGED DETAILS IN ACCORDANCE WITH SECTION
 606.2 FBC ACC.
  
 8) MP-8: PLEASE PROVIDE PLUMBING FIXTURE CALCULATIONS
 IN COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDE NUMBER
 OF PLUMBING FIXTURES. A) PLEASE LABEL THE TOILET ROOM
 AS EITHER MALE, FEMALE, OR FAMILY- SECS. 403.2 & 403.4
 FBC P.
  
 9) B1-62: PROVIDE HANGER SPACINGS FOR EACH OF THE DRAIN
 PIPE RUNS- TABLE 308.5 FBC P.
  
 10) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A ULL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1
 FBC P AND SECTION 714.4.1.2 FBC B.
  
 11) DEFERRED SUBMITTALS: MANUFACTURER'S SPECIFICATIONS,
 PRODUCT DATA SHEETS FOR ALL PLUMBING FIXTURES,
 APPLIANCES AND DEVICES SHALL BE UPLOADED FOR REVIEW OR
 SHOULD BE DESIGNATED AS DEFERRED SUBMITTALS- SEC.
 107.3.4.1 WPB. ALL ITEMS NOT SUBMITTED FOR REVIEW SHALL
 BE LISTED AS DEFERRED SUBMITTALS INCLUDING BUT NOT
 LIMITED TO:
 WATER HEATERS
 PLUMBING FIXTURES
 SUMP PUMPS AND PITS
 MIXING VALVES
 BACKWATER VALVE
 FIRESTOPPING
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  