Plan Review Notes
Plan Review Notes For Permit 21091242
Permit Number 21091242
Review Stop M
Sequence Number 1
Notes
Date Text
2021-10-06 16:05:361ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21091242
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RETURN AIR CANNOT COME FROM THE CLOSET. FBC M
 601.5 ? 7
 7. RETURN AIR SHALL NOT BE TAKEN FROM A CLOSET, TOILET
 ROOM,
 KITCHEN, GARAGE, BOILER ROOM, FURNACE ROOM OR
 UNCONDITIONED
 ATTIC.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved