Plan Review Notes
Plan Review Notes For Permit 21091235
Permit Number 21091235
Review Stop B
Sequence Number 1
Notes
Date Text
2021-10-15 12:12:531ST REVIEW FBC-2020 BUILDING
 PERMIT- 21091235
 10/15/2021
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A LEGIBLE ROOF PLAN SHEET R1.04 PLAN
 SHEET THAT INDICATES THE TYPES OF ROOFING TO BE
 INSTALLED, THE SQUARE FOOT AREAS OF THE ROOFING, AND
 THE MEAN ROOF HEIGHTS. A COMPLETE REVIEW OF THE PROJECT
 CANNOT BE COMPLETED WITHOUT THIS INFORMATION- SECTION
 1507.1 FBC B. PLEASE NOTE THE PLAN MUST BEAR THE
 SIGNATURE OF THE DESIGNER OF RECORD. IF THE DESIGNER IS
 AN ARCHITECT OR ENGINEER, THE PLAN SHALL BE DIGITALLY
 SIGNED AND SEALED IN ACCORDANCE WITH FL. STATUTES
 471.025, 481.221, AND SECTIONS 61G1-16.005 &
 61G15-23.005 FLORIDA ADMINISTRATIVE CODE.
  
 2) MIAMI-DADE NOA 11-0913.08 GAF DECK-ARMOUR
 UNDERLAYMENT IS NOT VALID FOR USE WITH THE GAF SHINGLES
 WITHOUT ENGINEEREED UPLIFT CALCULATIONS AND FASTENING
 DETAILS. REFER TO LIMITATION #8 ON PAGE 4: DECK-ARMOUR
 MAY BE USED WITH ANY APPROVED ROOF COVERING NOTICE OF
 ACCEPTANCE LISTING DECK-ARMOUR AS A COMPONENT PART OF
 AN ASSEMBLY IN THE NOTICE OF ACCEPTANCE. IF DECK-ARMOUR
 IS NOT LISTED, A REQUEST MAY BE MADE TO THE AUTHORITY
 HAVING JURISDICTION (AHJ) OR THE MIAMI-DADE COUNTY
 PRODUCT CONTROL DEPARTMENT FOR APPROVAL PROVIDED THAT
 APPROPRIATE DOCUMENTATION IS PROVIDED TO DETAIL
 COMPATIBILITY OF THE PRODUCTS, WIND UPLIFT RESISTANCE,
 AND FIRE TESTING RESULTS.
  
 3) PLEASE SUBMIT A CURRENT FL. PRODUCT APPROVAL FOR THE
 FLAT ROOF SYSTEM THAT IS A COMPLETE SUBMITTAL INCLUDING
 THE COVER SHEETS, AND EVALUATION REPORT- RULE 9N-3 FAC.
 THE CURRENT FL16732-R19 SUBMITTAL IS INCOMPLETE AND HAS
 BEEN SUPERSEDED BY R20. PLEASE REVIEW THE LIMITATIONS
 OF USE FOR THE PRODUCT- ENGINEERED CALCULATIONS AND
 ENHANCED FASTENING FOR ZONES 2 & 3 MAY BE REQUIRED.
 PLEASE NOTE THE SUBMITTED DESIGN PRESSURE CALCULATIONS
 ARE REFERENCING THE EXPIRED PRODUCT APPROVAL. PLEASE
 SUBMIT REVISED AND UPDATED CALCULATIONS WITH THE
 UPDATED PRODUCT APPROVAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  