Plan Review Notes For Permit 21091234
Permit Number 21091234
Review Stop B
Sequence Number 2
Notes
Date Text
2021-11-17 10:04:15PLAN REVIEW BUILDING ACCESSORY STRUCTURES
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE COMPLETE SET OF CONSTRUCTION DRAWINGS. SEE
 BELOW:
  
 CHECKLIST FOR SITE BUILT SHEDS - RESIDENTIAL
  
 EVERY STRUCTURE SUBJECT TO WIND LOADS SHALL BE DESIGNED
 PER FBC RES CHPT 3 SECTION R301 OR FBC CHPT 16/ASCE 7.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 2. PROVIDE A SITE PLAN. SUBMITTED OK SUBMITTED
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE
 SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE AND INCLUDED BOUNDARY LINE SURVEY.
  
 3. PROVIDE THE FOLLOWING PLANS
  
 2A) PROVIDE A FOUNDATION PLAN FOOTINGS/SLAB ON
 GRADE/REINFORCING/TIE DOWNS
 2B) PROVIDE BUILDING PLANS WITH REQUIRED DIMENSIONS
 2C) PROVIDE A FLOOR PLAN WITH FLOOR TO FOUNDATION
 CONNECTION DETAIL
 2D) PROVIDE A WALL PLAN WITH WALL TO FLOOR CONNECTION
 DETAIL
 2E) PROVIDE A ROOF FRAMING PLAN WITH ROOF TO WALL
 CONNECTION DETAIL
 2F) PROVIDE A WINDOW AND/OR DOOR SCHEDULE WITH ROUGH
 OPENINGS AND DESIGN WIND LOADS IF APPLICABLE.
 2G) PROVIDE PRODUCT APPROVALS FOR ALL ROOFING, WINDOWS,
 DOORS AND TIE DOWNS. >720 SQ. FT. SEE R301.2.1.2 OK
 SUBMITTED
  
 R301.2.1.2 PROTECTION OF OPENINGS.
 STRUCTURES THAT ARE NOT DESIGNED FOR HUMAN HABITATION
 AND THAT HAVE A FLOOR AREA OF 720 SQUARE FEET (67 M2)
 OR LESS ARE NOT REQUIRED TO COMPLY WITH THE MANDATORY
 WIND-BORNE DEBRIS IMPACT STANDARD OF THIS CODE
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 WHEN RE-SUBMITTING, PLEASE UPLOAD YOUR DOCUMENTS TO
 PROJECT DOX.
 DO NOT E-MAIL DOCUMENTS TO THE PLANS EXAMINER.
  
  