Plan Review Notes
Plan Review Notes For Permit 21091210
Permit Number 21091210
Review Stop P
Sequence Number 2
Notes
Date Text
2021-12-29 16:09:371ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21091210
 10/28/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN
 CAP LETTERS FOR FURTHER CLARIFICATIONS.
  
 3) FAILED ITEMS A & B. A4 DETAIL 7 RESTROOM PLAN:
 PLEASE CORRECT THE DETAIL ACCORDING TO THE FOLLOWING
 FBC ACC CODE SECTIONS AND NOTE THAT EXACT DETAILS AND
 DIMENSIONS ARE REQUIRED:
 A) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE WATER CLOSETS- SECTION 604.3. THE PLAN SHOWS 30X48
 INCH CLEAR FLOOR SPACES AT THE WATER CLOSETS- 60X56
 SPACES REQUIRED.
 B) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE LAVATORIES- SECTION 606.2. THE 30X48 INCH CLEAR
 FLOOR SPACE FORWARD APPROACH DIAGRAMS SHALL EXTEND INTO
 THE KNEE AND TOE CLEARANCE AREAS.
  
 4) FAILED ITEMS B, E, F, G, & H. A4 DETAIL 6
 ELEVATIONS: PLEASE CORRECT THE DETAIL ACCORDING TO THE
 FOLLOWING FBC ACC CODE SECTIONS AND NOTE THAT EXACT
 DETAILS AND DIMENSIONS ARE REQUIRED:
 B) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. GRAB BARS HEIGHTS APPEAR TO
 BE SHOWN TO THE CENTERS OF THE GRAB BARS AND NOT TO THE
 TOPS OF THE GRIPPING SURFACES- SEC. 609.4.
 E) FAILED. CENTERLINES OF THE TOILET PAPER DISPENSERS
 MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SECTION
 AND FIGURE 604.7. THE DISPENSERS SHALL BE 7 INCHES
 MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE WATER
 CLOSETS MEASURED TO THE CENTERLINES OF THE DISPENSERS.
 F) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 SECTION 606.2, AND FIGURES 306.2 & 306.3. PLEASE
 PROVIDE THE CLEARANCES PER THE LISTED CODE SECTIONS AND
 FIGURES.
 G) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE ACCESSIBLE DRINKING FOUNTAIN- SECTION 602.2 & 305.
 FIGURES 306.2 & 306.3. THE 30X48 INCH CLEAR FLOOR SPACE
 FORWARD APPROACH DIAGRAM SHALL EXTEND INTO THE KNEE AND
 TOE CLEARANCE AREAS.
 H) FAILED. KNEE AND TOE CLEARANCES FOR THE DRINKING
 FOUNTAIN- SECTION 606.2 & FIGURES 306.2 & 306.3. PLEASE
 PROVIDE THE CLEARANCES PER THE LISTED CODE SECTIONS AND
 FIGURES.
  
 6) FAILED. P1: PROVIDE A COMPLETE EQUIPMENT SCHEDULE
 FOR THE NEW WATER HEATER THAT INDICATES THE MAKE AND
 MODEL, GALLON SIZE AND EFFICIENCY RATING- TABLE C404.2
 FBC EC. BASED ON THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS THE BOSCH ES4 WATER HEATER SPECIFIED IS A
 POINT OF USE WATER HEATER DESIGNED TO BE INSTALLED
 UNDER A SINK. THE PLAN SHOWS THE HEATER BEING USED AS A
 CENTRAL HOT WATER SOURCE.
  
 13) FAILED. P1: THE 1/2-INCH HOT WATER SUPPLY PIPING TO
 THE PUBLIC LAVATORIES IS EXCEEDING THE 2 FT. MAXIMUM
 ALLOWABLE LENGTHS PER TABLE C404.5.1 FBC EC. THE 3M
 HEAT TRACE SYSTEM SPECIFICATION INDICATE THE CABLES
 MUST BE POWERED BY A 30 AMP GROUND FAULT CIRCUIT
 HOWEVER THE ELECTRICAL PLAN DOES NOT SHOW THE CABLES ON
 THE POWER.
  
 NEW COMMENT.
  
 1) SHEET A4: SHOW THE HEIGHTS OF THE MIRRORS FROM THE
 FINISHED FLOORS TO THE REFLECTIVE SURFACES- SECTION
 603.3 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  