| 2021-12-29 16:09:37 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21091210 |
| | 10/28/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| | CAP LETTERS FOR FURTHER CLARIFICATIONS. |
| | |
| | 3) FAILED ITEMS A & B. A4 DETAIL 7 RESTROOM PLAN: |
| | PLEASE CORRECT THE DETAIL ACCORDING TO THE FOLLOWING |
| | FBC ACC CODE SECTIONS AND NOTE THAT EXACT DETAILS AND |
| | DIMENSIONS ARE REQUIRED: |
| | A) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | THE WATER CLOSETS- SECTION 604.3. THE PLAN SHOWS 30X48 |
| | INCH CLEAR FLOOR SPACES AT THE WATER CLOSETS- 60X56 |
| | SPACES REQUIRED. |
| | B) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS |
| | FOR THE LAVATORIES- SECTION 606.2. THE 30X48 INCH CLEAR |
| | FLOOR SPACE FORWARD APPROACH DIAGRAMS SHALL EXTEND INTO |
| | THE KNEE AND TOE CLEARANCE AREAS. |
| | |
| | 4) FAILED ITEMS B, E, F, G, & H. A4 DETAIL 6 |
| | ELEVATIONS: PLEASE CORRECT THE DETAIL ACCORDING TO THE |
| | FOLLOWING FBC ACC CODE SECTIONS AND NOTE THAT EXACT |
| | DETAILS AND DIMENSIONS ARE REQUIRED: |
| | B) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| | GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. GRAB BARS HEIGHTS APPEAR TO |
| | BE SHOWN TO THE CENTERS OF THE GRAB BARS AND NOT TO THE |
| | TOPS OF THE GRIPPING SURFACES- SEC. 609.4. |
| | E) FAILED. CENTERLINES OF THE TOILET PAPER DISPENSERS |
| | MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SECTION |
| | AND FIGURE 604.7. THE DISPENSERS SHALL BE 7 INCHES |
| | MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE WATER |
| | CLOSETS MEASURED TO THE CENTERLINES OF THE DISPENSERS. |
| | F) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES- |
| | SECTION 606.2, AND FIGURES 306.2 & 306.3. PLEASE |
| | PROVIDE THE CLEARANCES PER THE LISTED CODE SECTIONS AND |
| | FIGURES. |
| | G) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | THE ACCESSIBLE DRINKING FOUNTAIN- SECTION 602.2 & 305. |
| | FIGURES 306.2 & 306.3. THE 30X48 INCH CLEAR FLOOR SPACE |
| | FORWARD APPROACH DIAGRAM SHALL EXTEND INTO THE KNEE AND |
| | TOE CLEARANCE AREAS. |
| | H) FAILED. KNEE AND TOE CLEARANCES FOR THE DRINKING |
| | FOUNTAIN- SECTION 606.2 & FIGURES 306.2 & 306.3. PLEASE |
| | PROVIDE THE CLEARANCES PER THE LISTED CODE SECTIONS AND |
| | FIGURES. |
| | |
| | 6) FAILED. P1: PROVIDE A COMPLETE EQUIPMENT SCHEDULE |
| | FOR THE NEW WATER HEATER THAT INDICATES THE MAKE AND |
| | MODEL, GALLON SIZE AND EFFICIENCY RATING- TABLE C404.2 |
| | FBC EC. BASED ON THE MANUFACTURER?S INSTALLATION |
| | INSTRUCTIONS THE BOSCH ES4 WATER HEATER SPECIFIED IS A |
| | POINT OF USE WATER HEATER DESIGNED TO BE INSTALLED |
| | UNDER A SINK. THE PLAN SHOWS THE HEATER BEING USED AS A |
| | CENTRAL HOT WATER SOURCE. |
| | |
| | 13) FAILED. P1: THE 1/2-INCH HOT WATER SUPPLY PIPING TO |
| | THE PUBLIC LAVATORIES IS EXCEEDING THE 2 FT. MAXIMUM |
| | ALLOWABLE LENGTHS PER TABLE C404.5.1 FBC EC. THE 3M |
| | HEAT TRACE SYSTEM SPECIFICATION INDICATE THE CABLES |
| | MUST BE POWERED BY A 30 AMP GROUND FAULT CIRCUIT |
| | HOWEVER THE ELECTRICAL PLAN DOES NOT SHOW THE CABLES ON |
| | THE POWER. |
| | |
| | NEW COMMENT. |
| | |
| | 1) SHEET A4: SHOW THE HEIGHTS OF THE MIRRORS FROM THE |
| | FINISHED FLOORS TO THE REFLECTIVE SURFACES- SECTION |
| | 603.3 FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |