2021-12-14 13:34:19WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21091210 / NEW CONSTRUCTION
 ADD: 1236 PALM BEACH LAKES BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected] JESSICA LALOGGIA
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
  
 2ND REVIEW
 DATE: TUES. DEC. 14TH/ 2021
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 2ND REQUEST. FL 14218-R11. AS IN THE PAST WITH AUTO
 ZONE ALL PRODUCT APPROVALS WERE SUBMITTED HAVE THE
 DESIGNER OF RECORD STAMP OF APPROVAL, BUT NONE OF THE
 SUB-SYSTEMS HAVE BEEN IDENTIFIED. PLEASE IDENTIFY IN
 THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 3A) COMPLIED. THE METAL ROOF REPORT FL 11241-R7 HAS 6
 SUB-REPORTS WITH VARYING METALS CONFIGURATIONS AND
 PRESSURES.
  
 3B) 2ND REQUEST. ROOFING REPORT FL16739-R26 ONLY HAS
 THE FIRST 2 SHEETS OF THE REPORT.
 1ST ROUND COMMENTS. GAF SINGLE PLY ROOF SYSTEM FL
 16739-R26 WAS SUBMITTED THE DESIGNER STAMP OF APPROVAL
 ON THE COVER SHEET, PAGE 1 OF 137, OR SHEET 8 OF 144
 HIGHLIGHTED TABLE 2D STEEL DECK NEW ROOF MECHANICALLY
 FASTENED ROOF PAGES 31-38 OF REPORT IS HIGHLIGHTED.
 PAGE 31 OF 137 STARTS THE SUB-SYSTEMS TABLE 2 D FOR
 MECHANICALLY FASTEN ROOF SYSTEMS THROUGH PAGE 38 OF 137
 PAGES, NO SUB-SYSTEM IS HIGHLIGHTED.
 ALSO
 ALSO ON PAGE 12 OF 137 SYSTEM S-45 HIGHLIGHTED WITH A
 DESIGN PRESSURE OF -45.0 *. AT THE TOP OF THE SHEET
 THIS IS FOR STEEL OR CONCRETE DECK. YOU CAN?T HIGHLIGHT
 2 SYSTEMS. PLEASE PICK WHICH SUB-SYSTEM IS TO BE
 INSTALLED. PLEASE ALSO READ WHAT THE * MEANS. SEE PAGE
 2 NOTE NUMBER 9 STATES THIS EXTRAPOLATION IS NOT
 PERMITTED FOR SYSTEMS MARKED WITH AN ASTERISK * MARK.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) BUILDING PROVISO: THE LIFE SAFETY SHEET A-1.1 SHOWS
 SHELVING UNITS 90 INCHES IN HEIGHT AND 114 INCHES IN
 HEIGHT. THERE IS ALSO A NOTE THE MAXIMUM SHELVING UNIT
 HEIGHT IS 144 INCHES. SHELVING UNITS THAT ARE OVER 60
 INCHES IN HEIGHT REQUIRE A SPERATE PERMIT AND REVIEW.
 2020 W. P. B. ADMINISTRATIVE CODE SECTION 105.2 (6).
 THE SHELVING CAN BE REVIEWED UNDER THIS SET OF PLANS A
 SEPARATE PERMIT APPLICATION AND FEES ARE REQUIRED.
  
 7) COMPLIED. STEEL FOR THE TOP BOND BEAM.
  
 8) BUILDING PROVISO: SHEET S-2 SHOWS THE BAR JOIST
 SPACING AND REQUIRED ADDITIONAL STEEL FOR RTU AND ROOF
 HATCH OPENINGS WITHIN THE ROOF FRAMING SYSTEM. WELDED
 OR BOLTED CONNECTIONS
 THIS BUILDING CONTAINS EITHER BOLTED AND OR WELDED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 9) 2ND REQUEST. SUBMITTED THE COVERSHEETS FOR THE
 PRODUCT APPROVAL FOR ROOF HATCH. NO TECHNICAL SHEETS
 WERE SUBMITTED. THE PRODUCT APPROVAL COVER SHEETS AND
 TECHNICAL SHEETS SHOULD BE SUBMITTED IN THE SAME FILE.
 1ST ROUND COMMENT. SHEET S2 DETAIL 5 INDICATES A ROOF
 HATCH. COMPONENTS & CLADDING. SUBMIT THE PRODUCT
 APPROVAL FOR THE ROOF HATCH. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(A)
 ROOF HATCHES.
  
 10) COMPLIED. ROOF TOP CURB NOA: 20-0917.03 PAGE PG 4 &
 5.
  
 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  