| 2021-10-20 15:23:45 | ROOFING REPORTS 2 WERE ALSO SUBMITTED. ONE FOR METAL |
| | ROOFING THE OTHER AN UNDERLAYMENT. THE METAL ROOF |
| | REPORT FL 11241-R7 HAS 6 SUB-REPORTS WITH VARYING |
| | METALS CONFIGURATIONS AND PRESSURES. THE DESIGNER OF |
| | RECORD HAS A STAMP OF APPROVAL BUT HAS NOT IDENTIFIED |
| | WHICH SUB-SYSTEM IS TO BE INSTALLED ON THIS JOB. GAF |
| | SINGLE PLY ROOF SYSTEM FL 16739-R26 WAS SUBMITTED THE |
| | DESIGNER STAMP OF APPROVAL ON THE COVER SHEET, PAGE 1 |
| | OF 137 TABLE 2D STEEL DECK NEW ROOF MECHANICALLY |
| | FASTENED ROOF PAGES 31-38 HIGHLIGHTED. ALSO ON PAGE 12 |
| | OF 137 SYSTEM S-45 HIGHLIGHTED WITH A DESIGN PRESSURE |
| | OF -45.0 *. AT THE TOP OF THE SHEET THIS IS FOR STEEL |
| | OR CONCRETE DECK. YOU CAN?T HIGHLIGHT 2 SYSTEMS. PLEASE |
| | PICK WHICH SUB-SYSTEM IS TO BE INSTALLED. PLEASE ALSO |
| | READ WHAT THE * MEANS. SEE PAGE 2 NOTE NUMBER 9 STATES |
| | THIS EXTRAPOLATION IS NOT PERMITTED FOR SYSTEMS MARKED |
| | WITH AN ASTERISK * MARK. |
| | |