| 2021-10-28 10:54:32 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21091210 |
| | 10/28/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLAN SHEET P-1 IS MISLABELED AS M-1, PLEASE CORRECT- |
| | SECTION 107.2.1 WPB. |
| | |
| | 2) SHEET A0: THE PLANS SHALL BE DESIGNED IN ACCORDANCE |
| | WITH THE FBC- 2020 7TH EDITION ACCESSIBILITY CODE. |
| | PLEASE ADD THE CODE TO THE LIST UNDER BUILDING CODE |
| | ANALYSIS. |
| | |
| | 3) A4 DETAIL 7 RESTROOM PLAN: PLEASE CORRECT THE DETAIL |
| | ACCORDING TO THE FOLLOWING FBC ACC CODE SECTIONS AND |
| | NOTE THAT EXACT DETAILS AND DIMENSIONS ARE REQUIRED: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. |
| | |
| | 4) A4 DETAIL 6 ELEVATIONS: PLEASE CORRECT THE DETAIL |
| | ACCORDING TO THE FOLLOWING FBC ACC CODE SECTIONS AND |
| | NOTE THAT EXACT DETAILS AND DIMENSIONS ARE REQUIRED: |
| | A) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER |
| | SURFACES FROM THE FINISHED FLOORS- SECTION 606.3. |
| | B) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. |
| | C) PLEASE REMOVE THE VERTICAL GRAB BARS- THEY ARE NOT |
| | REQUIRED AND IN CONFLICT WITH SECTION 609.4- GRABS |
| | SHALL BE INSTALLED IN A HORIZONTAL POSITION. |
| | D) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS - |
| | SECTION 604.6. |
| | E) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | F) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2, AND FIGURES 306.2 & 306.3. |
| | G) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | ACCESSIBLE DRINKING FOUNTAIN- SECTION 602.2 & 305. |
| | FIGURES 306.2 & 306.3. |
| | H) KNEE AND TOE CLEARANCES FOR THE DRINKING FOUNTAIN- |
| | SECTION 606.2 & FIGURES 306.2 & 306.3. |
| | I) SPOUT OUTLET HEIGHT OF THE DRINKING FOUNTAIN FOR |
| | STANDING PERSONS- SECTION 602.7. |
| | |
| | 5) SHEET A6: PLEASE PROVIDE A SCUPPER DETAIL IN |
| | ACCORDANCE WITH SECTION 1503.4.2.1 FBC B. |
| | |
| | 6) P1: PROVIDE A COMPLETE EQUIPMENT SCHEDULE FOR THE |
| | NEW WATER HEATER THAT INDICATES THE MAKE AND MODEL, |
| | GALLON SIZE AND EFFICIENCY RATING- TABLE C404.2 FBC EC. |
| | |
| | 7) P1: PLEASE ADD THE HYDRANT TO THE FIXTURE SCHEDULE- |
| | SECTION 424.6 FBC P. |
| | |
| | 8) P1 WATER RISER: SHOW THE LOCATIONS OF REQUIRED WATER |
| | HAMMER ARRESTORS FOR THE FLUSH VALVES- SECTION 604.9 |
| | FBC P. |
| | |
| | 9) P1 WASTE/VENT RISER: SHOW TWO FIXTURE TRAPS AT THE |
| | DRINKING FOUNTAIN- SECTION 1002.1 FBC P. |
| | |
| | 10) P1: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO |
| | THE LAVATORIES- SECTION 419.5 FBC P. PLEASE NOTE IF |
| | MIXING VALVES ARE PROVIDED, THEY SHALL BE IN ASSE 1070 |
| | APPROVED- SECTION 607.1.2 FBC P. |
| | |
| | 11) P1: PLEASE PROVIDE THE PEX PIPE SPECIFICATIONS AS |
| | INDICATED- TABLE 605.4 FBC P. |
| | |
| | 12) P1: MINIMUM 1-INCH THICK INSULATION IS REQUIRED FOR |
| | THE HOT WATER PIPING- TABLE C403.2.10 FBC EC. |
| | |
| | 13) P1: THE 1/2-INCH HOT WATER SUPPLY PIPING TO THE |
| | PUBLIC LAVATORIES IS EXCEEDING THE 2 FT. MAXIMUM |
| | ALLOWABLE LENGTHS PER TABLE C404.5.1 FBC EC. |
| | |
| | 14) A1, A4, & P1: PLEASE SHOW THE DRINKING FOUNTAIN |
| | GUARD RAILS CONSISTENTLY ON ALL SHEETS- SECTION 307.2 |
| | FBC ACC. |
| | |
| | 15) A0: PLEASE NOTE THAT THE POTABLE WATER SERVICE |
| | BACKFLOW PREVENTER AND THE IRRIGATION SYSTEM SHALL BE |
| | DONE UNDER SEPARATE PERMIT- SECTION 105.1 & 107.1 WPB. |
| | PLEASE PLACE A NOTE ON THE PLAN ACCORDINGLY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | |