| Plan Review Notes For Permit 21091182 |
| Permit Number |
21091182 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-06-02 08:25:24 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) "NEW" EMERGENCY SYSTEM REQUIREMENT WITH 700.3(F) | | | MISSING FROM EMERGENCY SYSTEM. | | | | | | 700.3(F) TEMPORARY SOURCE OF POWER FOR MAINTENANCE OR | | | REPAIR OF | | | THE ALTERNATE SOURCE OF POWER. IF THE EMERGENCY SYSTEM | | | RELIES | | | ON A SINGLE ALTERNATE SOURCE OF POWER, WHICH WILL BE | | | DISABLED FOR | | | MAINTENANCE OR REPAIR, THE EMERGENCY SYSTEM SHALL | | | INCLUDE | | | PERMANENT SWITCHING MEANS TO CONNECT A PORTABLE OR | | | TEMPORARY | | | ALTERNATE SOURCE OF POWER, WHICH SHALL BE AVAILABLE FOR | | | THE | | | DURATION OF THE MAINTENANCE OR REPAIR. | | | | | | 2) PLEASE LABEL ALL MAINS AND PROVIDE NOTE FOR LABELING | | | OF MAINS PER 230.2(E) | | | | | | 3) BREAKER OR FUSE AT FIRE PUMP MAIN TO BE INSTALLED | | | PER 240.87, OR 240.67 | | | | | | 4) SEPARATE PERMITS AND FEES WILL BE REQUIRED FOR ALL | | | LOW VOLTAGE SYSTEMS, GENERATORS, FIRE ALARM, SITE | | | LIGHTING SYSTEMS. | | | | | | |
|