2022-06-02 08:25:24FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) "NEW" EMERGENCY SYSTEM REQUIREMENT WITH 700.3(F)
 MISSING FROM EMERGENCY SYSTEM.
  
 700.3(F) TEMPORARY SOURCE OF POWER FOR MAINTENANCE OR
 REPAIR OF
 THE ALTERNATE SOURCE OF POWER. IF THE EMERGENCY SYSTEM
 RELIES
 ON A SINGLE ALTERNATE SOURCE OF POWER, WHICH WILL BE
 DISABLED FOR
 MAINTENANCE OR REPAIR, THE EMERGENCY SYSTEM SHALL
 INCLUDE
 PERMANENT SWITCHING MEANS TO CONNECT A PORTABLE OR
 TEMPORARY
 ALTERNATE SOURCE OF POWER, WHICH SHALL BE AVAILABLE FOR
 THE
 DURATION OF THE MAINTENANCE OR REPAIR.
  
 2) PLEASE LABEL ALL MAINS AND PROVIDE NOTE FOR LABELING
 OF MAINS PER 230.2(E)
  
 3) BREAKER OR FUSE AT FIRE PUMP MAIN TO BE INSTALLED
 PER 240.87, OR 240.67
  
 4) SEPARATE PERMITS AND FEES WILL BE REQUIRED FOR ALL
 LOW VOLTAGE SYSTEMS, GENERATORS, FIRE ALARM, SITE
 LIGHTING SYSTEMS.
  
  