2022-02-17 16:17:25CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21091182 751 W EXECUTIVE CENTER DR
  
 2ND REVIEW:
  
 GENERAL NOTES:
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTOR
  
 A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTER
  
 INSTALLATION MANUALS FOR ALL OWNER SUPPLIED EQUIPMENT
 SHALL BE ONSITE FOR INSPECTION
  
  
 PLUMBING COMMENTS: DENIED
  
 1. NEW COMMENT: DETAIL FOR GREASE INTERCEPTOR PROVIDED
 ON CIVIL C601.3; PER WPB FBC 107.2.1, SHOW ON P100 AND
 P700 THE TWO-WAY CLEANOUTS UPSTREAM AND DOWNSTREAM OF
 THE GREASE INTERCEPTOR.
  
 2. SECOND REQUEST: REVISED P801/DETAIL BJWC-10; TO BE
 CLEAR, A DEDICATED SHUT OFF VALVE IS REQUIRED FOR THE
 COLD WATER TO THE SINK AND HOT WATER TO THE SINK PER
 FBC PL 602.1. THE COLD WATER SHUT-OFF VALVE SHALL BE
 LOCATED IN THE COLD WATER LINE BETWEEN THE TEE AND THE
 TMV. A DEDICATED SHUT OFF VALVE SHALL BE LOCATED IN THE
 COLD WATER LINE BETWEEN THE TEE AND THE WATER HEATER
 PER FBC PL 503.1. A HOT WATER SHUT-OFF VALVE DOES NOT
 NEED TO BE LOCATED IN THE HOT WATER LINE AHEAD OF THE
 TMV AS IT WOULD BE REDUNDANT.
  
 3. NEW COMMENT: P801/DETAILS BJWC-05, BJWC-06 AND
 BJWC-07, PER FBC PL 504.6 (2) (10), PROVIDE AIR GAP OF
 NOT MORE THAN 6 INCHES AND NOT LESS THAN TWO TIMES THE
 PIPE DIAMETER FOR T&P DISHARGE TERMINATION POINT
  
 4. NEW COMMENT: CALCULATIONS FOR STORM DRAINS SHALL BE
 BASED UPON FLORIDA PLUMBING CODE 2020 7TH EDITION PER
 WPB FBC 107.2.1
  
 5. NEW COMMENT: PER WPB FBC 107.2.1, IDENTIFY THE ROOF
 DRAINS, SCUPPERS ON THE RISER AND PLAN VIEWS
 CORRESPONDING WITH THE ROOF DESIGNATIONS NOTED ON THE
 CALCULATION CHART.
  
 6. NEW COMMENT: THE CALCULATION CHART IS UNCLEAR AS IT
 NOTES OVERFLOW SCUPPERS AS WELL AS SCUPPERS. PER WPB
 FBC 107.2.1, PLEASE PROVIDE REFERENCE TO A300 AND
 A800/DETAILS 3 AND 5 FOR LOCATIONS AND DETAILS OF
 SCUPPERS AND OVERFLOW SCUPPERS.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  