| 2022-02-17 16:17:25 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21091182 751 W EXECUTIVE CENTER DR |
| | |
| | 2ND REVIEW: |
| | |
| | GENERAL NOTES: |
| | |
| | A SEPARATE PERMIT IS REQUIRED FOR THE GREASE |
| | INTERCEPTOR |
| | |
| | A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW |
| | PREVENTER |
| | |
| | INSTALLATION MANUALS FOR ALL OWNER SUPPLIED EQUIPMENT |
| | SHALL BE ONSITE FOR INSPECTION |
| | |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. NEW COMMENT: DETAIL FOR GREASE INTERCEPTOR PROVIDED |
| | ON CIVIL C601.3; PER WPB FBC 107.2.1, SHOW ON P100 AND |
| | P700 THE TWO-WAY CLEANOUTS UPSTREAM AND DOWNSTREAM OF |
| | THE GREASE INTERCEPTOR. |
| | |
| | 2. SECOND REQUEST: REVISED P801/DETAIL BJWC-10; TO BE |
| | CLEAR, A DEDICATED SHUT OFF VALVE IS REQUIRED FOR THE |
| | COLD WATER TO THE SINK AND HOT WATER TO THE SINK PER |
| | FBC PL 602.1. THE COLD WATER SHUT-OFF VALVE SHALL BE |
| | LOCATED IN THE COLD WATER LINE BETWEEN THE TEE AND THE |
| | TMV. A DEDICATED SHUT OFF VALVE SHALL BE LOCATED IN THE |
| | COLD WATER LINE BETWEEN THE TEE AND THE WATER HEATER |
| | PER FBC PL 503.1. A HOT WATER SHUT-OFF VALVE DOES NOT |
| | NEED TO BE LOCATED IN THE HOT WATER LINE AHEAD OF THE |
| | TMV AS IT WOULD BE REDUNDANT. |
| | |
| | 3. NEW COMMENT: P801/DETAILS BJWC-05, BJWC-06 AND |
| | BJWC-07, PER FBC PL 504.6 (2) (10), PROVIDE AIR GAP OF |
| | NOT MORE THAN 6 INCHES AND NOT LESS THAN TWO TIMES THE |
| | PIPE DIAMETER FOR T&P DISHARGE TERMINATION POINT |
| | |
| | 4. NEW COMMENT: CALCULATIONS FOR STORM DRAINS SHALL BE |
| | BASED UPON FLORIDA PLUMBING CODE 2020 7TH EDITION PER |
| | WPB FBC 107.2.1 |
| | |
| | 5. NEW COMMENT: PER WPB FBC 107.2.1, IDENTIFY THE ROOF |
| | DRAINS, SCUPPERS ON THE RISER AND PLAN VIEWS |
| | CORRESPONDING WITH THE ROOF DESIGNATIONS NOTED ON THE |
| | CALCULATION CHART. |
| | |
| | 6. NEW COMMENT: THE CALCULATION CHART IS UNCLEAR AS IT |
| | NOTES OVERFLOW SCUPPERS AS WELL AS SCUPPERS. PER WPB |
| | FBC 107.2.1, PLEASE PROVIDE REFERENCE TO A300 AND |
| | A800/DETAILS 3 AND 5 FOR LOCATIONS AND DETAILS OF |
| | SCUPPERS AND OVERFLOW SCUPPERS. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |