2022-02-25 15:03:532ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21091182
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS WITH AN
 OCCUPANT CLASSIFICATION AS BASED ON THE USE OF EACH
 SPACE ACCORDING TO FBC M TABLE 403.3.1.1. I NEED TO
 FOLLOW YOUR CALCULATION FOR EACH USE OF SPACE, IF WE
 USE THE SAME OCCUPANCY CLASSIFICATION WE WILL STAY ON
 THE SAME PAGE. PLEASE REMEMBER WHEN CALCULATING THE
 OUTDOOR AIR FOR EACH USE OF SPACE WE MUST USE FBC M
 403.3.1.1 AND NOT THE ARCHITECTS EGRESS OCCUPANT COUNT.
  
 FBC M 403.3.1.1 2ND SENTENCE: THE OCCUPANT LOAD
 UTILIZED FOR DESIGN OF THE VENTILATION SYSTEM SHALL BE
 NOT LESS THAN THE NUMBER DETERMINED FROM THE ESTIMATED
 MAXIMUM OCCUPANT LOAD RATE INDICATED IN TABLE
 403.3.1.1. VENTILATION RATES FOR OCCUPANCIES NOT
 REPRESENTED IN TABLE 403.3.1.1 SHALL BE THOSE FOR A
 LISTED OCCUPANCY CLASSIFICATION THAT IS MOST SIMILAR IN
 TERMS OF OCCUPANT DENSITY, ACTIVITIES AND BUILDING
 CONSTRUCTION; OR SHALL BE DETERMINED BY AN APPROVED
 ENGINEERING ANALYSIS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  