Plan Review Notes
Plan Review Notes For Permit 21091182
Permit Number 21091182
Review Stop G
Sequence Number 2
Notes
Date Text
2022-02-17 15:57:53GAS COMMENTS: APPROVED WITH PROVISOS
  
 PROVISO: PER FBC FG 410.1, MP REGULATORS PROVIDED IN
 OUTDOOR APPLICATIONS SHALL BE DESIGNED FOR OUTDOOR USE.
 SEE SUBMITTED MAXITROL SPECIFICATION SHEET NOTING
 IMBLUE TECHNOLOGY AND PROVIDE ACCORDINGLY. SEE
 P801/DETAIL BJWC- 02 AND BJWC-16; PRIOR TO INSPECTION,
 A PLAN REVISION REFLECTING THE OUTDOOR APPLICATION,
 ADDING SUFFIX B TO THE MODEL NUMBER SHALL BE SUBMITTED
 TO THE BUILDING DEPARTMENT, APPROVED AND ON SITE. WPB
 FBC 107.2.1. PROCEED AT YOUR OWN RISK.
  
 CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR
 MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL
 GAS INSPECTION. CALL 561-805-6692 FOR FURTHER
 INFORMATION.
  
 INSTALLATION MANUALS FOR ALL GAS EQUIPMENT SHALL BE
 ONSITE FOR GAS INSPECTION. A SEPARATE PERMIT IS
 REQUIRED FOR THE GAS
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
  
 21091182 751 W EXECUTIVE CENTER DR
  