Plan Review Notes
Plan Review Notes For Permit 21091182
Permit Number 21091182
Review Stop P
Sequence Number 1
Notes
Date Text
2021-11-23 13:25:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21091182 751 W EXECUTIVE CENTER DR
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 GENERAL NOTES:
 A SEPARATE PERMIT FOR REVIEW BY ENGINEERING AND
 PLUMBING FOR THE GREASE INTERCEPTOR IS REQUIRED
  
 A SEPARATE PERMIT FOR REVIEW BY ENGINEERING AND
 PLUMBING FOR THE BACKFLOW PREVENTER IS REQUIRED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 INDICATING THE FOLLOWING:
 ?A) A650/DETAIL 12/TOILET TISSUE DISPENSER: THE SIDE
 WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, LOCATED
 12 INCHES, NOT 10 INCHES (305 MM) MAXIMUM FROM THE REAR
 WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL
 PER FBC ACC 604.5.1
 ?B) A650/DETAIL 12/GRAB-BAR-HDCP: THE SEAT HEIGHT OF A
 WATER CLOSET ABOVE THE FINISH FLOOR SHALL BE 17 INCHES
 MINIMUM AND 19 INCHES MAXIMUM MEASURED TO THE TOP OF
 THE SEAT, NOT TO THE RIM OF THE FIXTURE PER FBC ACC
 604.4.
 ?C) 650/DETAIL 1: SHOW CLEAR FLOOR SPACE FOR COMPLIANT
 URINAL (REQUIRED BY FBC ACC 213.3) COMPLYING WITH FBC
 ACC 305; PROVIDE ELEVATION DETAIL FOR ADA COMPLIANT
 URINAL. URINALS SHALL BE THE STALL-TYPE OR THE
 WALL-HUNG TYPE WITH THE RIM 17 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. URINALS SHALL BE 13 1/2 INCHES
 DEEP MINIMUM MEASURED FROM THE OUTER FACE OF THE URINAL
 RIM TO THE BACK OF THE FIXTURE PER FBC ACC 605.2.
 ?D) PROVIDE DETAIL FOR COMPLIANT WALL HUNG LAVATORIES
 SHOWING COMPLIANCE WITH FBC ACC 606.3,
 ?E) 650/DETAIL 1 AND 3; DRINKING FOUNTAINS: OBJECTS
 WITH LEADING EDGES MORE THAN 27 INCHES AND NOT MORE
 THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE MORE
 THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION PATH
 PER FBC ACC 307.2.
 ?F) 650/DETAIL 1; DRINKING FOUNTAIN. PROVIDE SIDE
 ELEVATION SHOWING COMPLIANCE WITH FBC ACC 306, 602.6
 AND 602.7.
  
 2. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTER FOR THE WATER SERVICE.
  
 3. PER WPB FBC 107.2.1, PROVIDE A MANUFACTURER
 SPECIFICATION/INSTALLATION MANUAL AND A DETAIL FOR THE
 WATER SERVICE BACKFLOW PREVENTER.
  
 5.GREASE INTERCEPTOR-CITY OF WEST PALM BEACH PUBLIC
 WORKS DEPT- STANDARD DETAIL GS-7-CONCRETE GRAVITY SEWER
 SYSTEM-GREASE INTERCEPTOR. NOTE4: MAXIMUM CAPACITY OF A
 CONCRETE GRAVITY GREASE INTERCEPTOR IS 1200 GALLONS. IF
 MORE CAPACITY IS REQUIRED INSTALLATION OF
 MULTI-CHAMBERED INTERCEPTORS OR MULTIPLE INTERCEPTORS
 IN SERIES.
  
 6. PROVIDE CALCULATIONS FOR THE GREASE INTERCEPTOR
 WHICH IS TO BE FURNISHED UNDER THE CIVIL DRAWINGS.
  
 7. PROVIDE A DETAIL OF THE GREASE INTERCEPTOR SHOWING
 COMPLIANCE WITH CITY OF WEST PALM BEACH PUBLIC WORKS
 DEPT- STANDARD DETAIL GS-7-CONCRETE GRAVITY SEWER
 SYSTEM-GREASE INTERCEPTOR AND FBC PL SECTION 1003. SHOW
 ALL CLEANOUTS (WITH TWO-WAY CLEANOUT FITTING) AND
 MANHOLES TO GRADE. DOWNSTREAM TWO-WAY CLEANOUT SHALL
 ALSO SERVE AS THE SAMPLING STATION.
  
 8. IT IS NOTED THAT S2 AND S7 SINKS DISCHARGE TO GT1
 INTERCEPTORS WHICH IN TURN CONNECT TO THE GREASY WASTE
 SYSTEM. PER WPB FBC 107.2.1, CLARIFY. FBC PL 1003.3.1
 STATES A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL
 DEVICE SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM
 FIXTURES AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED
 IN FOOD PREPARATION AREAS, SUCH AS IN RESTAURANTS,
 HOTEL KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS,
 FACTORY CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT
 SHALL INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES
 OR SIMILAR DEVICES; WOK STATIONS; FLOOR DRAINS OR SINKS
 INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH
 UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED. WHERE LACK
 OF SPACE OR OTHER CONSTRAINTS PREVENT THE INSTALLATION
 OR REPLACEMENT OF A GREASE INTERCEPTOR, ONE OR MORE
 GREASE INTERCEPTORS SHALL BE PERMITTED TO BE INSTALLED
 ON OR ABOVE THE FLOOR AND UPSTREAM OF AN EXISTING
 GREASE INTERCEPTOR.
  
 9. THE PLANS(A900 ROOM FINISH SCHEDULE) ARE UNCLEAR AS
 TO THE WALL FINISHES ADJACENT TO MOP SINKS/SERVICE
 SINKS. PER WPB FBC 107.2.1, PROVIDE FINISH WALL
 SCHEDULE FOR ROOMS HOUSING SAID SINKS. FINISH SCHEDULE
 SHALL CLEARLY INDICATE COMPLIANCE WITH FBC PL 310.3 AND
 FBC 1210.2.2. WALLS AND PARTITIONS WITHIN 2 FEET (610
 MM) OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF NOT LESS THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE. PLEASE NOTE THAT FBC 1210.2.2
 STIPULATES THAT THE MATERIAL BE "HARD." THE INTENT OF
 THIS SECTION IS THAT THE SURROUNDING MATERIAL SHOULD
 NOT BE OF A TYPE THAT IS EASILY DAMAGED SUCH THAT THE
 MATERIAL COULD BECOME ABSORBENT AND THUS, NOT READILY
 CLEANABLE AND SANITIZED. PAINTED DRYWALL, EVEN WHERE
 COATED WITH HIGHLY DURABLE PAINTS, DOES NOT MEET THE
 INTENT OF SECTION 1210.2.2. THE TYPICAL MATERIALS USED
 FOR THIS APPLICATION ARE CERAMIC TILE, FIBERGLASS
 REINFORCED PLASTIC (FRP) PANELS, PHENOLIC PANELS,
 LAMINATED PLASTIC PANELS, PAINTED STEEL AND STAINLESS
 STEEL.
  
 10. S1 HAND SINKS ARE SHOWN ON SANITARY FLOOR PLANS AND
 RISER DIAGRAMS DISCHARGING TO THE GREASY WASTE. PER FBC
 PL 1003.3.1, DISCHARGE TO SANITARY, NOT THE GREASY
 WASTE.
  
 11. PER WPB FBC 107.2.1, PLEASE CLARIFY. IS S7 IN THE
 WASH AREA A PRE-RINSE SINK SERVICING PW10 POT & PAN
 WASHER?
  
 12. PER WPB FBC 107.2.1, PROVIDE MANUFACTURERS
 SPECIFICATION/INSTALLATION MANUALS FOR ALL OWNER
 PROVIDED EQUIPMENT.
  
 12. P800/DETAIL BJWC-11 AND P001 EQUIPMENT SCHEDULE
 INDICATES TEMPERING VALVE TO COOL POT WASHER DETAIL.
 PER FBC PL 608.1, 608.3, SPECIFY AND FURNISH A BACKFLOW
 PREVENTER IN THE COLD WATER LINE TO THE DEVICE.
 INDICATE THE DEVICE IN DETAIL AND SCHEDULE.
  
 13. P-100/PLUMBING & EQUIPMENT-ST1 SEDIMENT TRAP: MIFAB
 MI-SD-3; DESCRIPTION IS RECEPTACLE WITH DEEP SEAL TRAP
 AND INTERNAL VENT SYSTEM. 5/P-700 SANITARY RISER
 DIAGRAM AND 5/P-302 PLAN VIEW SHOWS A GRATED INLET
 STRUCTURE WITH A BOTTOM OUTLET CONNECTED TO A VENTED
 P-TRAP. MI-SD-3 SPECIFICATION SHEET SHOWS HORIZONTAL
 INLET AND OUTLET WITH A SEWER GAS STOPPER. PER WPB FBC
 107.2.1, CLARIFY. ADDITIONALLY, PROVIDE A MANUFACTURERS
 DETAIL SHOWING A 6 INCH WATER TRAP SEAL AS REQUIRED BY
 FBC PL 1003.5. PER WPB FBC 107.2.1, PROVIDE
 MANUFACTURERS SPECIFICATION/INSTALLATION MANUALS FOR
 DEVICE. MAKE CHANGES IN RISER DIAGRAM AND PLAN VIEW AS
 IS APPROPRIATE.
  
 14. P001/OWNER EQUIPMENT CONNECTION SCHEDULE. REGARDING
 S1 HAND SINK THERMAL MIXING VALVE, PER WPB FBC 107.2.1,
 PROVIDE TEMPERATURE SETTING INSTRUCTION.
  
 15. PER WPB FBC 107.2.1, CLEARLY INDICATE ON THE PLANS
 (INCLUDING SCHEDULE) ANY SINK TO BE USED FOR FOOD PREP.
 PLEASE NOTE THAT PER FBC PL 802.1.1, EQUIPMENT AND
 FIXTURES UTILIZED FOR THE STORAGE, PREPARATION AND
 HANDLING OF FOOD SHALL DISCHARGE THROUGH AN INDIRECT
 WASTE PIPE BY MEANS OF AN AIR GAP. EACH WELL OF A
 MULTIPLE-COMPARTMENT SINK SHALL DISCHARGE INDEPENDENTLY
 TO A WASTE RECEPTOR. P800/BJWC-7 DETAIL FOR THREE
 COMPARTMENT SINK DOES NOT COMPLY WITH THIS REQUIREMENT.
 IF A THREE-COMPARTMENT SINK IS A DESIGNATED FOOD PREP
 SINK, PER WPB FBC 107.2.3, PROVIDE A DETAIL SHOWING
 COMPLIANCE WITH FBC PL 802.1.1.
  
 16. PREP SINKS TO BE USED FOR WASHING OF PRODUCE OR
 OTHER NON-GREASY FOOD PRODUCT SHALL NOT DISCHARGE TO
 THE GREASY WASTE PER FBC PL 1003.3.1. PER WPB FBC
 107.2.1, CLEARLY INDICATE ANY SUCH SINK ON THE PLANS,
 INCLUDING SCHEDULE AND COMPLY WITH FBC PL 1003.3.1.
  
 17. P001/GENERAL NOTES; NOTE 6. REVISE NOTE TO REQUIRE
 1/4 INCH PER FOOT MINIMUM FALL FOR PIPE SIZED 2-1/2
 INCH OR SMALLER, 1/8 INCH PER FOOT MINIMUM FALL FOR
 PIPE SIZED 3 INCH TO 6 INCH PER FBC PL TABLE 704.1.
  
 18. REFER TO ?BJS WEST PALM BEACH FL SPECS? IN
 SUPPORTING DOCUMENTS FOR MATERIAL, MEANS, METHODS,
  
 19. N/A
  
 20. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL
 BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND
 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS
 STATING THE SAME.
  
 21. PER WPB FBC 107.2.1, PROVIDE ON PIPE HANGER DETAIL
 BJWC-18 A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 22. P800/BJWC-10; VALVING ARRANGEMENT FOR COLD WATER
 WITH WATER HEATER. PER WPB FBC 107.2.1 PROVIDE THE
 FOLLOWING, PER FBC PL 602.1, PROVIDE A TEE BETWEEN THE
 POINT THE COLD WATER OUTLET PROTRUDES FROM THE WALL
 PLACED BETWEEN THE TEMPERING VALVE/FIXTURE AND THE
 WATER HEATER. PLACE A DEDICATED SHUTOFF VALVE IN THE
 COLD WATER UPSTREAM OF THE WATER HEATER AND THE
 TEMPERING VALVE.
  
 23. P801/BJWC-14; SHOWS A TIGHT RADIUS FITTING AT THE
 BASE OF THE STORM LEADER. PER FBC PL 1101.6, 706.3 AND
 TABLE 706.3, PROVIDE A SHORT SWEEP.
  
 24. P801/BJWC-8; SHOWS A TIGHT RADIUS FITTING AT THE
 BASE OF THE OVERFLOW DOWNSPOUT. PER FBC PL 1101.6,
 706.3 AND TABLE 706.3, PROVIDE A SHORT SWEEP.
  
 25. P801/BJWC-9; HORIZONTAL DRAIN VENT DETAIL. PER FBC
 PL 905.3 AND 905.4, VENTS SHALL CONNECT ABOVE THE
 CENTERLINE OF THE DRAIN OF THE HORIZONTAL DRAIN AND
 SHALL RISE VERTICALLY (45 DEGREES MINIMUM FROM THE
 HORIZONTAL) TO A POINT NOT LESS THAN 6 INCHES ABOVE THE
 FLOOD LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE
 BEING VENTED
  
 26. P801/BJWC-07; PER WPB FBC 107.2.1, NOTE TERMINATION
 POINT OF T&P RELIEF VALVE COMPLYING WITH FBC PL 504.6.
  
 27. P801/BJWC-05; PER WPB FBC 107.2.1,
 ?A) NOTE TERMINATION POINT OF T&P RELIEF VALVES
 COMPLYING WITH FBC PL 504.6.
 ?B) PROVIDE PAN DRAIN FOR HEAT RECLAIM TANK
 ?C) PROVIDE MANUFACTURERS SPECIFICATION/INSTALLATION
 MANUAL FOR HEAT RECLAIM SYSTEM INCLUDING THE TANK AND
 THE HEAT RECLAIM UNIT. PROVISION SHALL BE MADE TO
 PREVENT CROSS CONTAMINATION BETWEEN POTABLE WATER AND
 REFRIGERATION. FBC PL 608.
  
 28. P801/BJWC-06; PER WPB FBC 107.2.1, NOTE TERMINATION
 POINT OF T&P RELIEF VALVE COMPLYING WITH FBC PL 504.6.
  
 29. P801/BJWC-06; PER WPB FBC 107.2.1,
 ?A) NOTE TERMINATION POINT OF T&P RELIEF VALVE AND PAN
 DRAIN COMPLYING WITH FBC PL 504.6. PLEASE NOTE THAT PER
 FBC PL CHAPTER 2, DEFINITIONS, A WASTE RECEPTOR IS
 DEFINED AS A FLOOR SINK, STANDPIPE, HUB DRAIN OR FLOOR
 DRAIN THAT RECEIVES THE DISCHARGE OF ONE OR MORE
 INDIRECT WASTE PIPES. A MOP SINK DOES NOT QUALIFY AS A
 WASTE RECEPTOR.
 ?B) PROVIDE A STRUCTURAL DETAIL FOR THE WATER HEATER
 WALL SUPPORT TO INCLUDE STRUCTURAL BRACKETS/FLOOR AND
 ANCHORS. A MANUFACTURED KIT MADE FOR THIS APPLICATION
 MAY BE SPECIFIED AND MANUFACTURERS
 SPECIFICATION/INSTALLATION MANUAL SUBMITTED AS LONG AS
 IT MEETS THE INTENT.
  
 30. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR TWO WAY
 CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND THE
 BUILDING SEWER. SEE FBC PL 708.1.3, 708.1.8.
  
 31. P700/DETAIL 2: P-5 UTILITY SINK IS S-TRAPPED.
 REVISE TO COMPLY WITH FBC PL 909.1 AND 1002.3(5).
  
 32. P001 PLUMBING FIXTURE SCHEDULE:
 ?A) INDICATES WATER CLOSETS PB1A AND PB1B ARE IDENTICAL
 IN SPECIFICATIONS. LOOKING AT THE PLANS, IT APPEARS
 THAT THE DIFFERENCE IS THAT ONE (PB1B) IS TO BE ADA
 COMPLIANT. PER WPB FBC 107.2.1P, INDICATE IN P001
 PLUMBING FIXTURE SCHEDULE WHICH IS ADA COMPLIANT.
 ?B) INDICATES WATER CLOSETS PB1A AND PB1B ARE IDENTICAL
 IN SPECIFICATIONS. LOOKING AT THE PLANS, IT APPEARS
 THAT THE DIFFERENCE IS THAT ONE (PB1B) IS TO BE ADA
 COMPLIANT. PER WPB FBC 107.2.1P, INDICATE IN P001
 PLUMBING FIXTURE SCHEDULE WHICH IS ADA COMPLIANT.
 ?C) URINAL; PER WPB FBC 107.2.1, PROVIDE IN PLUMBING
 SCHEDULE A DESIGNATION FOR THE ADA COMPLIANT URINAL AND
 IDENTIFY SAME ON THE PIPING PLANS.
 ?D) LAVATOTIES; PER WPB FBC 107.2.1, PROVIDE IN
 PLUMBING SCHEDULE A DESIGNATION FOR ADA COMPLIANT
 LAVATORIES AND IDENTIFY SAME ON THE PIPING PLANS.
  
 33. PER P001 PLUMBING FIXTURE SCHEDULE, PB1A AND PB1B
 WATER CLOSETS ARE TO DISCHARGE TO FLOOR MOUNTED CARRIER
 SYSTEM (EQUAL TO) JR SMITH 210Y WHICH IS A HORIZONTAL
 (ABOVE THE FLOOR) DRAINAGE PATTERN OR A 410Y WHICH IS A
 VERTICAL DRAINAGE (THROUGH THE FLOOR) DRAINAGE PATTERN.
 PROVIDED WITH FLOOR. WATER CLOSETS TO DISCHARGE TO A
 THROUGH THE WALL WASTE INLET. SANITARY RISER DIAGRAMS
 ALL SHOW HORIZONTAL BRANCH BELOW GRADE WITH FLOOR
 MOUNTED CONNECTIONS DOWN TO CLOSET BEND AND CONNECTING
 HORIZONTALLY TO HORIZONTAL BRANCH. PER WPB FBC 107.2.1,
 RISER DIAGRAMS SHALL DEPICT WATER CLOSETS DISCHARGING
 TO FLOOR MOUNTED CARRIER. DEPICTION SHALL NOTE VERTICAL
 OR HORIZONTAL DRAIN PATTERN AS IS APPLICABLE TO THE
 SITUATION. VENTING OF WATER CLOSETS SHALL CONNECT TO
 CARRIER IN ACCORDANCE WITH FBC PL 909.1 AND/OR AS
 APPLICABLE TO THE SITUATION, SECTIONS 910, 911AND 914.
 P302 AND P100 SHALL REFLECT THE CHANGES.
  
 34. FLOOR DRAINS SHOWN ON P700/DETAILS 2 AND 3, THAT
 ARE NOT CONNECTED TO A CIRCUIT VENTED BRANCH AS ALLOWED
 IN FBC PL 914.1.1 SHALL BE VENTED IN ACCORDANCE WITH
 FBC PL 909.1 AND SECTION 910 OR 911. THE DRY PORTION OF
 THE VENT SHALL BE IN ACCORDANCE WITH FBC PL 905.3,
 905.4 AND 905.5.
  
 35. PER WPB FBC 107.2.1, PROVIDE PLAN VIEW AND RISER
 DIAGRAM TO ADDRESS STORM DRAINAGE OF THE ROOF. PROVIDE
 CALCULATIONS FOR SIZING OF HORIZONTAL PIPING (INCLUDING
 SLOPE OF PIPE), VERTICAL LEADERS AND DOWNSPOUTS. PLANS
 SHALL COMPLY WITH FBC PL CHAPTER 11 INCLUDING BUT NOT
 LIMITED TO SECTION 1106.1, FIGURE 1106.1 100YR. 1 HOUR
 RAINFALL (INCHES) EASTERN UNITED STATES, SECTION
 1106.2, TABLE 1106.2, SECTION 1106.3, TABLE 1106.3,
 SECTION 1106.4, TABLE 1106.4, SECTION 1108.1, SECTION
 1108.2 AND SECTION 1108.3.
  
 36. PER WPB FBC 107.2.1 AND WPB FBC 107.3.5.1.3,
 PROVIDE A RISER DIAGRAM FOR THE HOT AND COLD WATER
 DISTRIBUTION. SHOW SIZING, VALVES, WATER HAMMER
 ARRESTORS, BACKFLOW PREVENTERS, TRAP PRIMER
 CONNECTIONS, FIXTURE/EQUIPMENT CONNECTIONS (ID
 FIXTURES/EQUIPMENT TO CORRESPOND TO FIXTURE/EQUIPMENT
 SCHEDULES) AND APPURTENANCES. FOR CONNECTIONS TO
 FIXTURES/EQUIPMENT THAT ARE DETAILED ON P800/P801, A
 NOTE REFERRING TO APPLICABLE DETAIL SHALL BE PROVIDED;
 VALVING, WHAS ETC. WILL NOT BE REQUIRED TO BE SHOWN IN
 RISER DIAGRAM.
  
 37. PER WPB FBC 107.2.1, PROVIDE A NOTE ON THE PLANS
 STATING ?REFER TO BJS WEST PALM BEACH FL SPECS 15010
 AND 15400 FOR EQUIPMENT, FIXTURES, APPURTENANCES,
 MATERIALS, MEANS AND METHOD SPECIFICATIONS?.
 38. RE: BJS SPEC 15400-2.16-D. BALL VALVES SHALL BE
 LEAD FREE.
  
 39. RE: BJS SPEC 15400-2.17. PER WPB FBC 107.2.1,
 SPECIFY THICKNESSES FOR INSULATION FOR THE DIFFERENT
 APPLICATIONS INCLUDING ABOVE GROUND CONDENSATE. HOT
 WATER SHALL BE INSULATED AS REQUIRED BY FBC EC E607.5
 AND EC C404.4.
  
 40. RE: BJS SPEC 15400-3.2-B. SOLDER SHALL BE LEAD FREE
 COMPLYING WITH FBC PL 605.2.1.
  
 41. RE: BJS SPEC 15400-3.2-C. BRASS SHALL BE LEAD FREE
 COMPLYING WITH FBC PL 605.2.1.
  
 39. RE: BJS SPEC 15400-3.5-B. PER WPB FBC 107.2.1,
 SPECIFY THICKNESSES FOR INSULATION OF THE DOMESTIC
 WATER. HOT WATER SHALL BE INSULATED AS REQUIRED BY FBC
 EC E607.5 AND EC C404.4.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21091182 751 W EXECUTIVE CENTER DR
  