| Date |
Text |
| 2021-11-23 13:25:12 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21091182 751 W EXECUTIVE CENTER DR |
| | 1ST REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | GENERAL NOTES: |
| | A SEPARATE PERMIT FOR REVIEW BY ENGINEERING AND |
| | PLUMBING FOR THE GREASE INTERCEPTOR IS REQUIRED |
| | |
| | A SEPARATE PERMIT FOR REVIEW BY ENGINEERING AND |
| | PLUMBING FOR THE BACKFLOW PREVENTER IS REQUIRED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS |
| | INDICATING THE FOLLOWING: |
| | ?A) A650/DETAIL 12/TOILET TISSUE DISPENSER: THE SIDE |
| | WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, LOCATED |
| | 12 INCHES, NOT 10 INCHES (305 MM) MAXIMUM FROM THE REAR |
| | WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL |
| | PER FBC ACC 604.5.1 |
| | ?B) A650/DETAIL 12/GRAB-BAR-HDCP: THE SEAT HEIGHT OF A |
| | WATER CLOSET ABOVE THE FINISH FLOOR SHALL BE 17 INCHES |
| | MINIMUM AND 19 INCHES MAXIMUM MEASURED TO THE TOP OF |
| | THE SEAT, NOT TO THE RIM OF THE FIXTURE PER FBC ACC |
| | 604.4. |
| | ?C) 650/DETAIL 1: SHOW CLEAR FLOOR SPACE FOR COMPLIANT |
| | URINAL (REQUIRED BY FBC ACC 213.3) COMPLYING WITH FBC |
| | ACC 305; PROVIDE ELEVATION DETAIL FOR ADA COMPLIANT |
| | URINAL. URINALS SHALL BE THE STALL-TYPE OR THE |
| | WALL-HUNG TYPE WITH THE RIM 17 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. URINALS SHALL BE 13 1/2 INCHES |
| | DEEP MINIMUM MEASURED FROM THE OUTER FACE OF THE URINAL |
| | RIM TO THE BACK OF THE FIXTURE PER FBC ACC 605.2. |
| | ?D) PROVIDE DETAIL FOR COMPLIANT WALL HUNG LAVATORIES |
| | SHOWING COMPLIANCE WITH FBC ACC 606.3, |
| | ?E) 650/DETAIL 1 AND 3; DRINKING FOUNTAINS: OBJECTS |
| | WITH LEADING EDGES MORE THAN 27 INCHES AND NOT MORE |
| | THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE MORE |
| | THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION PATH |
| | PER FBC ACC 307.2. |
| | ?F) 650/DETAIL 1; DRINKING FOUNTAIN. PROVIDE SIDE |
| | ELEVATION SHOWING COMPLIANCE WITH FBC ACC 306, 602.6 |
| | AND 602.7. |
| | |
| | 2. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW |
| | PREVENTER FOR THE WATER SERVICE. |
| | |
| | 3. PER WPB FBC 107.2.1, PROVIDE A MANUFACTURER |
| | SPECIFICATION/INSTALLATION MANUAL AND A DETAIL FOR THE |
| | WATER SERVICE BACKFLOW PREVENTER. |
| | |
| | 5.GREASE INTERCEPTOR-CITY OF WEST PALM BEACH PUBLIC |
| | WORKS DEPT- STANDARD DETAIL GS-7-CONCRETE GRAVITY SEWER |
| | SYSTEM-GREASE INTERCEPTOR. NOTE4: MAXIMUM CAPACITY OF A |
| | CONCRETE GRAVITY GREASE INTERCEPTOR IS 1200 GALLONS. IF |
| | MORE CAPACITY IS REQUIRED INSTALLATION OF |
| | MULTI-CHAMBERED INTERCEPTORS OR MULTIPLE INTERCEPTORS |
| | IN SERIES. |
| | |
| | 6. PROVIDE CALCULATIONS FOR THE GREASE INTERCEPTOR |
| | WHICH IS TO BE FURNISHED UNDER THE CIVIL DRAWINGS. |
| | |
| | 7. PROVIDE A DETAIL OF THE GREASE INTERCEPTOR SHOWING |
| | COMPLIANCE WITH CITY OF WEST PALM BEACH PUBLIC WORKS |
| | DEPT- STANDARD DETAIL GS-7-CONCRETE GRAVITY SEWER |
| | SYSTEM-GREASE INTERCEPTOR AND FBC PL SECTION 1003. SHOW |
| | ALL CLEANOUTS (WITH TWO-WAY CLEANOUT FITTING) AND |
| | MANHOLES TO GRADE. DOWNSTREAM TWO-WAY CLEANOUT SHALL |
| | ALSO SERVE AS THE SAMPLING STATION. |
| | |
| | 8. IT IS NOTED THAT S2 AND S7 SINKS DISCHARGE TO GT1 |
| | INTERCEPTORS WHICH IN TURN CONNECT TO THE GREASY WASTE |
| | SYSTEM. PER WPB FBC 107.2.1, CLARIFY. FBC PL 1003.3.1 |
| | STATES A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL |
| | DEVICE SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM |
| | FIXTURES AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED |
| | IN FOOD PREPARATION AREAS, SUCH AS IN RESTAURANTS, |
| | HOTEL KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, |
| | FACTORY CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT |
| | SHALL INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES |
| | OR SIMILAR DEVICES; WOK STATIONS; FLOOR DRAINS OR SINKS |
| | INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH |
| | UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS. GREASE |
| | INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL |
| | RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT |
| | ALLOW FATS, OILS OR GREASE TO BE DISCHARGED. WHERE LACK |
| | OF SPACE OR OTHER CONSTRAINTS PREVENT THE INSTALLATION |
| | OR REPLACEMENT OF A GREASE INTERCEPTOR, ONE OR MORE |
| | GREASE INTERCEPTORS SHALL BE PERMITTED TO BE INSTALLED |
| | ON OR ABOVE THE FLOOR AND UPSTREAM OF AN EXISTING |
| | GREASE INTERCEPTOR. |
| | |
| | 9. THE PLANS(A900 ROOM FINISH SCHEDULE) ARE UNCLEAR AS |
| | TO THE WALL FINISHES ADJACENT TO MOP SINKS/SERVICE |
| | SINKS. PER WPB FBC 107.2.1, PROVIDE FINISH WALL |
| | SCHEDULE FOR ROOMS HOUSING SAID SINKS. FINISH SCHEDULE |
| | SHALL CLEARLY INDICATE COMPLIANCE WITH FBC PL 310.3 AND |
| | FBC 1210.2.2. WALLS AND PARTITIONS WITHIN 2 FEET (610 |
| | MM) OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL |
| | HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT |
| | OF NOT LESS THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND |
| | EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN |
| | SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY |
| | AFFECTED BY MOISTURE. PLEASE NOTE THAT FBC 1210.2.2 |
| | STIPULATES THAT THE MATERIAL BE "HARD." THE INTENT OF |
| | THIS SECTION IS THAT THE SURROUNDING MATERIAL SHOULD |
| | NOT BE OF A TYPE THAT IS EASILY DAMAGED SUCH THAT THE |
| | MATERIAL COULD BECOME ABSORBENT AND THUS, NOT READILY |
| | CLEANABLE AND SANITIZED. PAINTED DRYWALL, EVEN WHERE |
| | COATED WITH HIGHLY DURABLE PAINTS, DOES NOT MEET THE |
| | INTENT OF SECTION 1210.2.2. THE TYPICAL MATERIALS USED |
| | FOR THIS APPLICATION ARE CERAMIC TILE, FIBERGLASS |
| | REINFORCED PLASTIC (FRP) PANELS, PHENOLIC PANELS, |
| | LAMINATED PLASTIC PANELS, PAINTED STEEL AND STAINLESS |
| | STEEL. |
| | |
| | 10. S1 HAND SINKS ARE SHOWN ON SANITARY FLOOR PLANS AND |
| | RISER DIAGRAMS DISCHARGING TO THE GREASY WASTE. PER FBC |
| | PL 1003.3.1, DISCHARGE TO SANITARY, NOT THE GREASY |
| | WASTE. |
| | |
| | 11. PER WPB FBC 107.2.1, PLEASE CLARIFY. IS S7 IN THE |
| | WASH AREA A PRE-RINSE SINK SERVICING PW10 POT & PAN |
| | WASHER? |
| | |
| | 12. PER WPB FBC 107.2.1, PROVIDE MANUFACTURERS |
| | SPECIFICATION/INSTALLATION MANUALS FOR ALL OWNER |
| | PROVIDED EQUIPMENT. |
| | |
| | 12. P800/DETAIL BJWC-11 AND P001 EQUIPMENT SCHEDULE |
| | INDICATES TEMPERING VALVE TO COOL POT WASHER DETAIL. |
| | PER FBC PL 608.1, 608.3, SPECIFY AND FURNISH A BACKFLOW |
| | PREVENTER IN THE COLD WATER LINE TO THE DEVICE. |
| | INDICATE THE DEVICE IN DETAIL AND SCHEDULE. |
| | |
| | 13. P-100/PLUMBING & EQUIPMENT-ST1 SEDIMENT TRAP: MIFAB |
| | MI-SD-3; DESCRIPTION IS RECEPTACLE WITH DEEP SEAL TRAP |
| | AND INTERNAL VENT SYSTEM. 5/P-700 SANITARY RISER |
| | DIAGRAM AND 5/P-302 PLAN VIEW SHOWS A GRATED INLET |
| | STRUCTURE WITH A BOTTOM OUTLET CONNECTED TO A VENTED |
| | P-TRAP. MI-SD-3 SPECIFICATION SHEET SHOWS HORIZONTAL |
| | INLET AND OUTLET WITH A SEWER GAS STOPPER. PER WPB FBC |
| | 107.2.1, CLARIFY. ADDITIONALLY, PROVIDE A MANUFACTURERS |
| | DETAIL SHOWING A 6 INCH WATER TRAP SEAL AS REQUIRED BY |
| | FBC PL 1003.5. PER WPB FBC 107.2.1, PROVIDE |
| | MANUFACTURERS SPECIFICATION/INSTALLATION MANUALS FOR |
| | DEVICE. MAKE CHANGES IN RISER DIAGRAM AND PLAN VIEW AS |
| | IS APPROPRIATE. |
| | |
| | 14. P001/OWNER EQUIPMENT CONNECTION SCHEDULE. REGARDING |
| | S1 HAND SINK THERMAL MIXING VALVE, PER WPB FBC 107.2.1, |
| | PROVIDE TEMPERATURE SETTING INSTRUCTION. |
| | |
| | 15. PER WPB FBC 107.2.1, CLEARLY INDICATE ON THE PLANS |
| | (INCLUDING SCHEDULE) ANY SINK TO BE USED FOR FOOD PREP. |
| | PLEASE NOTE THAT PER FBC PL 802.1.1, EQUIPMENT AND |
| | FIXTURES UTILIZED FOR THE STORAGE, PREPARATION AND |
| | HANDLING OF FOOD SHALL DISCHARGE THROUGH AN INDIRECT |
| | WASTE PIPE BY MEANS OF AN AIR GAP. EACH WELL OF A |
| | MULTIPLE-COMPARTMENT SINK SHALL DISCHARGE INDEPENDENTLY |
| | TO A WASTE RECEPTOR. P800/BJWC-7 DETAIL FOR THREE |
| | COMPARTMENT SINK DOES NOT COMPLY WITH THIS REQUIREMENT. |
| | IF A THREE-COMPARTMENT SINK IS A DESIGNATED FOOD PREP |
| | SINK, PER WPB FBC 107.2.3, PROVIDE A DETAIL SHOWING |
| | COMPLIANCE WITH FBC PL 802.1.1. |
| | |
| | 16. PREP SINKS TO BE USED FOR WASHING OF PRODUCE OR |
| | OTHER NON-GREASY FOOD PRODUCT SHALL NOT DISCHARGE TO |
| | THE GREASY WASTE PER FBC PL 1003.3.1. PER WPB FBC |
| | 107.2.1, CLEARLY INDICATE ANY SUCH SINK ON THE PLANS, |
| | INCLUDING SCHEDULE AND COMPLY WITH FBC PL 1003.3.1. |
| | |
| | 17. P001/GENERAL NOTES; NOTE 6. REVISE NOTE TO REQUIRE |
| | 1/4 INCH PER FOOT MINIMUM FALL FOR PIPE SIZED 2-1/2 |
| | INCH OR SMALLER, 1/8 INCH PER FOOT MINIMUM FALL FOR |
| | PIPE SIZED 3 INCH TO 6 INCH PER FBC PL TABLE 704.1. |
| | |
| | 18. REFER TO ?BJS WEST PALM BEACH FL SPECS? IN |
| | SUPPORTING DOCUMENTS FOR MATERIAL, MEANS, METHODS, |
| | |
| | 19. N/A |
| | |
| | 20. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL |
| | BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND |
| | 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS |
| | STATING THE SAME. |
| | |
| | 21. PER WPB FBC 107.2.1, PROVIDE ON PIPE HANGER DETAIL |
| | BJWC-18 A NOTE STATING, "HORIZONTAL PIPE SHALL BE |
| | SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| | |
| | 22. P800/BJWC-10; VALVING ARRANGEMENT FOR COLD WATER |
| | WITH WATER HEATER. PER WPB FBC 107.2.1 PROVIDE THE |
| | FOLLOWING, PER FBC PL 602.1, PROVIDE A TEE BETWEEN THE |
| | POINT THE COLD WATER OUTLET PROTRUDES FROM THE WALL |
| | PLACED BETWEEN THE TEMPERING VALVE/FIXTURE AND THE |
| | WATER HEATER. PLACE A DEDICATED SHUTOFF VALVE IN THE |
| | COLD WATER UPSTREAM OF THE WATER HEATER AND THE |
| | TEMPERING VALVE. |
| | |
| | 23. P801/BJWC-14; SHOWS A TIGHT RADIUS FITTING AT THE |
| | BASE OF THE STORM LEADER. PER FBC PL 1101.6, 706.3 AND |
| | TABLE 706.3, PROVIDE A SHORT SWEEP. |
| | |
| | 24. P801/BJWC-8; SHOWS A TIGHT RADIUS FITTING AT THE |
| | BASE OF THE OVERFLOW DOWNSPOUT. PER FBC PL 1101.6, |
| | 706.3 AND TABLE 706.3, PROVIDE A SHORT SWEEP. |
| | |
| | 25. P801/BJWC-9; HORIZONTAL DRAIN VENT DETAIL. PER FBC |
| | PL 905.3 AND 905.4, VENTS SHALL CONNECT ABOVE THE |
| | CENTERLINE OF THE DRAIN OF THE HORIZONTAL DRAIN AND |
| | SHALL RISE VERTICALLY (45 DEGREES MINIMUM FROM THE |
| | HORIZONTAL) TO A POINT NOT LESS THAN 6 INCHES ABOVE THE |
| | FLOOD LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE |
| | BEING VENTED |
| | |
| | 26. P801/BJWC-07; PER WPB FBC 107.2.1, NOTE TERMINATION |
| | POINT OF T&P RELIEF VALVE COMPLYING WITH FBC PL 504.6. |
| | |
| | 27. P801/BJWC-05; PER WPB FBC 107.2.1, |
| | ?A) NOTE TERMINATION POINT OF T&P RELIEF VALVES |
| | COMPLYING WITH FBC PL 504.6. |
| | ?B) PROVIDE PAN DRAIN FOR HEAT RECLAIM TANK |
| | ?C) PROVIDE MANUFACTURERS SPECIFICATION/INSTALLATION |
| | MANUAL FOR HEAT RECLAIM SYSTEM INCLUDING THE TANK AND |
| | THE HEAT RECLAIM UNIT. PROVISION SHALL BE MADE TO |
| | PREVENT CROSS CONTAMINATION BETWEEN POTABLE WATER AND |
| | REFRIGERATION. FBC PL 608. |
| | |
| | 28. P801/BJWC-06; PER WPB FBC 107.2.1, NOTE TERMINATION |
| | POINT OF T&P RELIEF VALVE COMPLYING WITH FBC PL 504.6. |
| | |
| | 29. P801/BJWC-06; PER WPB FBC 107.2.1, |
| | ?A) NOTE TERMINATION POINT OF T&P RELIEF VALVE AND PAN |
| | DRAIN COMPLYING WITH FBC PL 504.6. PLEASE NOTE THAT PER |
| | FBC PL CHAPTER 2, DEFINITIONS, A WASTE RECEPTOR IS |
| | DEFINED AS A FLOOR SINK, STANDPIPE, HUB DRAIN OR FLOOR |
| | DRAIN THAT RECEIVES THE DISCHARGE OF ONE OR MORE |
| | INDIRECT WASTE PIPES. A MOP SINK DOES NOT QUALIFY AS A |
| | WASTE RECEPTOR. |
| | ?B) PROVIDE A STRUCTURAL DETAIL FOR THE WATER HEATER |
| | WALL SUPPORT TO INCLUDE STRUCTURAL BRACKETS/FLOOR AND |
| | ANCHORS. A MANUFACTURED KIT MADE FOR THIS APPLICATION |
| | MAY BE SPECIFIED AND MANUFACTURERS |
| | SPECIFICATION/INSTALLATION MANUAL SUBMITTED AS LONG AS |
| | IT MEETS THE INTENT. |
| | |
| | 30. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR TWO WAY |
| | CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND THE |
| | BUILDING SEWER. SEE FBC PL 708.1.3, 708.1.8. |
| | |
| | 31. P700/DETAIL 2: P-5 UTILITY SINK IS S-TRAPPED. |
| | REVISE TO COMPLY WITH FBC PL 909.1 AND 1002.3(5). |
| | |
| | 32. P001 PLUMBING FIXTURE SCHEDULE: |
| | ?A) INDICATES WATER CLOSETS PB1A AND PB1B ARE IDENTICAL |
| | IN SPECIFICATIONS. LOOKING AT THE PLANS, IT APPEARS |
| | THAT THE DIFFERENCE IS THAT ONE (PB1B) IS TO BE ADA |
| | COMPLIANT. PER WPB FBC 107.2.1P, INDICATE IN P001 |
| | PLUMBING FIXTURE SCHEDULE WHICH IS ADA COMPLIANT. |
| | ?B) INDICATES WATER CLOSETS PB1A AND PB1B ARE IDENTICAL |
| | IN SPECIFICATIONS. LOOKING AT THE PLANS, IT APPEARS |
| | THAT THE DIFFERENCE IS THAT ONE (PB1B) IS TO BE ADA |
| | COMPLIANT. PER WPB FBC 107.2.1P, INDICATE IN P001 |
| | PLUMBING FIXTURE SCHEDULE WHICH IS ADA COMPLIANT. |
| | ?C) URINAL; PER WPB FBC 107.2.1, PROVIDE IN PLUMBING |
| | SCHEDULE A DESIGNATION FOR THE ADA COMPLIANT URINAL AND |
| | IDENTIFY SAME ON THE PIPING PLANS. |
| | ?D) LAVATOTIES; PER WPB FBC 107.2.1, PROVIDE IN |
| | PLUMBING SCHEDULE A DESIGNATION FOR ADA COMPLIANT |
| | LAVATORIES AND IDENTIFY SAME ON THE PIPING PLANS. |
| | |
| | 33. PER P001 PLUMBING FIXTURE SCHEDULE, PB1A AND PB1B |
| | WATER CLOSETS ARE TO DISCHARGE TO FLOOR MOUNTED CARRIER |
| | SYSTEM (EQUAL TO) JR SMITH 210Y WHICH IS A HORIZONTAL |
| | (ABOVE THE FLOOR) DRAINAGE PATTERN OR A 410Y WHICH IS A |
| | VERTICAL DRAINAGE (THROUGH THE FLOOR) DRAINAGE PATTERN. |
| | PROVIDED WITH FLOOR. WATER CLOSETS TO DISCHARGE TO A |
| | THROUGH THE WALL WASTE INLET. SANITARY RISER DIAGRAMS |
| | ALL SHOW HORIZONTAL BRANCH BELOW GRADE WITH FLOOR |
| | MOUNTED CONNECTIONS DOWN TO CLOSET BEND AND CONNECTING |
| | HORIZONTALLY TO HORIZONTAL BRANCH. PER WPB FBC 107.2.1, |
| | RISER DIAGRAMS SHALL DEPICT WATER CLOSETS DISCHARGING |
| | TO FLOOR MOUNTED CARRIER. DEPICTION SHALL NOTE VERTICAL |
| | OR HORIZONTAL DRAIN PATTERN AS IS APPLICABLE TO THE |
| | SITUATION. VENTING OF WATER CLOSETS SHALL CONNECT TO |
| | CARRIER IN ACCORDANCE WITH FBC PL 909.1 AND/OR AS |
| | APPLICABLE TO THE SITUATION, SECTIONS 910, 911AND 914. |
| | P302 AND P100 SHALL REFLECT THE CHANGES. |
| | |
| | 34. FLOOR DRAINS SHOWN ON P700/DETAILS 2 AND 3, THAT |
| | ARE NOT CONNECTED TO A CIRCUIT VENTED BRANCH AS ALLOWED |
| | IN FBC PL 914.1.1 SHALL BE VENTED IN ACCORDANCE WITH |
| | FBC PL 909.1 AND SECTION 910 OR 911. THE DRY PORTION OF |
| | THE VENT SHALL BE IN ACCORDANCE WITH FBC PL 905.3, |
| | 905.4 AND 905.5. |
| | |
| | 35. PER WPB FBC 107.2.1, PROVIDE PLAN VIEW AND RISER |
| | DIAGRAM TO ADDRESS STORM DRAINAGE OF THE ROOF. PROVIDE |
| | CALCULATIONS FOR SIZING OF HORIZONTAL PIPING (INCLUDING |
| | SLOPE OF PIPE), VERTICAL LEADERS AND DOWNSPOUTS. PLANS |
| | SHALL COMPLY WITH FBC PL CHAPTER 11 INCLUDING BUT NOT |
| | LIMITED TO SECTION 1106.1, FIGURE 1106.1 100YR. 1 HOUR |
| | RAINFALL (INCHES) EASTERN UNITED STATES, SECTION |
| | 1106.2, TABLE 1106.2, SECTION 1106.3, TABLE 1106.3, |
| | SECTION 1106.4, TABLE 1106.4, SECTION 1108.1, SECTION |
| | 1108.2 AND SECTION 1108.3. |
| | |
| | 36. PER WPB FBC 107.2.1 AND WPB FBC 107.3.5.1.3, |
| | PROVIDE A RISER DIAGRAM FOR THE HOT AND COLD WATER |
| | DISTRIBUTION. SHOW SIZING, VALVES, WATER HAMMER |
| | ARRESTORS, BACKFLOW PREVENTERS, TRAP PRIMER |
| | CONNECTIONS, FIXTURE/EQUIPMENT CONNECTIONS (ID |
| | FIXTURES/EQUIPMENT TO CORRESPOND TO FIXTURE/EQUIPMENT |
| | SCHEDULES) AND APPURTENANCES. FOR CONNECTIONS TO |
| | FIXTURES/EQUIPMENT THAT ARE DETAILED ON P800/P801, A |
| | NOTE REFERRING TO APPLICABLE DETAIL SHALL BE PROVIDED; |
| | VALVING, WHAS ETC. WILL NOT BE REQUIRED TO BE SHOWN IN |
| | RISER DIAGRAM. |
| | |
| | 37. PER WPB FBC 107.2.1, PROVIDE A NOTE ON THE PLANS |
| | STATING ?REFER TO BJS WEST PALM BEACH FL SPECS 15010 |
| | AND 15400 FOR EQUIPMENT, FIXTURES, APPURTENANCES, |
| | MATERIALS, MEANS AND METHOD SPECIFICATIONS?. |
| | 38. RE: BJS SPEC 15400-2.16-D. BALL VALVES SHALL BE |
| | LEAD FREE. |
| | |
| | 39. RE: BJS SPEC 15400-2.17. PER WPB FBC 107.2.1, |
| | SPECIFY THICKNESSES FOR INSULATION FOR THE DIFFERENT |
| | APPLICATIONS INCLUDING ABOVE GROUND CONDENSATE. HOT |
| | WATER SHALL BE INSULATED AS REQUIRED BY FBC EC E607.5 |
| | AND EC C404.4. |
| | |
| | 40. RE: BJS SPEC 15400-3.2-B. SOLDER SHALL BE LEAD FREE |
| | COMPLYING WITH FBC PL 605.2.1. |
| | |
| | 41. RE: BJS SPEC 15400-3.2-C. BRASS SHALL BE LEAD FREE |
| | COMPLYING WITH FBC PL 605.2.1. |
| | |
| | 39. RE: BJS SPEC 15400-3.5-B. PER WPB FBC 107.2.1, |
| | SPECIFY THICKNESSES FOR INSULATION OF THE DOMESTIC |
| | WATER. HOT WATER SHALL BE INSULATED AS REQUIRED BY FBC |
| | EC E607.5 AND EC C404.4. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21091182 751 W EXECUTIVE CENTER DR |
| | |