2021-11-12 15:40:301ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21091182
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT THE COMCHECK USING THE CURRENT FLORIDA
 2020 BUILDING CODE EDITION. FBC 107.2.1
  
 2) PLEASE HAVE THE DESIGNER THAT SUBMITTED THE COMCHECK
 TO SIGN AND DATE THE REPORT. F.S. 471, 481
  
 3) PLEASE ADD NOTE TO DRAWINGS STATING THE KITCHEN HOOD
 SYSTEM WILL NEED A SEPARATE PERMIT APPLICATION, REVIEW
 AND DRAWINGS AS THEY WILL NOT BE REVIEWED UNDER THIS
 PERMIT.
  
 4) PLEASE ADD A NOTE TO THE DRAWINGS THAT THE
 REFRIGERATION SYSTEMS WILL NEED A SEPARATE PERMIT
 APPLICATION, REVIEW AND DRAWINGS AS THEY WILL NOT BE
 REVIEWED UNDER THIS PERMIT.
  
 5) SHEET M002: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS BASED ON THE CURRENT 2020 FBC M.
  
 6) SHEET M002: PLEASE PROVIDE OUTDOOR AIR CALCULATIONS
 BASED ON EACH USE OF SPACE DETERMINED BY USING TABLE
 403.3.1.1 OCCUPANCY CLASSIFICATION AND SECTION
 403.3.1.1 FOR THE OCCUPANT DENSITY TO DETERMINE THE
 OCCUPANT COUNT FOR EACH USE OF SPACE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  