| 2021-11-12 15:40:30 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21091182 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SUBMIT THE COMCHECK USING THE CURRENT FLORIDA |
| | 2020 BUILDING CODE EDITION. FBC 107.2.1 |
| | |
| | 2) PLEASE HAVE THE DESIGNER THAT SUBMITTED THE COMCHECK |
| | TO SIGN AND DATE THE REPORT. F.S. 471, 481 |
| | |
| | 3) PLEASE ADD NOTE TO DRAWINGS STATING THE KITCHEN HOOD |
| | SYSTEM WILL NEED A SEPARATE PERMIT APPLICATION, REVIEW |
| | AND DRAWINGS AS THEY WILL NOT BE REVIEWED UNDER THIS |
| | PERMIT. |
| | |
| | 4) PLEASE ADD A NOTE TO THE DRAWINGS THAT THE |
| | REFRIGERATION SYSTEMS WILL NEED A SEPARATE PERMIT |
| | APPLICATION, REVIEW AND DRAWINGS AS THEY WILL NOT BE |
| | REVIEWED UNDER THIS PERMIT. |
| | |
| | 5) SHEET M002: PLEASE PROVIDE THE OUTDOOR AIR |
| | CALCULATIONS BASED ON THE CURRENT 2020 FBC M. |
| | |
| | 6) SHEET M002: PLEASE PROVIDE OUTDOOR AIR CALCULATIONS |
| | BASED ON EACH USE OF SPACE DETERMINED BY USING TABLE |
| | 403.3.1.1 OCCUPANCY CLASSIFICATION AND SECTION |
| | 403.3.1.1 FOR THE OCCUPANT DENSITY TO DETERMINE THE |
| | OCCUPANT COUNT FOR EACH USE OF SPACE. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |