Plan Review Notes
Plan Review Notes For Permit 21091182
Permit Number 21091182
Review Stop G
Sequence Number 1
Notes
Date Text
2021-11-30 13:50:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21091182 751 W EXECUTIVE CENTER DR
  
 1ST REVIEW
 GAS COMMENTS: DENIED
  
 1.PER WPB FBC 107.2.1, PROVIDE A NOTE ON THE PLANS
 STATING ?REFER TO BJS WEST PALM BEACH FL SPECS 15010
 AND 15140 FOR EQUIPMENT, FIXTURES, APPURTENANCES,
 MATERIALS, MEANS AND METHOD SPECIFICATIONS?.
  
 2. RE: BJS SPEC 15400-3.3-C. PIPING SHALL BE INSTALLED
 IN ACCORDANCE WITH THE FLORIDA FUEL GAS CODE 2020 7TH
 EDITION
  
 3.PER WPB FBC 107.2.1, PROVIDE THROUGH THE ROOF
 DETAIL(S) AND/OR THROUGH THE WALL DETAILS FOR SEALED
 INTAKE AIR AND FLUE EXHAUST VENTS FOR GAS FIRED WATER
 HEATERS (SEE P801 DETAILS BJWC -05 AND BJWC-07). ?A)
 ROOF PENETRATIONS: SHOW THE TYPE, SIZE, TERMINATION
 POINT, HEIGHT ABOVE THE ROOF AND ANCHORING DETAILS OF
 THE GAS VENT(S).
 ?B) SIDE WALL PENETRATIONS: SHOW THE TYPE, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE GROUND AND
 ANCHORING DETAILS OF THE GAS VENT(S).
 ?C) ROOF LOCATIONS ARE SHOWN ON M200 FOR WHG-1 AND
 WHG-3, BUT NOTHING FOR WHG-2. NOTE DISTANCES FROM ANY
 FRESH AIR INTAKES. COMPLY WITH FBC FG SECS. 502 THRU
 505 AND PER FBC FG 304.1, MANUFACTURERS INSTRUCTIONS.
 ?D) NOTE 6 ON M200 INDICATES THE VENTS ARE CONCENTRIC.
 PROVIDE MANUFACTURERS SPECIFICATION/INSTALLATION
 MANUALS FOR ANY CONCENTRIC VENTS. CONFIRM THAT THEY MAY
 BE USED IN WHICHEVER APPLICATION IS REQUIRED; VERTICAL
 OR HORIZONTAL.
 ?E) PROVIDE MATERIAL SPECIFICATION APPLICABLE TO THE
 SEALED INTAKE AIR AND FLUE EXHAUST VENTS.
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL (INCLUDING VENTING) FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC FG SEC. 402.2, AND 301.3.
  
 5.PER WPB FBC 107.3.5.1.5 AND 107.2.1, SUBMIT A SIZED
 ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL
 CUT SECTIONS OF PIPE PER FBC FG, SECS. 402.4.1,
 402.4.2. CLEARLY SHOW THE LOCATION OF ALL MP
 (STEP-DOWN) REGULATORS, VALVES AND UNIONS AND THE
 PIPING BETWEEN MP REGULATOR AND APPLIANCE. A LISTED
 SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF
 EACH MP REGULATOR. FBC FG SEC.409.4. INDICATE EACH
 APPLIANCE/EQUIPMENT POINT OF CONNECTION AND BTUS.
  
 6.PER WPB FBC 107.3.5.1.5 AND 107.2.1, INDICATE THE
 DELIVERY PRESSURE (PSI) OF THE SYSTEM(S) ON THE PLAN
 PER FBC FG SEC.402.1, 402.4.3 THRU 402.6. PLEASE NOTE
 THAT IF MP REGULATORS ARE REQUIRED FOR THE APPLIANCES
 THAT THE DOWNSTREAM SIDE OF THE REGULATOR IS A SECOND
 SYSTEM AND ARE CONSIDERED A SEPARATE SYSTEM AND TABLE
 FOR SIZING SHALL BE PROVIDED. P200 PROVIDES INFORMATION
 FOR THE 2PSI SYSTEM, BUT NOTHING FOR THE SYSTEMS
 DOWNSTREAM OF THE MP REGULATORS
  
 7.PER WPB FBC 107.3.5.1.5 AND 107.2.1, INDICATE TYPE OF
 GAS (NATURAL OR PROPANE)
  
 8.PER WPB FBC 107.3.5.1.5 AND 107.2.1, LIST TABLES AND
 MATERIAL FOR EACH SYSTEM
 REFER TO THE FBC FG SECS.401.8, 402.2, AND TABLES 402.4
 (1) THRU 402.4 (37). PLEASE NOTE THAT IF MP REGULATORS
 ARE REQUIRED FOR THE APPLIANCES THAT THE DOWNSTREAM
 SIDE OF THE REGULATOR IS A SECOND SYSTEM AND ARE
 CONSIDERED A SEPARATE SYSTEM.
  
 9.PER WPB FBC 107.3.5.1.5 AND 107.2.1, PROVIDE DISTANCE
 FROM THE POINT OF DELIVERY, (GAS METER / MP REGULATOR)
 TO THE FURTHEST POINT (PER SYSTEM). PLEASE NOTE THAT IF
 MP REGULATORS ARE REQUIRED FOR THE APPLIANCES THAT THE
 DOWNSTREAM SIDE OF THE REGULATOR IS A SECOND SYSTEM AND
 ARE CONSIDERED A SEPARATE SYSTEM. P200 PROVIDES
 INFORMATION FOR THE 2PSI SYSTEM, BUT NOTHING FOR THE
 SYSTEMS DOWNSTREAM OF THE MP REGULATORS
  
 10.PER WPB FBC 107.3.5.1.5 AND 107.2.1, PROVIDE DETAIL
 OF GAS METER/REGULATOR
  
 11.SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE FBC
 FG CODE SEC.304.1, FOR GAS EQUIPMENT OTHER THAN THE GAS
 FIRED WATER HEATERS AND INDICATE HOW REQUIREMENTS ARE
 SATISFIED.
  
 12. REGARDING MP REGULATORS, PER WPB FBC 107.3.5.1.5
 AND 107.2.1,
 ?A) SUBMIT MANUFACTURER?S SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE PRESSURE REGULATORS AND FOR VENT
 LIMITING DEVICES (ALLOWED PER FBC FG 410.3/EXCEPTION).
 IF A VENT LIMITING DEVICE IS NOT SPECIFIED, PROVIDE
 VENT PIPING, SIZING, ROUTING AND TERMINATION; COMPLY
 WITH FBC FG 410.3.1. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. FBC FG SEC.410.1
 ?B) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4.
 ?C) PROVIDE A DETAIL FOR MP (STEP-DOWN) REGULATORS.
 SHOW COMPLIANCE WITH FBC FG 409.4, 410.1, 410.2-SUB
 SECTIONS 1 THROUGH 7.
 ?D) SEE P801 DETAILS BJWC -05, BJWC-07, BJWC-02, P800
 DETAILS BJWC -08 AND BJWC -12. THE SYSTEM IS 2PSI AND
 THERE IS A MP REGULATOR SERVICING THE ROOFTOP AC UNIT
 AND THE CHICKEN OVENS. HOWEVER, THERE ARE NO MP
 REGULATORS SHOWN FOR THE GAS WATER HEATERS OR THE
 BAKERY OVEN. PER WPB FBC 107.2.1, CLARIFY ON THE
 DETAIL, RECONCILING WITH REQUIRED ISOMETRIC, P-200,
 P401 AND P402. ALL DRAWINGS SHALL MATCH.
  
 13. SEE P801 DETAIL BJWC-02 AND P100. DETAIL BJWC-02
 INDICATES GAS PIPING SUSPENDED IN THE JOIST SPACE UNDER
 THE ROOF. P100 AND P200 AT BUILDING ENTRY POINT
 INDICATES GAS PIPING SUSPENDED IN THE JOIST SPACE UNDER
 THE ROOF. P200 AT LOCATIONS FOR DROPS TO FLOOR LEVEL
 EQUIPMENT INDICATES PIPING AND MP REGULATORS LOCATED ON
 THE ROOF AND DROPPING DOWN THROUGH THE ROOF TO THE
 FLOOR LEVEL EQUIPMENT; PIPING TO RTUS SEEMS TO MATCH
 P801 DETAIL BJWC-02. PER WPB FBC 107.2.1, CLARIFY.
  
 14. SEE P801 DETAIL BJWC-02 AND BJS SPEC 15400-3.3-H;
 PIPE SUPPORTS. PER WPB FBC 107.2.1, PLEASE CLARIFY
 WHICH SUPPORT SHALL BE USED ON THE ROOF. MIFAB CXP PIPE
 SUPPORTS OR ROOF TOP BLOX-01 PIPE SUPPORTS. THE TWO
 PRODUCTS DIFFER IN FUNCTION AND THE ROOF TOP BLOX-01
 APPEARS TO BETTER SUIT THE INSTALLATION AT THE RTU.
 PROVIDE A CROSS SECTIONAL DETAIL OF THE ROOF SUPPORT
 SHOWING ALL COMPONENTS AND ANCHORING/SECURING TO ROOF.
  
 15.CHICKEN ROTISSERIES: PER WPB FBC 107.2.1, PROVIDE
 DETAIL FOR EMERGENCY HOOD SHUT DOWN VALVE SHOWING
 COMPLIANCE WITH NFPA 96-17, SECTIONS 10.4 AND 10.5.
 ASSEMBLY SHALL BE BELOW THE CEILING. THE MANUAL SHUTOFF
 VALVE SHALL BE UPSTREAM. UNION TO BE DOWN STREAM OF
 MANUAL VALVE.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21091182 751 W EXECUTIVE CENTER DR