| 2021-11-30 13:50:05 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21091182 751 W EXECUTIVE CENTER DR |
| | |
| | 1ST REVIEW |
| | GAS COMMENTS: DENIED |
| | |
| | 1.PER WPB FBC 107.2.1, PROVIDE A NOTE ON THE PLANS |
| | STATING ?REFER TO BJS WEST PALM BEACH FL SPECS 15010 |
| | AND 15140 FOR EQUIPMENT, FIXTURES, APPURTENANCES, |
| | MATERIALS, MEANS AND METHOD SPECIFICATIONS?. |
| | |
| | 2. RE: BJS SPEC 15400-3.3-C. PIPING SHALL BE INSTALLED |
| | IN ACCORDANCE WITH THE FLORIDA FUEL GAS CODE 2020 7TH |
| | EDITION |
| | |
| | 3.PER WPB FBC 107.2.1, PROVIDE THROUGH THE ROOF |
| | DETAIL(S) AND/OR THROUGH THE WALL DETAILS FOR SEALED |
| | INTAKE AIR AND FLUE EXHAUST VENTS FOR GAS FIRED WATER |
| | HEATERS (SEE P801 DETAILS BJWC -05 AND BJWC-07). ?A) |
| | ROOF PENETRATIONS: SHOW THE TYPE, SIZE, TERMINATION |
| | POINT, HEIGHT ABOVE THE ROOF AND ANCHORING DETAILS OF |
| | THE GAS VENT(S). |
| | ?B) SIDE WALL PENETRATIONS: SHOW THE TYPE, SIZE, |
| | TERMINATION POINT, HEIGHT ABOVE THE GROUND AND |
| | ANCHORING DETAILS OF THE GAS VENT(S). |
| | ?C) ROOF LOCATIONS ARE SHOWN ON M200 FOR WHG-1 AND |
| | WHG-3, BUT NOTHING FOR WHG-2. NOTE DISTANCES FROM ANY |
| | FRESH AIR INTAKES. COMPLY WITH FBC FG SECS. 502 THRU |
| | 505 AND PER FBC FG 304.1, MANUFACTURERS INSTRUCTIONS. |
| | ?D) NOTE 6 ON M200 INDICATES THE VENTS ARE CONCENTRIC. |
| | PROVIDE MANUFACTURERS SPECIFICATION/INSTALLATION |
| | MANUALS FOR ANY CONCENTRIC VENTS. CONFIRM THAT THEY MAY |
| | BE USED IN WHICHEVER APPLICATION IS REQUIRED; VERTICAL |
| | OR HORIZONTAL. |
| | ?E) PROVIDE MATERIAL SPECIFICATION APPLICABLE TO THE |
| | SEALED INTAKE AIR AND FLUE EXHAUST VENTS. |
| | |
| | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL (INCLUDING VENTING) FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC FG SEC. 402.2, AND 301.3. |
| | |
| | 5.PER WPB FBC 107.3.5.1.5 AND 107.2.1, SUBMIT A SIZED |
| | ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL |
| | CUT SECTIONS OF PIPE PER FBC FG, SECS. 402.4.1, |
| | 402.4.2. CLEARLY SHOW THE LOCATION OF ALL MP |
| | (STEP-DOWN) REGULATORS, VALVES AND UNIONS AND THE |
| | PIPING BETWEEN MP REGULATOR AND APPLIANCE. A LISTED |
| | SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF |
| | EACH MP REGULATOR. FBC FG SEC.409.4. INDICATE EACH |
| | APPLIANCE/EQUIPMENT POINT OF CONNECTION AND BTUS. |
| | |
| | 6.PER WPB FBC 107.3.5.1.5 AND 107.2.1, INDICATE THE |
| | DELIVERY PRESSURE (PSI) OF THE SYSTEM(S) ON THE PLAN |
| | PER FBC FG SEC.402.1, 402.4.3 THRU 402.6. PLEASE NOTE |
| | THAT IF MP REGULATORS ARE REQUIRED FOR THE APPLIANCES |
| | THAT THE DOWNSTREAM SIDE OF THE REGULATOR IS A SECOND |
| | SYSTEM AND ARE CONSIDERED A SEPARATE SYSTEM AND TABLE |
| | FOR SIZING SHALL BE PROVIDED. P200 PROVIDES INFORMATION |
| | FOR THE 2PSI SYSTEM, BUT NOTHING FOR THE SYSTEMS |
| | DOWNSTREAM OF THE MP REGULATORS |
| | |
| | 7.PER WPB FBC 107.3.5.1.5 AND 107.2.1, INDICATE TYPE OF |
| | GAS (NATURAL OR PROPANE) |
| | |
| | 8.PER WPB FBC 107.3.5.1.5 AND 107.2.1, LIST TABLES AND |
| | MATERIAL FOR EACH SYSTEM |
| | REFER TO THE FBC FG SECS.401.8, 402.2, AND TABLES 402.4 |
| | (1) THRU 402.4 (37). PLEASE NOTE THAT IF MP REGULATORS |
| | ARE REQUIRED FOR THE APPLIANCES THAT THE DOWNSTREAM |
| | SIDE OF THE REGULATOR IS A SECOND SYSTEM AND ARE |
| | CONSIDERED A SEPARATE SYSTEM. |
| | |
| | 9.PER WPB FBC 107.3.5.1.5 AND 107.2.1, PROVIDE DISTANCE |
| | FROM THE POINT OF DELIVERY, (GAS METER / MP REGULATOR) |
| | TO THE FURTHEST POINT (PER SYSTEM). PLEASE NOTE THAT IF |
| | MP REGULATORS ARE REQUIRED FOR THE APPLIANCES THAT THE |
| | DOWNSTREAM SIDE OF THE REGULATOR IS A SECOND SYSTEM AND |
| | ARE CONSIDERED A SEPARATE SYSTEM. P200 PROVIDES |
| | INFORMATION FOR THE 2PSI SYSTEM, BUT NOTHING FOR THE |
| | SYSTEMS DOWNSTREAM OF THE MP REGULATORS |
| | |
| | 10.PER WPB FBC 107.3.5.1.5 AND 107.2.1, PROVIDE DETAIL |
| | OF GAS METER/REGULATOR |
| | |
| | 11.SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE FBC |
| | FG CODE SEC.304.1, FOR GAS EQUIPMENT OTHER THAN THE GAS |
| | FIRED WATER HEATERS AND INDICATE HOW REQUIREMENTS ARE |
| | SATISFIED. |
| | |
| | 12. REGARDING MP REGULATORS, PER WPB FBC 107.3.5.1.5 |
| | AND 107.2.1, |
| | ?A) SUBMIT MANUFACTURER?S SPECIFICATIONS/INSTALLATION |
| | MANUAL FOR THE PRESSURE REGULATORS AND FOR VENT |
| | LIMITING DEVICES (ALLOWED PER FBC FG 410.3/EXCEPTION). |
| | IF A VENT LIMITING DEVICE IS NOT SPECIFIED, PROVIDE |
| | VENT PIPING, SIZING, ROUTING AND TERMINATION; COMPLY |
| | WITH FBC FG 410.3.1. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. FBC FG SEC.410.1 |
| | ?B) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS |
| | SEC.409.4. |
| | ?C) PROVIDE A DETAIL FOR MP (STEP-DOWN) REGULATORS. |
| | SHOW COMPLIANCE WITH FBC FG 409.4, 410.1, 410.2-SUB |
| | SECTIONS 1 THROUGH 7. |
| | ?D) SEE P801 DETAILS BJWC -05, BJWC-07, BJWC-02, P800 |
| | DETAILS BJWC -08 AND BJWC -12. THE SYSTEM IS 2PSI AND |
| | THERE IS A MP REGULATOR SERVICING THE ROOFTOP AC UNIT |
| | AND THE CHICKEN OVENS. HOWEVER, THERE ARE NO MP |
| | REGULATORS SHOWN FOR THE GAS WATER HEATERS OR THE |
| | BAKERY OVEN. PER WPB FBC 107.2.1, CLARIFY ON THE |
| | DETAIL, RECONCILING WITH REQUIRED ISOMETRIC, P-200, |
| | P401 AND P402. ALL DRAWINGS SHALL MATCH. |
| | |
| | 13. SEE P801 DETAIL BJWC-02 AND P100. DETAIL BJWC-02 |
| | INDICATES GAS PIPING SUSPENDED IN THE JOIST SPACE UNDER |
| | THE ROOF. P100 AND P200 AT BUILDING ENTRY POINT |
| | INDICATES GAS PIPING SUSPENDED IN THE JOIST SPACE UNDER |
| | THE ROOF. P200 AT LOCATIONS FOR DROPS TO FLOOR LEVEL |
| | EQUIPMENT INDICATES PIPING AND MP REGULATORS LOCATED ON |
| | THE ROOF AND DROPPING DOWN THROUGH THE ROOF TO THE |
| | FLOOR LEVEL EQUIPMENT; PIPING TO RTUS SEEMS TO MATCH |
| | P801 DETAIL BJWC-02. PER WPB FBC 107.2.1, CLARIFY. |
| | |
| | 14. SEE P801 DETAIL BJWC-02 AND BJS SPEC 15400-3.3-H; |
| | PIPE SUPPORTS. PER WPB FBC 107.2.1, PLEASE CLARIFY |
| | WHICH SUPPORT SHALL BE USED ON THE ROOF. MIFAB CXP PIPE |
| | SUPPORTS OR ROOF TOP BLOX-01 PIPE SUPPORTS. THE TWO |
| | PRODUCTS DIFFER IN FUNCTION AND THE ROOF TOP BLOX-01 |
| | APPEARS TO BETTER SUIT THE INSTALLATION AT THE RTU. |
| | PROVIDE A CROSS SECTIONAL DETAIL OF THE ROOF SUPPORT |
| | SHOWING ALL COMPONENTS AND ANCHORING/SECURING TO ROOF. |
| | |
| | 15.CHICKEN ROTISSERIES: PER WPB FBC 107.2.1, PROVIDE |
| | DETAIL FOR EMERGENCY HOOD SHUT DOWN VALVE SHOWING |
| | COMPLIANCE WITH NFPA 96-17, SECTIONS 10.4 AND 10.5. |
| | ASSEMBLY SHALL BE BELOW THE CEILING. THE MANUAL SHUTOFF |
| | VALVE SHALL BE UPSTREAM. UNION TO BE DOWN STREAM OF |
| | MANUAL VALVE. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |