| 2021-12-16 09:32:55 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| | PERMIT 21091179 |
| | 12/16/21 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 11 & 12: THE GAS PIPING PLAN SHOWS AN |
| | INDIVIDUAL BRANCH PIPE TO THE FIREPLACE DIRECTLY |
| | CONNECTED TO THE MAIN 2 PSI PE PIPE, BUT THE GAS |
| | ISOMETRIC SHOWS THE FIREPLACE PIPE CONNECTION ON THE |
| | BRANCH LINE SUPPLYING THE WATER HEATER- SEC. G2413.1 |
| | FBC RES. |
| | |
| | 2) SHEET 12 GAS ISOMETRIC: PLEASE LIST THE PIPE SIZING |
| | TABLES FOR THE LOW PRESSURE SCHEDULE 40 METALLIC- |
| | G2413.4(1), AND THE LOW PRESSURE CSST- G2413.4(5) FBC |
| | RES. |
| | |
| | 3) GAS ISOMETRIC: BASED ON TABLE G2413.4(1) THE |
| | 3/4-INCH SCHEDULE 40 BRANCH SUPPLYING TANKLESS WH #1 |
| | AND FIREPLACE IS UNDERSIZED- MINIMUM 1-INCH REQUIRED. |
| | |
| | 3) GAS ISOMETRIC: SHOW THE TYPES AND SIZES OF GAS |
| | PIPING FROM THE LOW PRESSURE REGULATOR TO TANKLESS WH |
| | #2 AND THE DRYER- SEC. G2413.3. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |